1.800.627.4499
46
Integral Indirect Gas-Fired Heat Module
OPTION
8.2 IGNITION CONTROLLER
Problems with ignition can often be diagnosed by viewing the LED indicator on the Series 5
Ignition Controller that is used on all models. The controller monitors operation of the module
and will shut down the module for a number of reasons and provide a flashing error code. It
also indicates the stages of ignition and correct operation.
ERROR CODE:
Solid Green = Normal operation
1 Red Flash = No Flame During Trial
2 Red Flashes = Flame Sense Fail
3 Red Flashes = Pilot Main Relay Fail
4 Red Flashes = Multiple Flame Loss
5 Red Flashes = Rollout Error
6 Red Flashes = APS Airflow Error
7 Red Flashes = Internal Control Error
Solid Red = Line Voltage Error
FIGURE 8.2.0 SERIES 5 IGNITION CONTROLLER
LED
TROUBLESHOOTING