Minimum distances 

The chart below indicates the minimum distances that 
must be maintained to ensure that the units operate 
properly. 

 

RKS 327 H AT 

200 

900 

300 

100 

200 

RKS 335 H AT 

200 

900 

300 

100 

200 

RKS 350 H AT 

200 

1200 

300 

150 

400 

RKS 371 H AT 

300 

1500 

300 

150 

600 

Assembly Instructions for 
Service Personnel 

 

Important instructions prior to installation 

à

Only use the swivel nuts supplied with the refrigerant 
lines. 

Other components can damage the thread.

 

à

The units are only suitable for limited use in com-
puter rooms because after a power outage there is 
no guarantee that the units will restart. It is also pos-
sible that they will only start again with specific set-
tings. 

à

The unit-specific, maximum length of the refrigerant 
line is 10 or 15 m respectively with a maximum 
height difference of 5 or 8 m. 

à

Ensure the contents of the package are complete 
and that the unit has no visible damage from trans-
port. 

à

Any problems must be communicated directly to 
your contract partner and the shipping company. 

Subsequent complaints will not be acknowledged. 

à

Place the units in their original packaging as close as 
possible to the location where they will be set up to 
prevent damage from transport. 

à

Do not install the outdoor part and the indoor unit in 
the direct vicinity of objects that emit intense heat. 

Reflective glass surfaces, lights, etc.

 

à

The condensation line must be placed at an incline 
of at least 2 % . 

à

If this line is connected to the drainage line, an odour 
seal must be installed the upper edge of which may 
not extend beyond the lower edge of the indoor unit. 

à

Prior to installation, the electrical values must be 
checked for consistency with the data on the type 
plate. 

à

Remove the protective caps of the unit connections 
just before connecting the refrigerant lines. 

à

All electrical connections must meet the relevant re-
quirements.  

à

The power supply is only connected to the indoor 
unit. The unit-specific connection and sensor lines 
leading to the outdoor part should be placed together 
with the refrigerant lines. 

à

The indoor unit and the outdoor part of the REMKO 
air-conditioner are adjusted to one another from a 
technical standpoint.

 

The guarantee becomes null and void if third-party 
components are used .

 

à

Remember that when installing and maintaining air 
conditioners, high-pressure and electrical current 
can pose hazards. 

à

During unit operation, some components in the cold 
cycle can reach temperatures of more than 70 °C. 

Be especially careful when covers are removed. 

à

The air intake and outlet openings may not be 
blocked by furniture, curtains, etc. 

à

The refrigerant lines may not be bent or pressed. 

à

Protect open refrigerant lines from moisture with 
caps or tape. 

à

Prevent unnecessary bends to minimise the pres-
sure loss in the refrigerant lines and ensure that the 
compressor oil can recirculate properly. 

à

If the outdoor part is mounted above the indoor unit, 
make sure to take steps to recirculate the oil (oil ele-
vation arcs)

.

 

à

Select a location to set up the unit where air can flow 
freely in and out of the device. Minimum distances 
can be found in chart below

 

à

Make sure that the electrical lines have been prop-
erly attached in the electrical terminals. 

à

Make sure that all refrigerant lines including all con-
nectors and valves are insulated against heat and 
sealed against diffusion. 

Wall lead-throughs 

Wall lead-throughs are necessary to establish the con-
nection between the indoor unit and the outdoor unit. 
Please observe the following: 

à

For the connection line to the outdoor part, a lead-
through of at least 70 mm in diameter must be cre-
ated. 

à

The lead-through must be placed at an incline of at 
least 10 mm between the inside and outside. 

à

Before beginning work, make sure that there are no 
supply lines (water, etc.) located in the vicinity of the 
wall lead-through. 

à

We recommend cushioning the inside of the hole or 
lining it with a PVC pipe to prevent the lines from be-
ing damaged. 

à

After assembly is complete, the wall lead-through 
must be sealed with a suitable sealing compound. 

Do not use any materials containing cement or lime!

 

Содержание RKS 327-371 H

Страница 1: ...REMKO powerful like a bear REMKO RKS 327 H 371 H Split Design Wall Mounted Room Air Conditioners Edition GB P07 Operation Technology Spare Parts...

Страница 2: ......

Страница 3: ...tion 20 Wiring Diagram 21 Condensation 21 Prior to Initial Operation 23 Adding Refrigerant 24 Initial Operation 24 Error Analysis for Service Personnel 25 Environment and Recycling 25 Customer Service...

Страница 4: ...ressure cleaners etc Protect the indoor units and the remote control against moisture Protect the units and the remote control from direct sunlight Protect the electrical cords and connection lines fr...

Страница 5: ...r part RKS H AT 3 Infrared remote control 4 Connection lines 5 Air filter 6 Air intake grille 7 Air outlet plate fins with swing motor 8 Plate fins for directing air or manually covered 9 Display and...

Страница 6: ...down to the set colder temperature 3 Dehumidifying mode DRY Most of the air in the room is dehumidified in this mode 4 Heating mode HEAT In this mode the colder air in the room is warmed up to the set...

Страница 7: ...on the right hand side of the indoor unit Timer buttons The Timer buttons are used to program a delayed start or stop If the air conditioner is to be switched on at a later time press the button and...

Страница 8: ...N AUTO Set temperature is below the room temperature AUTO FAN Functional process Clock button The time can be set by pressing and holding the button for two seconds Pressing and then releasing the but...

Страница 9: ...he plate fin position can be set The fan switches off at certain intervals to lower the temperature of the plate fins DEHUMIDIFYING MODE Functional process DRY COOL Fan button When the FAN button is p...

Страница 10: ...blocked from addi tional programming or setting changes The symbol appears on the display Functional process Manual air distribution On the air outlet side of the units there are individually adjusta...

Страница 11: ...ties from the fil ters with lukewarm water If the filters are wet dry before replacing 3 Remove the right and left air filter from the front 8 Reinsert the filters and close the air intake grille Clea...

Страница 12: ...amming and wait for the unit to start New batteries have been incor rectly inserted Are the ends lined up properly Insert batteries correctly Transmission distance is too far reception disrupted Trans...

Страница 13: ...3 44 42 44 47 Dimensions H W D mm 265 785 150 300 900 175 315 1025 210 320 1180 200 Weight kg 10 10 14 20 Outdoor part RKS 327 H AT RKS 335 H AT RKS 350 H AT RKS 371 H AT Operating range C 7 to 43 Ref...

Страница 14: ...H IT RKS 335 H AT RKS 335 H IT 47 30 900 448 840 340 340 175 300 785 150 265 484 450 290 290 113 45 1025 315 210 275 210 240 301 420 450 356 392 464 350 57 1190 320 508 146 475 1138 55 55 441 435 205...

Страница 15: ...c connection and sensor lines leading to the outdoor part should be placed together with the refrigerant lines The indoor unit and the outdoor part of the REMKO air conditioner are adjusted to one ano...

Страница 16: ...should be installed at least 20 cm above the expected snow level to prevent snow from entering the outdoor part A base console can be purchased as an accessory Wind If the unit is operated primarily i...

Страница 17: ...sembling the wall mount To assemble the wall mount parts of the housing panel of the indoor unit must be disassembled 1 Place the indoor unit with the backside facing up on a soft surface 2 Remove the...

Страница 18: ...r crack 4 Use the following tools for assembly GOnly tools approved for use in cold conditions may be used 13 Insulate the installed refrigerant lines including the connector against heat 14 Only use...

Страница 19: ...lity Test Once all connections have been made the manometer station is connected to the corresponding valve connec tions as described below red small valve injection pressure blue large valve suction...

Страница 20: ...distance to be covered with this line is more than 10 m the line must be length ened by the customer Electrical wiring diagram RKS 327 335 H AT Condenser fan 1 2 N 3 4 Compressor Winter regulation mec...

Страница 21: ...f the indoor units are equipped with a condensation hose This hose must be placed at an incline to ensure that the condensation drains Condensation hose on the outdoor part Condensation can be guided...

Страница 22: ...lines If as a result of structural design conditions it is nec essary to have a different guideway for the conden sation hose the hose can also be guided to the in door unit through a different drain...

Страница 23: ...The pump is equipped with an alarm contact that switches off the indoor unit and can also control a cus tomer installed malfunction alarm system The electrical connections may only be made by author i...

Страница 24: ...for the test Check the following items Check refrigerant lines for leaks Check that the ventilator and compressor are run ning evenly Check that cold air is being expelled from the indoor unit and war...

Страница 25: ...and the guarantee becomes null and void Customer Service and Guarantee For the guarantee to be valid the purchaser or his cus tomer must completely fill out the guarantee certificate enclosed with all...

Страница 26: ...elevation arcs units Condensation pump yes know Total refrigerant amount g Result Visual check Setup of outdoor part and indoor unit R good Q poor Heat exchanger insulation lines R good Q poor Electr...

Страница 27: ......

Страница 28: ...REMKO GmbH Co KG Klima und W rmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606260...

Отзывы: