Installation Guide RN5000US
58
9.3 Trip Limits / Trip Times
Nominal
Freq. (Hz)
Trip Limit (Hz)
Trip Freq. (Hz)
Trip Times (s)
> 60.5
60.45 - 60.55
max. 0.1602
< 59.3
59.25 - 59.35
max. 0.1602
60
Nominal
Voltage (V)
Trip Limit
Trip Voltages
Line-to-Neutral (V)*
Trip Times (s)
50%
119 - 121
max. 0.1602
88%
210 - 212
max. 2.002
110%
261 - 263
max. 1.001
120%
287 - 289
max. 0.1602
240
NOTE:
This unit or system is provided with fixed trip limits and shall not be
aggregated above 30 kW on a single Point of Common Connection.
9.4 Torque Values and Wire Sizes
Terminal
Install Torque
(Nm / ft-lbs)
Wire Size
Green AC & DC Terminal Blocks (Phoenix)
2.5 / 1.8
10 AWG
Cover Machine Screws
6 / 4.4
--