Air filter for indoor unit

Clean the air filter at intervals of 
no more than 2 weeks. 
Reduce this interval in case of 
heavily soiled air.

Cleaning the cover  
of the indoor unit

1.  Disconnect the supply voltage 

to the equipment.

2.  Open and fold down the air 

inlet guard on the cover. The 
filter is held in place by the flaps 
screwed in at the side of the 
guard 

(Fig. 1)

.

3.  Clean the guard using a soft, 

damp cloth.

4.  Switch the supply voltage back 

on.

Cleaning the filter

1.  Disconnect the supply voltage 

to the equipment.

2.  Open and fold down the air 

inlet guard on the cover. The 
filter is held in place by the flaps 
screwed in at the side of the 
guard 

(Fig. 1)

.

3.  Tilt the filter and lift it out.

4.  Clean the filter using a normal 

vacuum cleaner 

(Fig. 2).

Turn the dirty side until it faces 
up.

5.  Any dirt can be cleaned off us-

ing lukewarm water and mild 
cleaning agents.  
To do so, turn the dirty side 
downward

 (Fig. 3)

6.  When using water, allow   

the filter dry out properly in air 
before replacing it in the unit.

7.  Carefully insert the filter. Make 

sure it is seated correctly.

8.  Close the cover as described 

above but in reverse order.

9.  Switch the supply voltage back 

on.

10. Switch the unit back on.

Cleaning the  
condensation pump

The indoor unit includes a built-in 
condensation pump,  
for pumping the condensation to a 
drain at a higher level.

The pump is more or less main-
tenance free. The condensation 
pipes should be checked for dirt 
at regular intervals. Clean them as 
required.

If an external pump is also used, 
observe the maintenance and care 
instructions given in the separate  
operating manual.

 

1    Guard on cover

 

2    Clean with a vacuum cleaner

 

3    Cleaning with lukewarm water

REMKO RVD...DC

14

Содержание RVD 351DC

Страница 1: ...Issue D V03 REMKO RVD RVD 351DC RVD 521DC Inverter ceiling mounted air conditioner in split design Operation Technology Spare parts...

Страница 2: ......

Страница 3: ...tion and recycling 4 warranty 4 Transport and packaging 5 Description of the equipment 5 Operation 6 12 Shutdown 13 Care and maintenance 13 14 Troubleshooting and customer service 15 16 Installation i...

Страница 4: ...stalled by qualified per sonnel The setup connection and operation of the unit and its components must be in accord ance with the operating condi tions stipulated in this manual and comply with all ap...

Страница 5: ...ant circuit with compressor fin liquefier liquefier fan reverse flow valve and flow regulator The outdoor unit is controlled via the regulation of the indoor unit The indoor unit is designed for indoo...

Страница 6: ...e manually operated Problems are shown in code see chapter Troubleshooting and Customer service CAUTION Immediately replace flat batter ies with a new set otherwise there is a risk of leakage It is re...

Страница 7: ...t LOCK button pre vents subsequent operation the right RESET button resets the display Buttons on the remote control ON OFF Button Press this button to start the unit MODE button Press this button to...

Страница 8: ...modes The nominal temperature can be preselected and is then applied in automatic mode The fan speed is automatically adapted to the given circumstances AUTOMATIC MODE COOLING or HEATING The nominal...

Страница 9: ...rns the cooling on again after a waiting period of 3 minutes COOLING mode COOLING OPERATION and In dehumidification mode the room temperature is set to 24 C Due to the low temperature of the refrigera...

Страница 10: ...n the room The inverter controller checks the difference between the adjusted target temperature and the actual room temperature In the event of a greater difference a higher cooling performance is cr...

Страница 11: ...function of the air discharge fins can be adjusted with this button The air distribution in the room is improved with the swing function In order to adjust the aim of the air discharge fins to a parti...

Страница 12: ...F TIMER ON button activation delay Activation delay TIMER OFF button switch off delay CANCEL delete timer program Switch off delay Time stored TIMER ON TIMER ADJUST TIMER ADJUST TIMER ADJUST OK TIMER...

Страница 13: ...ice life of the unit Care Ensure the indoor unit and out door component are protected against dirt mould and other deposits Clean the equipment using a damp cloth Do not use any caustic abrasive or so...

Страница 14: ...2 Turn the dirty side until it faces up 5 Any dirt can be cleaned off us ing lukewarm water and mild cleaning agents To do so turn the dirty side downward Fig 3 6 When using water allow the filter dr...

Страница 15: ...ot transmitted when in terference sources are operational Button in remote control jammed two buttons pressed at same time Does the Send symbol appear on the display Release the button only press one...

Страница 16: ...that the compres sor oil can flow back without obstruction LED Operation LED Timer LED Defrost LED Alarm Display outdoor unit Cause Required action E0 EEPROM error Check EEPROM E2 Communication error...

Страница 17: ...densation line Injection pipe Suction pipe PVC tube Selection of the installation location Interior unit The indoor unit is designed for horizontal wall installation above doors However it can also be...

Страница 18: ...ir work and facilitate optimum air distribution 500 1000 1000 1000 1000 E C B A D Air intake Air outlet All values in mm Minimum clearances Ensure a continuous and unob structed air flow from outside...

Страница 19: ...on nections to a second room or a fresh air intake are required See section Connections to Installation should only be performed by authorised spe cialists NOTE a second room or a fresh air intake 3 F...

Страница 20: ...ns NOTE Flanging tool 7 Flanging the refrigerant pipe Refrigerant pipe Deburrer 6 Deburring the refrigerant pipe 8 Correct flange shape Tighten 1 spanner Counter 2 spanner 9 Tighten the fitting Tighte...

Страница 21: ...e required to generate the vacuum is dependent on the pipe work volume of the indoor unit and the length of the refrigerant pipes This always takes at least 60 minutes Once any foreign gases and humid...

Страница 22: ...ram 4 Re assemble the unit Terminal block Control line Cover Control line from the out door unit 12 Connecting the indoor unit Connecting the outdoor com ponent Proceed as follows to connect the cable...

Страница 23: ...caps are tight after carrying out any work on the refrigerant circuit If necessary use appropri ate sealant products NOTE Functional test for cooling and heating modes 1 Remove the caps from the valv...

Страница 24: ...e 10 35 40 11 40 45 C 12 45 50 13 50 55 C 14 55 60 15 60 65 C 16 65 70 Display Temperature 15 7 5 20 5 0 C 25 2 5 30 0 C 35 2 5 40 5 0 C 45 7 5 50 10 0 C 55 12 5 60 15 0 C 65 17 5 C 70 20 0 C 75 22 5...

Страница 25: ...Steuerleiter DM Display Y G c Blau Y G CN5 GM P1 Lila Wei Netzzuleitung Innenteil Rot Wei CN4 CN11 CN5 CN7 CN9 Wei C5 Wei Schwarz Rot CN3 CN2 T1 T2 T2 T1 CN14 CN10 CN15 E Y X Schwarz Grau Gelb Schwarz...

Страница 26: ...5 CN6 CN4 CN8 CN10 CN9 Blau Ventilator CN1 CN2 L N L N P 1 L H Sensor Hei gas Sensor Au entemperatur Sensor Austritt Verfl ssiger Elektronisches Expansionsventil Leistungsplatine zum Innenger t Steuer...

Страница 27: ...dimensions and constructional design as part of the ongoing technical development process All values in mm 650 650 400 610 28 580 A D E B C RVD 351 521 DC IT RVD 351 521 DC AT RVD 351 DC RVD 521 DC A...

Страница 28: ...1110955 1110956 7 Vaporiser 1110957 1110958 8 Condensation pump cpl 1110959 1110959 9 Fan wheel 1110960 1110961 10 Vaporiser fan motor 1110962 1110963 11 Control PCB 1110964 1110965 12 Transformer 11...

Страница 29: ...alve injection pipe 1111006 1111007 10 Reverse flow valve 1111008 1111009 11 Control PCB 1111010 1111011 12 Condenser compressor 1111012 1111013 Spare parts not illustrated E Box complete 1111014 1111...

Страница 30: ...T RVD 521DC IT Adjustment range room temperature C 17 30 Operating range C 17 31 Air flow volume per speed setting m h 510 530 680 560 710 800 Sound pressure level per speed setting 3 dB A 33 37 40 37...

Страница 31: ...Notes 31...

Страница 32: ...ore than mere salespeople they must primarily act as advisers in air conditioning and heating technology for our customers Customer Service Our units work precisely and dependably Should a failure occ...

Отзывы: