Troubleshooting and customer service

The equipment and components are manufactured using state-of-the-art production methods and tested several times  
to verify their correct function. If malfunctions should occur, please check the functions as detailed in the list below. 
Please inform your dealer if the unit is still not working correctly after all the functional checks have been performed!

Malfunction

Fault

Possible cause

Checks

Remedial measures

The unit does not start  
or switches itself off 
 

Power outage, undervoltage, 

defective mains fuse / main circuit 

breaker switched off

Are all other  

electrical installations functioning 

correctly?

Check voltage  

possible wait until turned on 

again.

Damaged mains cable

Are all other  

electrical installations functioning 

correctly?

Repair by  

a specialist

Waiting time after switch-on too 

short

Have approx. 5 minutes 

elapsed since the restart?

Schedule longer waiting  

periods

Temperature outside operating 

range.

Are the fans in the indoor unit 

and outdoor component working 

correctly?

Take into account the tempera-

ture range for the indoor unit and 

outdoor component

Overvoltages caused by thunder 

storms

Has there recently been lightning?

Switch off the mains breaker and 

switch it back on. Have it checked 

by a specialist

Fault in external condensation 

pump

Did the pump shut down due to 

a fault?

Check and if necessary clean the 

pump

High-pressure / low-pressure 
monitors have triggered

Check refrigerant pressure and 

look for leaks if necessary

Rectify leakage and re-start

The unit does not respond  
to the remote control

Transmission distance too far / 

receiver affected by interference

Does the indoor unit beep when 

pressing a button?

Reduce the distance to less than 6 

m or change position

Defective remote control

Is the unit running in manual 

mode?

Replace the remote control

Receiver or transmitter unit ex-

posed to excessive solar radiation

Does it function correctly in the 

shade?

Place the receiver&transmitter unit 

in the shade

Electromagnetic fields are interfer-

ing with transmission

Does it function when switching off 

possible sources of interference?

Signal is not transmitted when in-

terference sources are operational

Button in remote control jammed 

/ two buttons pressed at same 

time

Does the “Send” 

symbol appear on the display?

Release the button / only press 

one button

Batteries in remote control are flat

Have new batteries been inserted? 

Is the display incomplete?

Insert new batteries

The unit is running with  
reduced or without  
reduced cooling / heating 
performance

Filter is unclean / air inlet / outlet 

blocked by foreign items

Have the filters been cleaned?

Clean the filters

Windows and doors open.  Heat-

ing/cooling output increases

Have there been any construc-

tional /  

application-related  

changes?

Close windows and doors / install 

additional units

Neither cooling nor heating mode 

has been set

Does the cooling symbol appear 

on the display?

Correct the settings for the unit

Fins on outdoor component 

blocked by foreign items

Is the fan on the outdoor com-

ponent running? Are the fins 

unobstructed?

Check the fan or winter controller, 

reduce the air resistance

Leaking refrigerant circuit

Are there signs of frost on the fins 

of the indoor unit?

Repair by specialist

Outdoor component iced up

Check outdoor component. Has 

the cassette sensor on the outdoor 

component been correctly posi-

tioned? 

De-ice and fit the sensor at the 

point where the most ice forms

Condensation discharge  

on unit

Drainage pipe on collection con-

tainer clogged / damaged

Can the condensation drain off 

without any obstruction?

Clean the drainage pipe and col-

lection container

Faulty external condensation 

pump or float

Is the collection tray full of water 

and the pump not running?

Call out a specialist to replace the 

pump

Condensation has not drained 

away and has collected in the 

condensation line

Is there a steady fall on the con-

densation pipe? Check there is no 

blockage in the pipe.

Ensure there is a fall when laying 

the condensation pipe and clean 

the pipe. 

Condensation does not drain off

Are the condensation lines un-

blocked and is there a steady fall? 

Are the condensation pump and 

float switch functioning correctly?

The condensation line must have 

a fall. If necessary, clean the pipe. 

A faulty condensation pump and 

float switch should be replaced.

Float is stuck or jammed due to 

excessive dirt.

Are the LEDs on the receiver unit 

of the indoor unit flashing?

Should be cleaned by specialist firm

15

Содержание RVD 351DC

Страница 1: ...Issue D V03 REMKO RVD RVD 351DC RVD 521DC Inverter ceiling mounted air conditioner in split design Operation Technology Spare parts...

Страница 2: ......

Страница 3: ...tion and recycling 4 warranty 4 Transport and packaging 5 Description of the equipment 5 Operation 6 12 Shutdown 13 Care and maintenance 13 14 Troubleshooting and customer service 15 16 Installation i...

Страница 4: ...stalled by qualified per sonnel The setup connection and operation of the unit and its components must be in accord ance with the operating condi tions stipulated in this manual and comply with all ap...

Страница 5: ...ant circuit with compressor fin liquefier liquefier fan reverse flow valve and flow regulator The outdoor unit is controlled via the regulation of the indoor unit The indoor unit is designed for indoo...

Страница 6: ...e manually operated Problems are shown in code see chapter Troubleshooting and Customer service CAUTION Immediately replace flat batter ies with a new set otherwise there is a risk of leakage It is re...

Страница 7: ...t LOCK button pre vents subsequent operation the right RESET button resets the display Buttons on the remote control ON OFF Button Press this button to start the unit MODE button Press this button to...

Страница 8: ...modes The nominal temperature can be preselected and is then applied in automatic mode The fan speed is automatically adapted to the given circumstances AUTOMATIC MODE COOLING or HEATING The nominal...

Страница 9: ...rns the cooling on again after a waiting period of 3 minutes COOLING mode COOLING OPERATION and In dehumidification mode the room temperature is set to 24 C Due to the low temperature of the refrigera...

Страница 10: ...n the room The inverter controller checks the difference between the adjusted target temperature and the actual room temperature In the event of a greater difference a higher cooling performance is cr...

Страница 11: ...function of the air discharge fins can be adjusted with this button The air distribution in the room is improved with the swing function In order to adjust the aim of the air discharge fins to a parti...

Страница 12: ...F TIMER ON button activation delay Activation delay TIMER OFF button switch off delay CANCEL delete timer program Switch off delay Time stored TIMER ON TIMER ADJUST TIMER ADJUST TIMER ADJUST OK TIMER...

Страница 13: ...ice life of the unit Care Ensure the indoor unit and out door component are protected against dirt mould and other deposits Clean the equipment using a damp cloth Do not use any caustic abrasive or so...

Страница 14: ...2 Turn the dirty side until it faces up 5 Any dirt can be cleaned off us ing lukewarm water and mild cleaning agents To do so turn the dirty side downward Fig 3 6 When using water allow the filter dr...

Страница 15: ...ot transmitted when in terference sources are operational Button in remote control jammed two buttons pressed at same time Does the Send symbol appear on the display Release the button only press one...

Страница 16: ...that the compres sor oil can flow back without obstruction LED Operation LED Timer LED Defrost LED Alarm Display outdoor unit Cause Required action E0 EEPROM error Check EEPROM E2 Communication error...

Страница 17: ...densation line Injection pipe Suction pipe PVC tube Selection of the installation location Interior unit The indoor unit is designed for horizontal wall installation above doors However it can also be...

Страница 18: ...ir work and facilitate optimum air distribution 500 1000 1000 1000 1000 E C B A D Air intake Air outlet All values in mm Minimum clearances Ensure a continuous and unob structed air flow from outside...

Страница 19: ...on nections to a second room or a fresh air intake are required See section Connections to Installation should only be performed by authorised spe cialists NOTE a second room or a fresh air intake 3 F...

Страница 20: ...ns NOTE Flanging tool 7 Flanging the refrigerant pipe Refrigerant pipe Deburrer 6 Deburring the refrigerant pipe 8 Correct flange shape Tighten 1 spanner Counter 2 spanner 9 Tighten the fitting Tighte...

Страница 21: ...e required to generate the vacuum is dependent on the pipe work volume of the indoor unit and the length of the refrigerant pipes This always takes at least 60 minutes Once any foreign gases and humid...

Страница 22: ...ram 4 Re assemble the unit Terminal block Control line Cover Control line from the out door unit 12 Connecting the indoor unit Connecting the outdoor com ponent Proceed as follows to connect the cable...

Страница 23: ...caps are tight after carrying out any work on the refrigerant circuit If necessary use appropri ate sealant products NOTE Functional test for cooling and heating modes 1 Remove the caps from the valv...

Страница 24: ...e 10 35 40 11 40 45 C 12 45 50 13 50 55 C 14 55 60 15 60 65 C 16 65 70 Display Temperature 15 7 5 20 5 0 C 25 2 5 30 0 C 35 2 5 40 5 0 C 45 7 5 50 10 0 C 55 12 5 60 15 0 C 65 17 5 C 70 20 0 C 75 22 5...

Страница 25: ...Steuerleiter DM Display Y G c Blau Y G CN5 GM P1 Lila Wei Netzzuleitung Innenteil Rot Wei CN4 CN11 CN5 CN7 CN9 Wei C5 Wei Schwarz Rot CN3 CN2 T1 T2 T2 T1 CN14 CN10 CN15 E Y X Schwarz Grau Gelb Schwarz...

Страница 26: ...5 CN6 CN4 CN8 CN10 CN9 Blau Ventilator CN1 CN2 L N L N P 1 L H Sensor Hei gas Sensor Au entemperatur Sensor Austritt Verfl ssiger Elektronisches Expansionsventil Leistungsplatine zum Innenger t Steuer...

Страница 27: ...dimensions and constructional design as part of the ongoing technical development process All values in mm 650 650 400 610 28 580 A D E B C RVD 351 521 DC IT RVD 351 521 DC AT RVD 351 DC RVD 521 DC A...

Страница 28: ...1110955 1110956 7 Vaporiser 1110957 1110958 8 Condensation pump cpl 1110959 1110959 9 Fan wheel 1110960 1110961 10 Vaporiser fan motor 1110962 1110963 11 Control PCB 1110964 1110965 12 Transformer 11...

Страница 29: ...alve injection pipe 1111006 1111007 10 Reverse flow valve 1111008 1111009 11 Control PCB 1111010 1111011 12 Condenser compressor 1111012 1111013 Spare parts not illustrated E Box complete 1111014 1111...

Страница 30: ...T RVD 521DC IT Adjustment range room temperature C 17 30 Operating range C 17 31 Air flow volume per speed setting m h 510 530 680 560 710 800 Sound pressure level per speed setting 3 dB A 33 37 40 37...

Страница 31: ...Notes 31...

Страница 32: ...ore than mere salespeople they must primarily act as advisers in air conditioning and heating technology for our customers Customer Service Our units work precisely and dependably Should a failure occ...

Отзывы: