Regulation 

CH–DIN regulation of all RKW INOX units

 

The CH–DIN microprocessor regulates the chiller for all 
INOX units. It is located in the electrical switch box of 
the unit and monitors all control and safety functions: 

Controls and displays incoming and outgoing cold 
water temperatures 

Displays the time delay of the compressor and fan 

Checks that the outgoing water temperature is  not 
too low (frost monitoring) 

Displays and controls all safety mechanisms that 
have been stopped due to a malfunction 

Displays the operating mode 

Regulates the condensation temperature 

The regulator consists of the basic unit to control unit 
operation. A fan board is connected to the basic unit 
that controls the rotation of the fan motors by regulating 
the output current depending on the liquefaction tem-
perature. 
Models RKW 3600 INOX and higher have two cold cy-
cles. The second cycle cannot be regulated by the CH–
DIN basic unit because there are not enough inputs and 
outputs. For this reason, the extra C2-DIN regulator 
controls the second cycle. Programming is, however, 
still performed using the CH–DIN basic unit. 

Value Display 

The value display shows the target value in degrees 
with one decimal place in Celsius. It can also display: 

All parameter settings 

The codes for all alarms 

The status of the functions 

The operating hours 

The shut-off status 

The current delays 

A square LED displays minus temperatures and an LED 
in the top left-hand corner shows the multiplier of the 
displayed value with 100. 

8

 

8.

 

8

 

Arrow Keys 

The set value for each parameter can be changed with 
the arrow keys. 
When the parameter programming operating mode is 
accessed (via the MENU button), both displays show a 
value (continuous display). After the SET button has 
been pressed, the code display (parameters) starts 
blinking. The displayed values can be increased or de-
creased using the arrow keys. If the SET is pressed a 
second time, the value display blinks. The new values 
are saved by pressing the SET button again. Both dis-
plays switch from a blinking display to a continuous display. 

MENU Button with one LED 

The MENU button provides access to the parameter list 
and displays the parameters on the code display and 
the associated value on the value display. 

MENU 

CH– DIN panel 

CH-DIN 

Line 

Alarm 

Comp 

Heat 

Cool 

STATUS 

MENU 

ON/OFF 

RESET 

8

 

8

 

8

 

8.

 

8

 

SET 

MODE 

 

e

 

Value display 

Code display 

Arrow keys 

MODE button 

SET button 

MENU button 

STATUS button 

ON/OFF  

RESET button 

Code Display 

The code display indicates the number of the parameter 
(or the function) whose value or status appears in the 
value display. If a parameter is shown in the code dis-
play, the setting appears in the value display. 

8

 

8

 

STATUS Button with one LED 

The STATUS button provides access to the status list 
and displays the status settings by pressing the  arrow 
keys. 
The code display shows the function number of the 
function list and the value display shows the corre-
sponding setting. The codes and their descriptions are 
described in the table on page 8. 

STATUS 

The panel has two displays: the value display (three 
numbers on the left) and the code display (two numbers 
on the right). 

The buttons  

allow operating 

processes (parameters) and their associated values to 
be changed. 

STATUS 

MENU 

ON/OFF 

RESET 

SET 

MODE 

MODE Button with two LEDs 

The regulation mechanism was designed for use of a 
chiller in the cooling operating mode 

and as a 

heat pump in the cooling and heating operating 
modes. 

Only the summer operating mode (cooling mode) 
may be used for all INOX units

MODE 

Cool 

e

 

Heat 

Cool 

e

 

Содержание RKW 1000 INOX

Страница 1: ...REMKO powerful like a bear REMKO RKW 1000 9800 INOX Stainless Steel Chiller Edition GB M11 Operation Technology Spare Parts...

Страница 2: ......

Страница 3: ...ce Personnel 14 Unit Assembly 14 Storage Modules for RKW 3600 to 9800 I 17 Cable Remote Control 20 Electrical Connection 21 Hydraulic System 24 Initial Operation 25 Environment and Recycling 26 Servic...

Страница 4: ...s by means of a quiet fan When the air in the room leaves the unit it is cooled demoisturized and filtered The water warms up and transports the heat absorbed from the room back to the outer part wher...

Страница 5: ...arge amounts of dust or aggres sive air Installation and repair work may only be performed by authorised personnel Cleaning and minor maintenance work made only be performed by the operator or an auth...

Страница 6: ...on both displays show a value continuous display After the SET button has been pressed the code display parameters starts blinking The displayed values can be increased or de creased using the arrow k...

Страница 7: ...g the corresponding programmed output current to the CTK 1 CTK 2 output of the TK 1 TK 2 fan board The fan motor rotation can be controlled by the modulat ing output current Compressor LED This LED is...

Страница 8: ...in hours Not installed Operating hours of Compressor 2 23 Fan s Cycle 2 01 02 04 06 Not installed Fans in operation Off not in use Time delay ON OFF 25 Rotations condenser fan s Cycle 2 Not installed...

Страница 9: ...i n s t o b l i n k w h e n t h e S E T button is pressed This mode displays the options for changing the parameters to the programmer If one of the arrow keys is now pressed the parameter jumps to t...

Страница 10: ...ycle 2 E40 Sensor defective ST 1 incoming water E41 Flow switch differential pressure monitor activated E42 Hardware defective The second parameter level can be programmed to reset the alarms Enter th...

Страница 11: ...ture E06 E07 E26 E27 E40 Sensors defective ST1 to ST6 It is the alarm activated when the sensor is replaced Replace defective sensors E41 Flow switch differential pres sure monitor activated Are the f...

Страница 12: ...ater chiller inch 1 1 2 2 x 2 Outgoing water chiller inch 1 1 2 2 x 2 Filling connection inch 1 2 Sound pressure level 2 dB A 43 44 49 48 48 53 54 Refrigerant R 407C Cold cycles Compressor type 1 Scro...

Страница 13: ...tgoing water inch 1 inside 1 inside 1 inside 2 inside 2 inside 2 x 2 inside 2 x 2 inside M filling connection water inch outside outside outside Fan number mm 450 2 450 2 630 1 630 2 630 2 800 2 800 2...

Страница 14: ...room will heat up and the chiller will switch off due to a malfunction This occurs once the room temperature exceeds the upper operating range of the set value of the safety mechanism Minimum distance...

Страница 15: ...sorbers in this series These must be connected to statically permissi ble and level building or structural components The locations for attachment described below are for fastening the vibration absor...

Страница 16: ...liers must be used to mount the pipe lines on the RKW so as not to create any strain on the pipe lines in the inside of the unit If the chiller is only initially operated with a single part of the ove...

Страница 17: ...ge module 3 for RKW 8000 and 9800 INOX 2 x 216 l tanks safety component 3 kPa and MAG without pump Ref No 1611545 4 Storage module 4 for RKW 8000 and 9800 INOX 2 x 216 l tanks safety component 3 kPa a...

Страница 18: ...a 5 8 6 10 8 11 10 11 15 13 Available external pressure differential kPa 92 89 59 66 47 32 Electrical connection V 3 400 3 400 3 400 Power Current consumption kW A 0 55 1 44 0 55 1 44 0 75 1 86 1 1 2...

Страница 19: ...ption max 1 44 A 1 44 A 1 86 A 400 V 50 Hz 3 N PE Characteristic curve of the pump RKW 3600 4500 INOX storage module 2 Characteristic curve of the pump RKW 8000 9800 INOX storage module 4 Characterist...

Страница 20: ...contact with drinking water or food antifreeze L is to be given preference because it contains the physiologically harmless substance 1 2 propylene glycol The data provided in the table refers to anti...

Страница 21: ...AT 9 Differential pressure monitor Neutral contact 15 17 AT 7 Heating cooling removed Neutral contact 15 18 closed AT 10 On Off remote control contact for heating pump Neutral contact 19 20 RL 1 Glob...

Страница 22: ...Verfl ssiger fan 1 Potentialfreier Kontakt for regulating cool ing EXTERNAL Flow switch EXTERNAL Phase sequence relay Terminal strip M1 Terminal strip M2 Compressor motor Relay compressor ST 1 Tempera...

Страница 23: ...4 L1 N L1 12V 12V N Pri 230V CH DIN regulation C2 DIN regulation Additional module for the remote control Transformer 220 12 V in the switch box RKW Operating module Maximum line length 50 meter Assem...

Страница 24: ...1 15 13 3 1 2 12 17 14 10 16 18 9 6 5 4 7 8 15 13 3 Hydraulic Diagram RKW 8000 9800 INOX 1 2 12 17 14 1 16 18 9 6 5 4 7 8 1 15 P 10 19 Terminal strip M1 Condenser fan 1 and 2 Klemmleiste M2 Compressor...

Страница 25: ...is correct The electrical lines of the system must be checked that they are attached properly to the terminal strips Prior to operation all screws in the water system must be checked to ensure that th...

Страница 26: ...then select a higher drainage temperature 17 The supply temperature is approx 5 Kelvin under the drainage temperature for the rated flow rate 18 If the supply temperature is below the factory setting...

Страница 27: ......

Страница 28: ...REMKO GmbH Co KG Klima und W rmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606260...

Отзывы: