background image

18 

 

 

3600

 

4500

 

8000

 

9800

 

Storage module for RKW INOX 

 

Storage contents 

216 

2 x 216 

Number of pumps 

 

Incoming water / Outgoing  
water 

inch 

1½ 

1½ 

Filling connection 

inch 

1/2 

1/2 

Operating pressure max. 

kPa 

250 

250 

Rated volume current water 

m³/h 

6.2 

7.6 

13.4 

16.9 

Minimum volume current 
 water 

m³/h 

4.5 

5.2 

8.8 

10.8 

Pump pressure max. 

kPa 

124 

118 

90 

95 

82 

65 

Storage pressure loss,  
internal 

kPa 

10 

11 

10 

11 

15 

13 

Available external pressure  
differential 

kPa 

92 

89 

59 

66 

47 

32 

Electrical connection 

3~,400 

3~,400 

3~,400 

Power/Current consumption 

kW/A 

 

0.55/1.44 

 

0.55/1.44 

0.75/1.86

 

1.1/2.88 

0.75/1.86  1.1/2.88

 

Dimensions               Width 

mm 

2370 

2 x 2370 

                                   Height 

mm 

535 

2 x 535 

                                   Depth 

mm 

560 

2 x 560 

Weight when empty, storage 

kg 

123 

126 

123 

126 

246 

246 

Weight pump 

kg 

Ref.No. 

 

1611530  1611540  1611530  1611540  1611545  1611550  1611555  1611545  1611550  1611555 

3~,400 

Storage module dimensions 

Parallel operation 

Individual operation 

Storage Module Technical Data 

Hydraulic operation of the storage module 

Содержание RKW 1000 INOX

Страница 1: ...REMKO powerful like a bear REMKO RKW 1000 9800 INOX Stainless Steel Chiller Edition GB M11 Operation Technology Spare Parts...

Страница 2: ......

Страница 3: ...ce Personnel 14 Unit Assembly 14 Storage Modules for RKW 3600 to 9800 I 17 Cable Remote Control 20 Electrical Connection 21 Hydraulic System 24 Initial Operation 25 Environment and Recycling 26 Servic...

Страница 4: ...s by means of a quiet fan When the air in the room leaves the unit it is cooled demoisturized and filtered The water warms up and transports the heat absorbed from the room back to the outer part wher...

Страница 5: ...arge amounts of dust or aggres sive air Installation and repair work may only be performed by authorised personnel Cleaning and minor maintenance work made only be performed by the operator or an auth...

Страница 6: ...on both displays show a value continuous display After the SET button has been pressed the code display parameters starts blinking The displayed values can be increased or de creased using the arrow k...

Страница 7: ...g the corresponding programmed output current to the CTK 1 CTK 2 output of the TK 1 TK 2 fan board The fan motor rotation can be controlled by the modulat ing output current Compressor LED This LED is...

Страница 8: ...in hours Not installed Operating hours of Compressor 2 23 Fan s Cycle 2 01 02 04 06 Not installed Fans in operation Off not in use Time delay ON OFF 25 Rotations condenser fan s Cycle 2 Not installed...

Страница 9: ...i n s t o b l i n k w h e n t h e S E T button is pressed This mode displays the options for changing the parameters to the programmer If one of the arrow keys is now pressed the parameter jumps to t...

Страница 10: ...ycle 2 E40 Sensor defective ST 1 incoming water E41 Flow switch differential pressure monitor activated E42 Hardware defective The second parameter level can be programmed to reset the alarms Enter th...

Страница 11: ...ture E06 E07 E26 E27 E40 Sensors defective ST1 to ST6 It is the alarm activated when the sensor is replaced Replace defective sensors E41 Flow switch differential pres sure monitor activated Are the f...

Страница 12: ...ater chiller inch 1 1 2 2 x 2 Outgoing water chiller inch 1 1 2 2 x 2 Filling connection inch 1 2 Sound pressure level 2 dB A 43 44 49 48 48 53 54 Refrigerant R 407C Cold cycles Compressor type 1 Scro...

Страница 13: ...tgoing water inch 1 inside 1 inside 1 inside 2 inside 2 inside 2 x 2 inside 2 x 2 inside M filling connection water inch outside outside outside Fan number mm 450 2 450 2 630 1 630 2 630 2 800 2 800 2...

Страница 14: ...room will heat up and the chiller will switch off due to a malfunction This occurs once the room temperature exceeds the upper operating range of the set value of the safety mechanism Minimum distance...

Страница 15: ...sorbers in this series These must be connected to statically permissi ble and level building or structural components The locations for attachment described below are for fastening the vibration absor...

Страница 16: ...liers must be used to mount the pipe lines on the RKW so as not to create any strain on the pipe lines in the inside of the unit If the chiller is only initially operated with a single part of the ove...

Страница 17: ...ge module 3 for RKW 8000 and 9800 INOX 2 x 216 l tanks safety component 3 kPa and MAG without pump Ref No 1611545 4 Storage module 4 for RKW 8000 and 9800 INOX 2 x 216 l tanks safety component 3 kPa a...

Страница 18: ...a 5 8 6 10 8 11 10 11 15 13 Available external pressure differential kPa 92 89 59 66 47 32 Electrical connection V 3 400 3 400 3 400 Power Current consumption kW A 0 55 1 44 0 55 1 44 0 75 1 86 1 1 2...

Страница 19: ...ption max 1 44 A 1 44 A 1 86 A 400 V 50 Hz 3 N PE Characteristic curve of the pump RKW 3600 4500 INOX storage module 2 Characteristic curve of the pump RKW 8000 9800 INOX storage module 4 Characterist...

Страница 20: ...contact with drinking water or food antifreeze L is to be given preference because it contains the physiologically harmless substance 1 2 propylene glycol The data provided in the table refers to anti...

Страница 21: ...AT 9 Differential pressure monitor Neutral contact 15 17 AT 7 Heating cooling removed Neutral contact 15 18 closed AT 10 On Off remote control contact for heating pump Neutral contact 19 20 RL 1 Glob...

Страница 22: ...Verfl ssiger fan 1 Potentialfreier Kontakt for regulating cool ing EXTERNAL Flow switch EXTERNAL Phase sequence relay Terminal strip M1 Terminal strip M2 Compressor motor Relay compressor ST 1 Tempera...

Страница 23: ...4 L1 N L1 12V 12V N Pri 230V CH DIN regulation C2 DIN regulation Additional module for the remote control Transformer 220 12 V in the switch box RKW Operating module Maximum line length 50 meter Assem...

Страница 24: ...1 15 13 3 1 2 12 17 14 10 16 18 9 6 5 4 7 8 15 13 3 Hydraulic Diagram RKW 8000 9800 INOX 1 2 12 17 14 1 16 18 9 6 5 4 7 8 1 15 P 10 19 Terminal strip M1 Condenser fan 1 and 2 Klemmleiste M2 Compressor...

Страница 25: ...is correct The electrical lines of the system must be checked that they are attached properly to the terminal strips Prior to operation all screws in the water system must be checked to ensure that th...

Страница 26: ...then select a higher drainage temperature 17 The supply temperature is approx 5 Kelvin under the drainage temperature for the rated flow rate 18 If the supply temperature is below the factory setting...

Страница 27: ......

Страница 28: ...REMKO GmbH Co KG Klima und W rmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606260...

Отзывы: