background image

13 

8.    The condensation and control lines also have to be 

connected and, depending on the selected option, 
guided to the outside.  

Described below.

 

9.    If, due to structural design conditions, it is not possi-

ble to guide the condensation line through as well, 
make sure that the condensation can drain freely at 
all times. 

10. Hang the indoor unit leaning slightly to the back in 

the previously assembled wall mount and press the 
bottom of the unit into the mount until it catches. 

Prior to beginning installation, please observe the fol-
lowing: 

à

We recommend that the customer install a main or 
repair switch close to the outdoor part. 

à

Power is supplied to the indoor units via a connec-
tion line from the outdoor part. 

à

Fuse protection for the system must occur in accor-
dance with the technical data. 

The connections of the indoor unit are located on the 
right hand side next to the fan and are hidden from view 
by the housing. Proceed as follows to connect the line: 
1.  Open the air intake grille of the unit downwards or 

take it off completely and remove the right air filter. 

2.  The connection terminal strip is freely accessible 

once the protective cover has been removed. 

3.   Connect the indoor unit to the outdoor part using the 

current-free line in accordance with the electrical wir-
ing diagram and reassemble the unit in the reverse 
order. 

11. If the outdoor part is set 

up at a higher level than 
the indoor unit, appropri-
ate steps must be taken 
for oil recirculation.      

This can be achieved by 
installing oil elevation 
arcs every 2.5 meters of 
line going up.

 

7.   Before you flare the refrigerant lines, ensure that 

there is a swivel nut on the hose. Also make sure 
that the flare has the correct shape. 

 

Prior to performing any work on the indoor unit and 
outdoor part, it must be unplugged from the power 
supply and secured against being inadvertently 
switched on! 

Electrical Connection 

 

To control the outdoor part, a 4-wire control line must be 
laid to the indoor unit and a feed-in line installed. The 
electrical installations may only be performed by author-
ised personnel in line with the relevant regulations. Local 
guidelines for operation as well as the requirements es-
tablished by local energy supply companies must be ob-
served for setup and initial operation. 

uneven 

thickness 

formation 

of cracks 

formation 

of cracks 

rippled 

CORRECT 

 

A vacuum with a minimum of 0.05 mbar must be 
created! 

How long it takes to create the vacuum is based on the 
hose line volume of the indoor unit and the length of the 
refrigerant lines. However, this process takes a mini-
mum of 30 minutes. 
Once foreign gases and moisture have been completely 
removed from the system, the manometer station 
valves are closed and the valves of the outdoor part are 
opened as described in the section "Initial Operation“. 

Impermeability Check

 

 

Once all connections have been made, the manometer 
station is connected to the corresponding valve connec-
tions as described below: 

red     =      small valve       =    injection pressure. 
blue   =      large valve        =    suction pressure. 

After the connection has been made, an impermeability 
test is conducted using dry nitrogen. 

The connections that have been established are 
sprayed with a leak locator spray to test for imperme-
ability. Tighten the bolts more firmly or, if necessary, 
create a new flare. 
After this test has been successfully conducted, any ex-
cess pressure is removed from the refrigerant lines and 
a vacuum pump with an absolute final partial pressure 
of at least 0.01 mbar is put into operation to create a 
vacuum in the lines. This also removes any moisture 
from the lines. 

12. 

First manually connect 
the refrigerant lines with 
the screws of the indoor 
unit to ensure that they are in the proper position. 
Now tighten the bolts using 2 hexagonal wrenches 
that have a large enough opening. 

13. The installed refrigerant lines are heat-insulated and 

sealed against diffusion. Only use insulated hoses 
suitable for this temperature range. 

14. Lay the connected lines and the control lines to the 

outdoor part. Remove the protective caps of the 
valves and proceed as described under Point 5. 

Radius:  
50 mm 

Oil elevation arcs in 
the control line to the 
outdoor part 

Indoor 
unit 

Outdoor 
part 

Содержание RKV 13 T

Страница 1: ...REMKO powerful like a bear REMKO RKV 13 T 24 T Wall Ceiling Chests Edition GB P05 Operation Technology Spare Parts...

Страница 2: ......

Страница 3: ...ctrical Connection 13 Condensation Connection 14 External Condensation Pump 15 Prior to Initial Operation 16 Initial Operation 17 Environment and Recycling 17 Customer Service and Guarantee 17 Certifi...

Страница 4: ...als Protect the indoor unit and the remote control from direct and indirect sunlight Do not expose the remote control to strong vibra tions Regularly check that condensation is not blocked from flowin...

Страница 5: ...oom 4 Timer button You can program the unit to automatically switch on or off within the next 24 hour period with the timer 5 Sleep button If the Sleep function is activated the set room tem perature...

Страница 6: ...e the COOL mode when you want to cool the room to the desired temperature Reduce the desired temperature by pressing the Temperature button in 0 5 C in crements After you hear a beep the COMP display...

Страница 7: ...room air conditioner is to be switched off at a later time press when of these buttons when the remote control is on In both operating modes 12 0H appears in the lower right hand corner of the displa...

Страница 8: ...ce left right 6 Closed the front of the unit Shutting Down the Unit Temporary shutdown 1 Switch all indoor units off using the remote control 2 Disconnect the system with the main switch or fuse prote...

Страница 9: ...batteries with the correct polarity Transmission distance too great reception blocked Is the transmission signal at a dis tance of approx 3 m when the but ton is pressed Reduce distance to under 6 m...

Страница 10: ...e line RKM Inch mm 1 4 6 35 Connection intake line RKM Inch mm 1 2 12 7 Additional amount to add 2 g m 18 15 Dehumidification capacity l h 1 0 2 0 Power supply V Hz 230 1 50 Hz supplied via outdoor pa...

Страница 11: ...blocked by furniture curtains etc Make sure that the electrical terminals have been properly attached The refrigerant lines may not be bent or pressed Protect open refrigerant lines from moisture with...

Страница 12: ...mm screws bolts as well as washers to the ceiling An incline of approx 8 mm to the connection adaptor must be maintained to ensure that the condensation can flow freely Wall mount Ceiling mount Insta...

Страница 13: ...lled The electrical installations may only be performed by author ised personnel in line with the relevant regulations Local guidelines for operation as well as the requirements es tablished by local...

Страница 14: ...information The condensation drainage line is generally placed in the same guideway as the refrigerant lines If as a result of structural design conditions it is necessary to have a different guidewa...

Страница 15: ...ed on Kondensatab laufschlauch Entl ftungsschlauch kurz Pumpe Reservoir Ansaugschlauch lang Tropfwanne Condensation drainage hose Ventilation house short Pump Collection tray Reservoir Suction hose lo...

Страница 16: ...he condensation pump Before putting the pump into operation the lines that have been laid must be checked to ensure that they are functioning properly and leakproof 1 Switch the power supply of the pu...

Страница 17: ...n mode and dehu midifying mode 6 Adjust the plate fins correctly to prevent air from be ing distributed unfavourably 7 Familiarise the operator with the system and give him the certificate for initial...

Страница 18: ...permeability check of the connections on the outdoor part and indoor unit s OK problem Shut off valves on the outdoor unit open if applicable OK problem Test run of unit operation Compressor fan outdo...

Страница 19: ......

Страница 20: ...REMKO GmbH Co KG Klima und W rmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606260 E Mail info remko de Internet www remko de...

Отзывы: