background image

23 

Connections of the condensation pump on the wa-
ter side 

The reservoir is attached to the condensation collection 
tray connection of the indoor unit via a customer-
supplied hose (20 mm Ø). The factory-installed flexible 
hose of the condensation tray must be disassembled. 
The supplied ventilation hose must be used for the res-
ervoir to function properly. 
The end of the ventilation hose must at least be at the 
same height as the condensation tray to prevent water 
from overflowing. The supplied metal wire clips are 
used to secure the hose in a vertical position 
Keep the hose from being suspended which will prevent 
an air pocket from forming. 

Prior to Initial Operation 

 

After the pressure check has been performed, the vac-
uum pump must be connected to the valve connections 
of the outdoor part (see section “Impermeability Check”) 
by means of the manometer station and a vacuum cre-
ated. 
Prior to initial operation of the unit and after contact with 
the cold cycle, the following checks must be performed 
and documented in the initial operation log: 

à

Check the refrigerant lines, the outdoor part and the 
indoor unit to ensure that any remaining moisture 
has been completely removed. 

à

Check all refrigerant lines and shut-off valves for 
leaks with a leak locator spray or soapy water when 
the unit is not in operation. 

à

Check that the electrical connection between the in-
door unit and the outer part has been correctly at-
tached. 

à

Check the electrical control line to ensure that it is 
securely attached in the terminals. 

Loose lines in the terminals can cause fires. 

à

Check the refrigerant lines and insulation for dam-
age. 

à

Check all fixtures and suspended parts to ensure 
that they are in the proper position and at the correct 
height. 

G

 

If the refrigerant line is longer than 5 m, more re-
frigerant should be added to the system

Electrical connection of the condensation pump 

There is an electrical connection area located under the 
hose connections. This area also a cover that can be 
taken on and off. 
The pump is equipped with an alarm contact that 
switches off the indoor unit and can also control a cus-
tomer-installed malfunction/alarm system. 
The electrical connections may only be made by author-
ised service personnel in accordance with the relevant 
regulations. 
Local guidelines for operation as well as the require-
ments established by local energy supply companies 
must be observed for setup and initial operation. 

Initial operation of the condensation pump 

Before putting the pump into operation, the lines that 
have been laid must be checked to ensure that they are 
functioning properly and leakproof. 
1.   Switch the power supply of the pump on. 
2.  Pour distilled water into the condensation tray until 

the pump switches on from the reservoir. 

Pump operation can be heard when it is being oper-
ated for the first time or being put back into opera-
tion. After it has run for short period, the noise nor-
malises. 

3.  Keep in mind that the pump automatically switches 

off once the water has been pumped out of the res-
ervoir. 

4.  If upon initial operation there is a lot of noise from vi-

brating hoses, insulate these hoses using foam 
hoses. 

Condensation buildup is prevented when using insu-
lated hoses sealed against diffusion.

 

5.   Check the function of the alarm contact by drastically 

increasing the amount of water. 

The alarm contact should switch off the unit. 

G

 

Always use a contactor or relay to switch off the 
outdoor part! 

The 6 mm (inner diameter) thick hose is placed at a 
maximum height difference of 6 meters to the drain. 
If the pump is installed outside the unit, a maximum 
height difference of 3 meters between the lower edge of 
the unit and the pump mounted above may not be ex-
ceeded. The condensation line should be as vertical as 
possible to guide the condensation. 
The reservoir and pump are connected to one another 
with the long suction hose and the plugable sensor line 
from the reservoir. To ensure that the pump operates as 
quietly as possible, the suction hose should not be 
shortened. 

 

 

Kondensatab-
laufschlauch

Entlüftungsschlauch

(kurz)

Pumpe

Reservoir

Ansaugschlauch
(lang)

Tropfwanne

Condensation 
drainage hose 

Ventilation hose 

short 

Pump 

Condensation tray 

Reservoir 
Suction hose 
(long) 

Содержание RKS 327-371 H

Страница 1: ...REMKO powerful like a bear REMKO RKS 327 H 371 H Split Design Wall Mounted Room Air Conditioners Edition GB P07 Operation Technology Spare Parts...

Страница 2: ......

Страница 3: ...tion 20 Wiring Diagram 21 Condensation 21 Prior to Initial Operation 23 Adding Refrigerant 24 Initial Operation 24 Error Analysis for Service Personnel 25 Environment and Recycling 25 Customer Service...

Страница 4: ...ressure cleaners etc Protect the indoor units and the remote control against moisture Protect the units and the remote control from direct sunlight Protect the electrical cords and connection lines fr...

Страница 5: ...r part RKS H AT 3 Infrared remote control 4 Connection lines 5 Air filter 6 Air intake grille 7 Air outlet plate fins with swing motor 8 Plate fins for directing air or manually covered 9 Display and...

Страница 6: ...down to the set colder temperature 3 Dehumidifying mode DRY Most of the air in the room is dehumidified in this mode 4 Heating mode HEAT In this mode the colder air in the room is warmed up to the set...

Страница 7: ...on the right hand side of the indoor unit Timer buttons The Timer buttons are used to program a delayed start or stop If the air conditioner is to be switched on at a later time press the button and...

Страница 8: ...N AUTO Set temperature is below the room temperature AUTO FAN Functional process Clock button The time can be set by pressing and holding the button for two seconds Pressing and then releasing the but...

Страница 9: ...he plate fin position can be set The fan switches off at certain intervals to lower the temperature of the plate fins DEHUMIDIFYING MODE Functional process DRY COOL Fan button When the FAN button is p...

Страница 10: ...blocked from addi tional programming or setting changes The symbol appears on the display Functional process Manual air distribution On the air outlet side of the units there are individually adjusta...

Страница 11: ...ties from the fil ters with lukewarm water If the filters are wet dry before replacing 3 Remove the right and left air filter from the front 8 Reinsert the filters and close the air intake grille Clea...

Страница 12: ...amming and wait for the unit to start New batteries have been incor rectly inserted Are the ends lined up properly Insert batteries correctly Transmission distance is too far reception disrupted Trans...

Страница 13: ...3 44 42 44 47 Dimensions H W D mm 265 785 150 300 900 175 315 1025 210 320 1180 200 Weight kg 10 10 14 20 Outdoor part RKS 327 H AT RKS 335 H AT RKS 350 H AT RKS 371 H AT Operating range C 7 to 43 Ref...

Страница 14: ...H IT RKS 335 H AT RKS 335 H IT 47 30 900 448 840 340 340 175 300 785 150 265 484 450 290 290 113 45 1025 315 210 275 210 240 301 420 450 356 392 464 350 57 1190 320 508 146 475 1138 55 55 441 435 205...

Страница 15: ...c connection and sensor lines leading to the outdoor part should be placed together with the refrigerant lines The indoor unit and the outdoor part of the REMKO air conditioner are adjusted to one ano...

Страница 16: ...should be installed at least 20 cm above the expected snow level to prevent snow from entering the outdoor part A base console can be purchased as an accessory Wind If the unit is operated primarily i...

Страница 17: ...sembling the wall mount To assemble the wall mount parts of the housing panel of the indoor unit must be disassembled 1 Place the indoor unit with the backside facing up on a soft surface 2 Remove the...

Страница 18: ...r crack 4 Use the following tools for assembly GOnly tools approved for use in cold conditions may be used 13 Insulate the installed refrigerant lines including the connector against heat 14 Only use...

Страница 19: ...lity Test Once all connections have been made the manometer station is connected to the corresponding valve connec tions as described below red small valve injection pressure blue large valve suction...

Страница 20: ...distance to be covered with this line is more than 10 m the line must be length ened by the customer Electrical wiring diagram RKS 327 335 H AT Condenser fan 1 2 N 3 4 Compressor Winter regulation mec...

Страница 21: ...f the indoor units are equipped with a condensation hose This hose must be placed at an incline to ensure that the condensation drains Condensation hose on the outdoor part Condensation can be guided...

Страница 22: ...lines If as a result of structural design conditions it is nec essary to have a different guideway for the conden sation hose the hose can also be guided to the in door unit through a different drain...

Страница 23: ...The pump is equipped with an alarm contact that switches off the indoor unit and can also control a cus tomer installed malfunction alarm system The electrical connections may only be made by author i...

Страница 24: ...for the test Check the following items Check refrigerant lines for leaks Check that the ventilator and compressor are run ning evenly Check that cold air is being expelled from the indoor unit and war...

Страница 25: ...and the guarantee becomes null and void Customer Service and Guarantee For the guarantee to be valid the purchaser or his cus tomer must completely fill out the guarantee certificate enclosed with all...

Страница 26: ...elevation arcs units Condensation pump yes know Total refrigerant amount g Result Visual check Setup of outdoor part and indoor unit R good Q poor Heat exchanger insulation lines R good Q poor Electr...

Страница 27: ......

Страница 28: ...REMKO GmbH Co KG Klima und W rmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606260...

Отзывы: