Minimum/maximum medium flow

The chiller`s circulation pump gen-
erates a constant medium flow;
the result is a loss of pressure in 
the system and in the chiller. The 
differential pressure switch in the 
chiller measures the medium pres-
sure loss over the evaporator and 
switches the unit off if the mini-
mum flow volume is undercut.
The medium flow limit may like-
wise not be exceeded (maximum 
flow volume).
A 3-way valve with bypass and 
a hydraulic switch to establish a 
primary and secondary circuit or 
a volume dependent bypass are 
necessary to ensure a constant 
flow volume.

Minimum medium volume, of the 
system

As a consequence of the adaptive 
controller a storage tank is not 
mandatory. However, the mini-
mum medium volume may not be 
fallen short of in order to ensure 
fault-free operation of the unit.

individual pressure losses of each 
individual unit in the pipeline 
network design must be adjusted 
to the entire system. The nomi-
nal flow volumes for the medium 
adjust to the necessary values as 
a consequence of the pressure loss.

Valves for hydronic balancing

Through valves for hydronic bal-
ancing to be installed on-site,

Medium piping

Medium piping can be made of 
copper, steel or plastic. To minimise 
pressure losses, only streamlined 
fittings should be used.
When designing the layout, the 
large flow volumes in cold wa-
ter systems, high pressure losses 
in connection with water-glycol 
mixtures and the chiller's minimum 
flow volume must be taken into 
account.
The lines are to be insulated 
against vapour diffusion and, 
if necessary, the current Energy-
Savings-Ordinance (EnEV) must to 
be observed. UV resistance must 
be realised outdoors.

During use and 

disposal the product and safety 

data sheets of the glycol type 

which is used must be ob-

served.

 

!

   CAUTION

Propor-

tion 

glycol

Frost 

protection 

+-2°C

Correction factors when using a 

mixture of glycol * and water

Cooling 

capacity

Compressor capacity 

Cooling         Heating

Flow 

volume

Pressure 

loss

Vol. %

°C

K

L

K

P cooling

K

P heating

K

V

K

D

0

0

1

1

1,012

1

1

20

-9

0,981

0,988

1,012

1,040

1,19

35

-21

0,971

0,982

1,018

1,090

1,35

40

-26

0,968

0,981

1,019

1,105

1,51

Use the required type and 

mixture to ensure the freezing 

point.

 

!

   CAUTION

We recommend using an ethylene glycol mixture. Observe the safety and 
product data sheets for the glycol type being used.

Frost protection (accessories)

As a medium for a cold water
system, a water-glycol mixture 
is used as a rule. Depending on 
the use to which the glycol type 
and quantity is put, the viscos-
ity changes, the loss in pressure 
increases and the unit's cooling or 
heating capacity reduces. All sys-
tem components must be ap-
proved for use with glycol.
As a rule, the addition to the water 
of ethylene glycol, in a proportion 
of 34%, with inhibitors for corro-
sion protection is recommended. 
This concentration ensures anti-
freeze protection to –20°C; at lower 
temperatures, an ice porridge forms 
which has no explosive effect.
The toxicologically harmless 
propylene glycol should be used if 
there is a risk that the medium can 
come into contact with drinking 
water or food stuffs. To inhibit the 
explosive effects, a proportion of 
38% is necessary as a rule.

To regulate the circulation pump 
we recommend a main 
pipe regulating valve near the unit.

      NOTE

Pressure gauge and thermometer

The pressure gauge and thermom-
eter to be installed on-site at  
the intake and outlet serve to set 
the medium flow. The display 
should mean shut down In the  
system there are temperature 
sensors in the medium intake and 
medium outlet.
The temperature at the probes can 
be seen on the controller.

23

Содержание KWL 130

Страница 1: ...NOX KWL 220 INOX KWL 270 INOX KWL 320 INOX KWL 370 INOX KWL 130 H KWL 160 H KWL 180 H INOX KWL 220 H INOX KWL 270 H INOX KWL 320 H INOX KWL 370 H INOX Air cooled Chiller and Air cooled Chiller with He...

Страница 2: ......

Страница 3: ...nsport and packaging 5 System description 5 6 System configuration 7 Operation 7 13 Care and maintenance 14 Shut down 14 Trouble shooting and customer service 15 17 Installation instructions for quali...

Страница 4: ...e malfunctions Equipment and components may not be operated in areas where there is an increased risk of damage Observe the minimum clearances The electrical supply is to be adapted to the requirement...

Страница 5: ...nit an air to water chiller takes heat out of the operating medium to be cooled water or a mixture of water and glycol within a closed medium circuit in the evaporator plate heat exchanger and gives i...

Страница 6: ...er dryer 13 Schrader valve 14 Thermal expansion valve cooling 15 Sensor medium intake 16 Sensor medium outlet 17 Fan control sensor Construction 1 1 3 3 4 4 5 5 6 6 7 7 17 17 8 8 9 9 14 14 11 11 11 10...

Страница 7: ...output can be transmitted to the room to be cooled via the floor the building structure or by means of ceiling cooling For each of the different systems a minimum flow volume and a minimum medium vol...

Страница 8: ...e is set The controller is divided into a left value display and a right function display M key With this key you reach the function menu or can adjust time and date SET With this key the selection of...

Страница 9: ...on a different functional meaning of the display can be programmed Mode setting External contact Enable open Display of the current operating values The normal display shows the current medium intake...

Страница 10: ...e is longer than 3 minutes the current target value is kept The medium temperature increases and the compressor is switched off when the shut off point is reached B Factory setting for target value St...

Страница 11: ...ange the set value press the key for approx 5 seconds The display begins to blink With the or keys the value can be adjusted within the limits defined at the factory St 07 St 08 St 07 36 C Minimum tar...

Страница 12: ...rd The menu program is automatically closed after 15 seconds if the controller is not actuated Querying the fault reports See chapter on troubleshooting and customer service open ALrM submenu short te...

Страница 13: ...mp sensor target value C Sd 05 Outside temp sensor target value H Sd 06 Outside temp sensor hysteresis C Sd 07 Outside temp sensor Hysteresis H Pr2 Password ES 01 Switch on time ES 02 Shut off time ES...

Страница 14: ...nsure trouble free operation and a long service life Prior to performing any work ensure the equipment is isolated from the voltage supply and secured to prevent accidental switch on CAUTION Care Ensu...

Страница 15: ...not start the compressor icon in the display is flashing Delay time Wait out the delay time max 360 sec the compressor should then start The lower display flashes and alternately shows an alphanumeri...

Страница 16: ...n the cooling circuit OK Have checked by a specialist A05 Excessive temperature condenser Are the fans turning Is the condenser s air intake free of obstacles Have checked by a specialist A06 Excess t...

Страница 17: ...onfiguration error x x x x x x ACF3 Configuration error x x x x x x ACF4 Configuration error x CF28 x x x x AFr Power supply x x x x x x Reset 1 Faults with automatic reset The resetting of the alarm...

Страница 18: ...on lines valves and connections must be insulated against vapour diffusion If necessary also insulate the condensate line only units with HP function In dual systems with cooling and heating modes the...

Страница 19: ...the fins and reduces the heat released by the finned heat exchanger The unit should whenever possible be installed on the north side of the building If necessary take measures to provide sufficient sh...

Страница 20: ...KWL 270 H 320 H KWL 370 H Minimum clearances The following illustration indicates the minimum clearances for trou ble free operation of the system These protection zones serve to ensure unrestricted...

Страница 21: ...Load point F 55 59 72 58 60 75 6 Weight loads All values in kg KWL 130 H 160 H KWL 180 H 220 H KWL 270 H 320 H KWL 370 H KWL H with medium storage tank A C B D A C E F B D A C E F B D A C B D Installa...

Страница 22: ...ompo nents is to be simulated using a pipe leg regulating valve The pipe sizing is to be de signed so that the required minimum flow volume is not under cut A permanent large flow volume must be ensur...

Страница 23: ...and safety data sheets of the glycol type which is used must be ob served CAUTION Propor tion glycol Frost protection 2 C Correction factors when using a mixture of glycol and water Cooling capacity...

Страница 24: ...ent of the realisation of a cooling heating system the installation of another diaphragm expansion vessel may be necessary Safety valve Safety valves limit excess operat ing pressure due to excess war...

Страница 25: ...e condensate If necessary fit supplementary pipe heating After completed installation check that the condensate run off is unobstructed and ensure that the line is durably leak tight Condensate drain...

Страница 26: ...n accordance with the applica ble regulations Check all terminal points for stability The supply line must be ad equately insulated on site and the voltage drop may not exceed permissible values Make...

Страница 27: ...the programming the cooling mode is activated with a closed contact between terminals 2 and 3 Display temperatures 5 sec short short short short short change value short 8 External potential free cont...

Страница 28: ...rd With a modulating output voltage the condenser fan s speed can be adjusted to the condenser tem perature and in this way hold the noise level to a minimum The iCHiLL controller determines the curre...

Страница 29: ...signal 2 6 Cooling heating switching 7 12V 8 0V 9 10 Cable remote control Compressor Probe Intake High pressure switch Probe Outlet Low pres sure switch Probe LN contr Diff press switch Pressure tran...

Страница 30: ...320 H KWL 130 H 160 H Compressor Circulation pump Fan controller Condenser fan 1 Condenser fan 2 Anti freeze heating cooling medium Accessories Reversing valve only KWL H CW heater Accessories REMKO...

Страница 31: ...ing switching 7 12V 8 0V 9 10 Cable remote control Probe Intake High pressure switch Probe Outlet Low pres sure switch Probe LN contr Diff press switch Pressure transducer pressure reg Accessories Ant...

Страница 32: ...V 8 0V 9 10 Cable remote control Compressor Probe Intake High pressure switch Probe Outlet Low pres sure switch Probe LN contr Diff press switch Pressure transducer pressure reg Accessories Circulatio...

Страница 33: ...M11 Condenser fan 2 RC1 Compressor crank case heating TA Transformer 230 12V TR 3 not used accessory pressure transducer TX1 Thermal contact fan 1 TX2 Thermal contact fan 2 KWL 370 H Component equipm...

Страница 34: ...AG The preliminary pressure for the diaphragm expansion vessel must be adjusted individually to the system layout the volume of the medium and the installation site If the unit is positioned at the lo...

Страница 35: ...k the cooling cycle for leaks Observe the manuals for the unit and all other components when commissioning the entire system Commissioning The systems are equipped with a phase sequence relay which pr...

Страница 36: ...d to the dimensions listed above to work after approx 3 min utes 5 Please note that the supply temperature at the nominal medium flow lies approx 5 K above the intake temperature The circulation pump...

Страница 37: ...ic curves KWL 130 H KWL 160 H KWL 180 H KWL 220 H KWL 320 H KWL 270 H KWL 370 H l sec l sec l sec l sec l sec l sec l sec Circulation pump U P I KWL 130 H 320 H 230 400V 0 37 0 5kW 2 5 1 4A KWL 370 H...

Страница 38: ...KWL 130 H kPa kPa l sec l sec kPa kPa l sec l sec kPa l sec kPa kPa l sec l sec KWL 160 H KWL 180 H KWL 220 H KWL 320 H KWL 270 H KWL 370 H Equipment pressure available REMKO KWL H 38...

Страница 39: ...We reserve the right to modify the dimensions and constructional design as part of the ongoing technical development process Exploded view KWL 130 H 220 H 4 5 6 9 10 11 12 2 1 14 15 16 7 13 3 9 39...

Страница 40: ...37 1110037 1110036 1110036 1110037 1110037 14 Circulation pump 1110033 1110033 1110033 1110033 1110033 1110033 1110033 1110033 15 Differential pressure switch 1110034 1110034 1110035 1110035 1110034 1...

Страница 41: ...loded view KWL 270 H 370 H We reserve the right to modify the dimensions and constructional design as part of the ongoing technical development process 7 16 18 17 3 4 9 10 5 6 11 14 1 15 19 2 12 13 4...

Страница 42: ...mpressor 1110088 1110089 1110090 1110088 1110089 1110090 14 Expansion valve cpl 1110030 1110091 1110092 1110030 1110091 1110092 15 Circulation pump 1110033 1110033 1110093 1110033 1110033 1110093 16 D...

Страница 43: ...0 5 5 12 2 5 9 14 4 5 9 16 5 6 0 17 6 6 0 18 8 6 1 21 8 6 1 45 10 4 5 6 12 3 5 8 14 0 5 8 14 9 5 9 16 0 5 9 18 5 6 0 12 1 6 5 14 2 6 6 16 2 6 6 17 5 6 7 18 4 6 7 21 3 6 7 KWL 180 H KWL 220 H Air intak...

Страница 44: ...4 43 7 1000 39 3 39 4 44 0 43 6 43 6 43 7 45 6 43 5 43 5 44 0 43 6 43 7 43 8 45 6 2000 41 1 41 1 43 4 42 9 43 0 43 0 47 1 42 7 42 7 43 4 42 9 43 1 43 3 47 1 4000 35 4 35 5 39 7 39 4 39 4 39 4 42 7 39...

Страница 45: ...4 4 64 5 44 6 41 Minimum flow volume medium m h 1 40 1 80 2 00 2 40 3 00 3 50 4 1 Maximum flow volume medium m h 3 40 4 50 5 20 6 20 7 80 9 00 10 70 Nominal pump pressure max kPa 207 0 195 0 188 0 177...

Страница 46: ...ing medium max 35 ethylene glycol max 35 propylene glycol Operating limits medium C 4 to 50 Max operating pressure medium kPa 300 Nominal flow volume medium C H m h 2 23 2 74 3 10 3 74 4 64 5 44 6 41...

Страница 47: ...12 D 32791 Lage Equipment machinery Implementation Air cooled water chiller and Air cooled water chiller with heat pump function Series Model REMKO KWL 130 KWL 160 KWL 180 INOX KWL 220 INOX KWL 270 IN...

Страница 48: ...ialists REMKO field staff are more than just sales representatives above all they must act as advisers to our customers in air conditioning and heating technology Customer Service Our equipment operat...

Отзывы: