33
1.800.627.4499
Integral Indirect Gas-Fired Heat Module
OPTION
All piping should be clean and free of any foreign material. Foreign material entering the gas
train can cause damage.
IMPORTANT
DO NOT connect the module to gas types other than what is specified and DO NOT connect
the unit to gas pressures that are outside the pressure range shown on the unit label.
IMPORTANT
Before applying gas to the valves, test the gas pressure to make sure it is less than 13.5
InWC. Pressures greater than 13.5 inches WC will damage the gas valves.
IMPORTANT
INSTALLATION
5.8.2 Determine Gas Supply Requirements
The data sticker located on the outside of the unit lists the requirements for the gas being
supplied to the unit.
FIGURE 5.8.0 TYPICAL DATA LABEL
Ground
Joint
Union
8 in. Trap
Gas to
Controls
From Gas Supply
Bleeder Valve or
1/8 in Plugged Tap
Gas Cock
FIGURE 5.8.1 TYPICAL GAS SUPPLY PIPING CONNECTION
TYPE OF GAS REQUIRED
MINIMUM PRESSURE
REQUIRED
NOTE: When
connecting the gas
supply, the length
of the run must be
considered in determin-
ing the pipe size to avoid
excessive pressure drop.
Refer to a Gas Engineer’s
handbook for gas pipe
capacities.
NOTE: Gas heat
modules 50
MBH–100 MBH have
a single 1/2" NPT gas
connection. Gas heat
modules 125–350 MBH
have a single 3/4" NPT gas
connection.
All gas piping must be installed in accordance with the latest edition of the National Fuel Gas
Code, ANSI Z223.1 and any local codes that may apply. In Canada, the equipment shall be
installed in accordance with the Installation Code for Gas Burning Appliances and Equipment,
(CGAB 149) and Provincial Regulations for the class. Authorities having jurisdiction should be
consulted before installations are made.
IMPORTANT