The following electrical connections must be made: 

Connecting the power supply 

Connecting the cable remote control if applicable 

Please follow the instructions below to install the electri-
cal connections: 

The inner units function independently of the chiller. 
An electrical control line is hence not necessary. 

The electrical connections are to be performed as 
fixed connections in accordance with the relevant 
regulations. 

An all-polo separating switch is to be installed in the 
power line in front of the unit. 

The power line must be insulated adequately by the 
customer and the line drop may not fall below the 
permissible values. 

Make sure that the electrical system is suitable to 
supply the required operating current for operating 
the unit and any other units that are already in opera-
tion. 

Prior to installation, if connections are made to exist-
ing system parts, you must check that the line has 
the right dimensions for unit consumption. 

The units must always be connected with low-ohm 
protection conductors with sufficient dimensions. In 
certain circumstances, the module must be grounded 
as a measure to protect against lightning in several 
places (especially when plastic pipes are used).

 

Terminal 

strip 

Normal status 

Input / 

Output 

Function 

Connections 

01 – 02 

 

ST 1 

Incoming water - Sensor 

PTC - input 

03 – 04 

 

ST 2 

Outgoing water – Sensor 

PTC - input 

05 – 06 

 

ST 5 

Condenser – Sensor 

PTC - input 

07 – 08 

closed 

AT 1 

High pressure switch 

Neutral contact 

09 – 10 

closed 

AT 3 

Low pressure switch 

Neutral contact 

11 – 12 

closed 

AT 5 

Not in use 

Neutral contact 

13 – 14 

12 V ~ 

Tr 

Current supply 

12 V ~, 50 Hz 

15 – 16 

Closed when pump is in operation  AT 9 

Differential pressure monitor 

Neutral contact

 

15 – 17 

 

AT 7 

Heating-cooling removed 

Neutral contact 

15 – 18 

closed 

AT 10 

On Off, remote control contact for heating pump  Neutral contact 

19 – 20 

 

RL 1 

Global shut-off 

Max. 48 V ~, 200 mA 

22 – 23 

 

RL 2 

Defrost heating / Boiler signal 

230 V ~, 50 Hz, 4,0 A 

22 – 24 

 

RL 4 

Compressor 

230 V ~, 50 Hz, 0,4 A 

22 – 25 

 

RL 8 

Circulation valve (heating pump only) 

230 V ~, 50 Hz, 0,4 A, 

21 – 22 

 

RL 10 

Pump switch contact 

230 V ~, 50 Hz, 4,0 A 

42 – 43 

 

TK 1 

Fan regulation - output  

Phase regulation 

Description of the CH-DIN inputs and outputs 

All electrical connections such as power input, cable re-
mote control, etc., are to be made in the switch box of 
the unit. The lines to be laid must be guided through the 
appropriate cable penetrations on the back of the unit 
into the housing. 

All units require a three-phase alternating current con-
nection. The power line is to be guided through the L1, 
L2, L3, N and PE terminal strips. 

The line dimensions are based on the local conditions. 
The connection capacity of units can be found in the ta-
ble below: 

 Type 

 

RKW INOX 

 

 

1000  1600  2600  3600  4500  8000  9800 

 Electrical connection 

 

400 V /3~, N. PE / 50 Hz 

 Power consumption 

kW 

4.4 

7.1 

11.2  15.7  19.4  36.0  45.2 

 Cur. Consumption max. 

12.8  18.8  26.3  32.6  58.5  73.5 

 Start-up current 

49 

101 

167  2x90  2x120 2x116 2x127 

 Fuse protection 
 customer-side 

20 

20 

25 

35 

50 

80 

100 

Electrical Connection

 

G

 

Warning! The units are equipped with a phase-sequencer relay that prevents the unit from operating if the ro-
tational direction of the electrical connection is wrong. If the chiller remains neutral (i.e. no current) when be-
ing put into operation, the rotational field must be switched.

 

G

 

Electrical installations may only be performed by 
authorised service personnel. Prior to performing 
any work on the unit, it must be unplugged from 
the power supply.

 

Содержание RKW 1000 INOX

Страница 1: ...REMKO powerful like a bear REMKO RKW 1000 9800 INOX Stainless Steel Chiller Edition GB M11 Operation Technology Spare Parts...

Страница 2: ......

Страница 3: ...ce Personnel 14 Unit Assembly 14 Storage Modules for RKW 3600 to 9800 I 17 Cable Remote Control 20 Electrical Connection 21 Hydraulic System 24 Initial Operation 25 Environment and Recycling 26 Servic...

Страница 4: ...s by means of a quiet fan When the air in the room leaves the unit it is cooled demoisturized and filtered The water warms up and transports the heat absorbed from the room back to the outer part wher...

Страница 5: ...arge amounts of dust or aggres sive air Installation and repair work may only be performed by authorised personnel Cleaning and minor maintenance work made only be performed by the operator or an auth...

Страница 6: ...on both displays show a value continuous display After the SET button has been pressed the code display parameters starts blinking The displayed values can be increased or de creased using the arrow k...

Страница 7: ...g the corresponding programmed output current to the CTK 1 CTK 2 output of the TK 1 TK 2 fan board The fan motor rotation can be controlled by the modulat ing output current Compressor LED This LED is...

Страница 8: ...in hours Not installed Operating hours of Compressor 2 23 Fan s Cycle 2 01 02 04 06 Not installed Fans in operation Off not in use Time delay ON OFF 25 Rotations condenser fan s Cycle 2 Not installed...

Страница 9: ...i n s t o b l i n k w h e n t h e S E T button is pressed This mode displays the options for changing the parameters to the programmer If one of the arrow keys is now pressed the parameter jumps to t...

Страница 10: ...ycle 2 E40 Sensor defective ST 1 incoming water E41 Flow switch differential pressure monitor activated E42 Hardware defective The second parameter level can be programmed to reset the alarms Enter th...

Страница 11: ...ture E06 E07 E26 E27 E40 Sensors defective ST1 to ST6 It is the alarm activated when the sensor is replaced Replace defective sensors E41 Flow switch differential pres sure monitor activated Are the f...

Страница 12: ...ater chiller inch 1 1 2 2 x 2 Outgoing water chiller inch 1 1 2 2 x 2 Filling connection inch 1 2 Sound pressure level 2 dB A 43 44 49 48 48 53 54 Refrigerant R 407C Cold cycles Compressor type 1 Scro...

Страница 13: ...tgoing water inch 1 inside 1 inside 1 inside 2 inside 2 inside 2 x 2 inside 2 x 2 inside M filling connection water inch outside outside outside Fan number mm 450 2 450 2 630 1 630 2 630 2 800 2 800 2...

Страница 14: ...room will heat up and the chiller will switch off due to a malfunction This occurs once the room temperature exceeds the upper operating range of the set value of the safety mechanism Minimum distance...

Страница 15: ...sorbers in this series These must be connected to statically permissi ble and level building or structural components The locations for attachment described below are for fastening the vibration absor...

Страница 16: ...liers must be used to mount the pipe lines on the RKW so as not to create any strain on the pipe lines in the inside of the unit If the chiller is only initially operated with a single part of the ove...

Страница 17: ...ge module 3 for RKW 8000 and 9800 INOX 2 x 216 l tanks safety component 3 kPa and MAG without pump Ref No 1611545 4 Storage module 4 for RKW 8000 and 9800 INOX 2 x 216 l tanks safety component 3 kPa a...

Страница 18: ...a 5 8 6 10 8 11 10 11 15 13 Available external pressure differential kPa 92 89 59 66 47 32 Electrical connection V 3 400 3 400 3 400 Power Current consumption kW A 0 55 1 44 0 55 1 44 0 75 1 86 1 1 2...

Страница 19: ...ption max 1 44 A 1 44 A 1 86 A 400 V 50 Hz 3 N PE Characteristic curve of the pump RKW 3600 4500 INOX storage module 2 Characteristic curve of the pump RKW 8000 9800 INOX storage module 4 Characterist...

Страница 20: ...contact with drinking water or food antifreeze L is to be given preference because it contains the physiologically harmless substance 1 2 propylene glycol The data provided in the table refers to anti...

Страница 21: ...AT 9 Differential pressure monitor Neutral contact 15 17 AT 7 Heating cooling removed Neutral contact 15 18 closed AT 10 On Off remote control contact for heating pump Neutral contact 19 20 RL 1 Glob...

Страница 22: ...Verfl ssiger fan 1 Potentialfreier Kontakt for regulating cool ing EXTERNAL Flow switch EXTERNAL Phase sequence relay Terminal strip M1 Terminal strip M2 Compressor motor Relay compressor ST 1 Tempera...

Страница 23: ...4 L1 N L1 12V 12V N Pri 230V CH DIN regulation C2 DIN regulation Additional module for the remote control Transformer 220 12 V in the switch box RKW Operating module Maximum line length 50 meter Assem...

Страница 24: ...1 15 13 3 1 2 12 17 14 10 16 18 9 6 5 4 7 8 15 13 3 Hydraulic Diagram RKW 8000 9800 INOX 1 2 12 17 14 1 16 18 9 6 5 4 7 8 1 15 P 10 19 Terminal strip M1 Condenser fan 1 and 2 Klemmleiste M2 Compressor...

Страница 25: ...is correct The electrical lines of the system must be checked that they are attached properly to the terminal strips Prior to operation all screws in the water system must be checked to ensure that th...

Страница 26: ...then select a higher drainage temperature 17 The supply temperature is approx 5 Kelvin under the drainage temperature for the rated flow rate 18 If the supply temperature is below the factory setting...

Страница 27: ......

Страница 28: ...REMKO GmbH Co KG Klima und W rmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606260...

Отзывы: