background image

Operating structure

> 5 sec.

< 2 sec.

< 2 sec.

> 5 sec.

< 2 sec.

< 2 sec.

< 2 sec.

< 2 sec.

> 5 sec.

+

+

/

/

Open configuration

Value/parameter up

Open submenu/value

Close configuration

Value/parameter down

Close submenu

+
+

Standard display

Change target values

C/H target value change

Value change in cooling 

between 10.0 and 18.0 and in 

heating between 36.0 and 43.0 

with the key 

/

, save with 

"SET".

Param.level 2  with password

All parameters

Input

Password

All parameters of 

the Submenus:

St, CF, Sd, ES, CO,  

Ar, dF

Display target values

Display target value cooling

Current target value in cooling mode

Display target value heating

Current target value in heating mode

Menu  without password

Current fault list

currently pending, non-

resettable faults are displayed 

with "no", resettable faults are 

displayed with "rSt"; resetting 

with the SET key.

Operating hours compressor 1

Value in hours, resettable after 

maintenance, etc. by pressing the 

SET key (5 sec.).

Parameter backup to 

hotkey

Using a plugged-in hotkey 

the current parameters of the 

controller can be transferred to 

the hotkey.

Operating hours compressor 2

Value in hours, resettable after 

maintenance, etc. by pressing the 

SET key (5 sec.).

Reset fault list

Faults are displayed in the 

sequence n01 (oldest) to n50 

(most recent). Through input of 

the password under "ArSt" the 

list can be reset.

Pump operating hours

Value in hours, resettable after 

maintenance, etc. by pressing 

the SET key (5 sec.).

Defrosting period

Value in min. and sec. until the 

next defrosting interval

Param.level 1  without password

St 01  Target value cooling

St 02  Hysteresis cooling

St 03  Target value heating

St 04  Hysteresis heating

St 09  Output range

Pr2  Password
CF 16 ID 5 Configuration

CF 24 Pb 1 Shut-off

CF 25 Pb 2 Shut-off

CF 26 Pb 3 Shut-off

CF 27 Pb 4 Shut-off

CF 28 Unit active/operating mode

CF 29 Autom.  changeover target value

CF 30 Hysteresis changeover

CF 31 Cooling / heating display icon

CF 32 °C/°F conversion

CF 37 Company version

Pr2  Password
Sd 01 Dyn. target value configuration

Sd 02 Shut-off dyn. target value C

Sd 03 Shut-off dyn. target value H

Sd 04  Outside temp. sensor target value C

Sd 05  Outside temp. sensor target value H

Sd 06  Outside temp. sensor hysteresis C

Sd 07 Outside temp. sensor Hysteresis H

Pr2  Password
ES 01  Switch-on time

ES 02  Shut-off time

ES 03  Activation Monday

ES 04  Activation Tuesday

ES 05  Activation Wednesday

ES 06  Activation Thursday

ES 07  Activation Friday

ES 08  Activation Saturday

ES 09  Activation Sunday

ES 10  Target value cooling

ES 11  Hysteresis cooling

ES 12  Target value heating

ES 13  Hysteresis heating

Pr2  Password

Ar 03  Target value anti-freeze protection fault C

Ar 04  Hysteresis anti-freeze protection fault C

Ar 08  Target value anti-freeze protection heating C

Ar 09  Target value anti-freeze protection heating H

Ar 10  Target value cooling  W/W

Ar 11  Hysteresis cooling  W/W

Ar 12  Hysteresis heating  W/W

Ar 13  Config. anti-freeze protection heating

Ar 14  Config. Cooling

Ar 20  E-heating active/operating mode

Ar 21  Target value air temp. active

Ar 22  Hysteresis air temp. active htg

Ar 24  After-run time E-heating 2

Ar 25  Target value air temp. active compr.

Ar 26  Target value air temp. locked compr.

Ar 27  Target value anti-freeze protection fault H

Ar 28  Hysteresis anti-freeze protection fault H

Ar 29  Target value external pump W/W

Ar 30  Hysteresis external pump W/W

Ar 31  Pump active/operating mode

Ar 32  Pump active/operating mode

Pr2 

Password

dF 02  Defrosting input parameter

dF 03  Target value defrosting start

dF 04  Target value defrosting end

dF 05  Min. operating time before  

 

defrosting start

dF 06  Minimum defrosting time

dF 07  Maximum defrosting time

dF 10  Min.time defrosting interval

dF 11  Target value defrosting begin (df 10)

dF 12  Target value defrosting (dF 10)

dF 16  Active fault low temperature

dF 19  Target value forced defrost. begin

dF 20  Hysteresis forced defrost. begin

Pr2 

Password

Pr2    Password

Pr2    Password

Pr2  Password

All open 

parameters

Target values

Configuration

Dyn. target value

Energy-saving 

cycle

Compressor

Fan

Anti-freeze 

protection

Faults

Defrost

Display adaptive target value

Current, adaptive target value

Display of current values

Medium outlet display

Current value (supply)

Medium intake display

Current value (return)

Condenser display

Current value of condenser tem-

perature or pressure (with winter 

pressure controller accessory)

13

Содержание KWL 130

Страница 1: ...NOX KWL 220 INOX KWL 270 INOX KWL 320 INOX KWL 370 INOX KWL 130 H KWL 160 H KWL 180 H INOX KWL 220 H INOX KWL 270 H INOX KWL 320 H INOX KWL 370 H INOX Air cooled Chiller and Air cooled Chiller with He...

Страница 2: ......

Страница 3: ...nsport and packaging 5 System description 5 6 System configuration 7 Operation 7 13 Care and maintenance 14 Shut down 14 Trouble shooting and customer service 15 17 Installation instructions for quali...

Страница 4: ...e malfunctions Equipment and components may not be operated in areas where there is an increased risk of damage Observe the minimum clearances The electrical supply is to be adapted to the requirement...

Страница 5: ...nit an air to water chiller takes heat out of the operating medium to be cooled water or a mixture of water and glycol within a closed medium circuit in the evaporator plate heat exchanger and gives i...

Страница 6: ...er dryer 13 Schrader valve 14 Thermal expansion valve cooling 15 Sensor medium intake 16 Sensor medium outlet 17 Fan control sensor Construction 1 1 3 3 4 4 5 5 6 6 7 7 17 17 8 8 9 9 14 14 11 11 11 10...

Страница 7: ...output can be transmitted to the room to be cooled via the floor the building structure or by means of ceiling cooling For each of the different systems a minimum flow volume and a minimum medium vol...

Страница 8: ...e is set The controller is divided into a left value display and a right function display M key With this key you reach the function menu or can adjust time and date SET With this key the selection of...

Страница 9: ...on a different functional meaning of the display can be programmed Mode setting External contact Enable open Display of the current operating values The normal display shows the current medium intake...

Страница 10: ...e is longer than 3 minutes the current target value is kept The medium temperature increases and the compressor is switched off when the shut off point is reached B Factory setting for target value St...

Страница 11: ...ange the set value press the key for approx 5 seconds The display begins to blink With the or keys the value can be adjusted within the limits defined at the factory St 07 St 08 St 07 36 C Minimum tar...

Страница 12: ...rd The menu program is automatically closed after 15 seconds if the controller is not actuated Querying the fault reports See chapter on troubleshooting and customer service open ALrM submenu short te...

Страница 13: ...mp sensor target value C Sd 05 Outside temp sensor target value H Sd 06 Outside temp sensor hysteresis C Sd 07 Outside temp sensor Hysteresis H Pr2 Password ES 01 Switch on time ES 02 Shut off time ES...

Страница 14: ...nsure trouble free operation and a long service life Prior to performing any work ensure the equipment is isolated from the voltage supply and secured to prevent accidental switch on CAUTION Care Ensu...

Страница 15: ...not start the compressor icon in the display is flashing Delay time Wait out the delay time max 360 sec the compressor should then start The lower display flashes and alternately shows an alphanumeri...

Страница 16: ...n the cooling circuit OK Have checked by a specialist A05 Excessive temperature condenser Are the fans turning Is the condenser s air intake free of obstacles Have checked by a specialist A06 Excess t...

Страница 17: ...onfiguration error x x x x x x ACF3 Configuration error x x x x x x ACF4 Configuration error x CF28 x x x x AFr Power supply x x x x x x Reset 1 Faults with automatic reset The resetting of the alarm...

Страница 18: ...on lines valves and connections must be insulated against vapour diffusion If necessary also insulate the condensate line only units with HP function In dual systems with cooling and heating modes the...

Страница 19: ...the fins and reduces the heat released by the finned heat exchanger The unit should whenever possible be installed on the north side of the building If necessary take measures to provide sufficient sh...

Страница 20: ...KWL 270 H 320 H KWL 370 H Minimum clearances The following illustration indicates the minimum clearances for trou ble free operation of the system These protection zones serve to ensure unrestricted...

Страница 21: ...Load point F 55 59 72 58 60 75 6 Weight loads All values in kg KWL 130 H 160 H KWL 180 H 220 H KWL 270 H 320 H KWL 370 H KWL H with medium storage tank A C B D A C E F B D A C E F B D A C B D Installa...

Страница 22: ...ompo nents is to be simulated using a pipe leg regulating valve The pipe sizing is to be de signed so that the required minimum flow volume is not under cut A permanent large flow volume must be ensur...

Страница 23: ...and safety data sheets of the glycol type which is used must be ob served CAUTION Propor tion glycol Frost protection 2 C Correction factors when using a mixture of glycol and water Cooling capacity...

Страница 24: ...ent of the realisation of a cooling heating system the installation of another diaphragm expansion vessel may be necessary Safety valve Safety valves limit excess operat ing pressure due to excess war...

Страница 25: ...e condensate If necessary fit supplementary pipe heating After completed installation check that the condensate run off is unobstructed and ensure that the line is durably leak tight Condensate drain...

Страница 26: ...n accordance with the applica ble regulations Check all terminal points for stability The supply line must be ad equately insulated on site and the voltage drop may not exceed permissible values Make...

Страница 27: ...the programming the cooling mode is activated with a closed contact between terminals 2 and 3 Display temperatures 5 sec short short short short short change value short 8 External potential free cont...

Страница 28: ...rd With a modulating output voltage the condenser fan s speed can be adjusted to the condenser tem perature and in this way hold the noise level to a minimum The iCHiLL controller determines the curre...

Страница 29: ...signal 2 6 Cooling heating switching 7 12V 8 0V 9 10 Cable remote control Compressor Probe Intake High pressure switch Probe Outlet Low pres sure switch Probe LN contr Diff press switch Pressure tran...

Страница 30: ...320 H KWL 130 H 160 H Compressor Circulation pump Fan controller Condenser fan 1 Condenser fan 2 Anti freeze heating cooling medium Accessories Reversing valve only KWL H CW heater Accessories REMKO...

Страница 31: ...ing switching 7 12V 8 0V 9 10 Cable remote control Probe Intake High pressure switch Probe Outlet Low pres sure switch Probe LN contr Diff press switch Pressure transducer pressure reg Accessories Ant...

Страница 32: ...V 8 0V 9 10 Cable remote control Compressor Probe Intake High pressure switch Probe Outlet Low pres sure switch Probe LN contr Diff press switch Pressure transducer pressure reg Accessories Circulatio...

Страница 33: ...M11 Condenser fan 2 RC1 Compressor crank case heating TA Transformer 230 12V TR 3 not used accessory pressure transducer TX1 Thermal contact fan 1 TX2 Thermal contact fan 2 KWL 370 H Component equipm...

Страница 34: ...AG The preliminary pressure for the diaphragm expansion vessel must be adjusted individually to the system layout the volume of the medium and the installation site If the unit is positioned at the lo...

Страница 35: ...k the cooling cycle for leaks Observe the manuals for the unit and all other components when commissioning the entire system Commissioning The systems are equipped with a phase sequence relay which pr...

Страница 36: ...d to the dimensions listed above to work after approx 3 min utes 5 Please note that the supply temperature at the nominal medium flow lies approx 5 K above the intake temperature The circulation pump...

Страница 37: ...ic curves KWL 130 H KWL 160 H KWL 180 H KWL 220 H KWL 320 H KWL 270 H KWL 370 H l sec l sec l sec l sec l sec l sec l sec Circulation pump U P I KWL 130 H 320 H 230 400V 0 37 0 5kW 2 5 1 4A KWL 370 H...

Страница 38: ...KWL 130 H kPa kPa l sec l sec kPa kPa l sec l sec kPa l sec kPa kPa l sec l sec KWL 160 H KWL 180 H KWL 220 H KWL 320 H KWL 270 H KWL 370 H Equipment pressure available REMKO KWL H 38...

Страница 39: ...We reserve the right to modify the dimensions and constructional design as part of the ongoing technical development process Exploded view KWL 130 H 220 H 4 5 6 9 10 11 12 2 1 14 15 16 7 13 3 9 39...

Страница 40: ...37 1110037 1110036 1110036 1110037 1110037 14 Circulation pump 1110033 1110033 1110033 1110033 1110033 1110033 1110033 1110033 15 Differential pressure switch 1110034 1110034 1110035 1110035 1110034 1...

Страница 41: ...loded view KWL 270 H 370 H We reserve the right to modify the dimensions and constructional design as part of the ongoing technical development process 7 16 18 17 3 4 9 10 5 6 11 14 1 15 19 2 12 13 4...

Страница 42: ...mpressor 1110088 1110089 1110090 1110088 1110089 1110090 14 Expansion valve cpl 1110030 1110091 1110092 1110030 1110091 1110092 15 Circulation pump 1110033 1110033 1110093 1110033 1110033 1110093 16 D...

Страница 43: ...0 5 5 12 2 5 9 14 4 5 9 16 5 6 0 17 6 6 0 18 8 6 1 21 8 6 1 45 10 4 5 6 12 3 5 8 14 0 5 8 14 9 5 9 16 0 5 9 18 5 6 0 12 1 6 5 14 2 6 6 16 2 6 6 17 5 6 7 18 4 6 7 21 3 6 7 KWL 180 H KWL 220 H Air intak...

Страница 44: ...4 43 7 1000 39 3 39 4 44 0 43 6 43 6 43 7 45 6 43 5 43 5 44 0 43 6 43 7 43 8 45 6 2000 41 1 41 1 43 4 42 9 43 0 43 0 47 1 42 7 42 7 43 4 42 9 43 1 43 3 47 1 4000 35 4 35 5 39 7 39 4 39 4 39 4 42 7 39...

Страница 45: ...4 4 64 5 44 6 41 Minimum flow volume medium m h 1 40 1 80 2 00 2 40 3 00 3 50 4 1 Maximum flow volume medium m h 3 40 4 50 5 20 6 20 7 80 9 00 10 70 Nominal pump pressure max kPa 207 0 195 0 188 0 177...

Страница 46: ...ing medium max 35 ethylene glycol max 35 propylene glycol Operating limits medium C 4 to 50 Max operating pressure medium kPa 300 Nominal flow volume medium C H m h 2 23 2 74 3 10 3 74 4 64 5 44 6 41...

Страница 47: ...12 D 32791 Lage Equipment machinery Implementation Air cooled water chiller and Air cooled water chiller with heat pump function Series Model REMKO KWL 130 KWL 160 KWL 180 INOX KWL 220 INOX KWL 270 IN...

Страница 48: ...ialists REMKO field staff are more than just sales representatives above all they must act as advisers to our customers in air conditioning and heating technology Customer Service Our equipment operat...

Отзывы: