REMKO KWL (H)
46
Technical data
Series
KWL
130 H
KWL
160 H
KWL
180 H
KWL
220 H
KWL
270 H
KWL
320 H
KWL
370 H
Operating mode
Air-cooled compact chiller with heat pump function
and with the adaptive function for cooling and heating
Nominal cooling capacity
1)
kW
12,9
15,9
18,1
21,8
27,1
31,5
37,2
Nominal heating capacity
2)
kW
14,9
17,5
19,8
24,2
29,9
35,1
39,7
Energy efficiency ratio cooling EER
1)
2,42
2,59
2,57
2,56
2,67
2,67
2,65
Energy efficiency ratio heating COP
2)
2,53
2,60
2,58
2,70
2,80
2,78
2,71
Setting range return temp. Cooling
°C
+10 to +18
Setting range return temp. Heating
°C
+20 to +45
Operating range - cooling
°C
+5 to +45
5)
Operating range - heating
°C
-10 to +20
Operating range cooling (extension)
°C
-15 to +45
6)
Cooling circuits, number
1
Capacity scaling
%
0 / 100
Refrigerant
R 407C
7)
Max. operating pressure, refrigerant
kPa
1900 / 2800
Compressor, number / type
1 / Scroll
Air flow rate, max.
m³/h
9570
9740
10240
10240
11940
11720
16300
Sound pressure level
3)
dB(A)
48,2
48,2
48,7
48,4
48,5
48,6
51,3
Sound power level
dB(A)
79,2
79,2
79,7
79,4
79,5
79,6
82,3
Power supply
V / Hz
400/3~/50
Protection class
IP
24
Elec. power consumption, max.
4)
kW
11,56
12,90
15,03
17,08
18,59
21,94
31,08
Elec. current consumption, max.
4)
A
16,69
18,62
21,70
24,66
26,83
31,67
44,86
Nom. electrical power consumption, cooling
1)
kW
5,33
6,13
7,04
8,51
10,16
11,81
14,02
Elec. nominal current consumption cooling
1)
A
11,45
12,77
16,04
16,96
19,54
22,35
30,06
Nom. electrical power consumption, heating
2)
kW
5,90
6,72
7,68
8,97
10,66
12,64
14,63
Elec. nominal current consumption heating
2)
A
12,15
13,07
16,54
16,98
20,03
23,42
30,70
Elec. starting current, max.
A
72
80
101
126
130
170
183
Operating medium
max. 35% ethylene glycol; max. 35% propylene glycol
Operating limits, medium
°C
+4 to +50
Max. operating pressure, medium
kPa
300
Nominal flow volume, medium C/H
m³/h
2,23
2,74
3,10
3,74
4,64
5,44
6,41
Minimum flow volume, medium
m³/h
1,40
1,80
2,00
2,40
3,00
3,50
4,10
Maximum flow volume, medium
m³/h
3,40
4,50
5,20
6,20
7,80
9,00
10,70
Nominal pump pressure, max.
kPa
207,0
195,0
188,0
177,0
162,0
145,0
175,0
Nominal pressure loss, internal cooling
kPa
38,0
30,1
23,2
31,4
45,0
47,2
58,1
System pressure, available cooling
kPa
169,0
164,9
164,8
145,6
117,0
97,8
116,9
Diaphragm expansion vessel, volume
l
6,0
Diaphragm expansion vessel MAG, preliminary pressure
kPa
150
Medium connection, intake
Inches
1 /1/4 indoors
Medium connection, outlet
Inches
1 /1/4 indoors
Medium content, pipe lines
l
2,1
2,5
3,1
3,7
4,2
4,8
6,4
Minimum medium volume, per unit
l
40,0
47,0
51,0
62,0
80,0
91,0
104,0
Dimensions - height
mm
1115
1215
1300
1300
width
mm
430
520
620
1160
depth
mm
1220
1420
1670
1535
Weight
kg
170,0
176,0
268,0
285,0
325,0
332,0
398,0
Operating weight, approx.
kg
172,1
178,5
271,1
288,7
329,2
336,8
404,4
Standard colour
similar to RAL 9018 / INOX
Serial number INOX
1025...
1026...
1027...
1028...
1029...
1030...
1031...
EDP no. INOX
1650133 1650163 1650183 1650223 1650273 1650323 1650373
Serial number RAL 9018
911...
912...
913...
914...
915...
916...
917...
EDP no. RAL 9018
1650131 1650161 1650181 1650221 1650271 1650321 1650371
1) Air intake temperature TK 35°C, medium intake 12 °C, medium outlet 7 °C, 0% glycol concentration
2) Air intake temperature TK 7°C, medium intake 40 °C, medium outlet 45 °C, 0% glycol concentration
3) Distance 10 m free field
4) Air intake temperature TK 45°C, medium intake 18 °C, medium outlet 15 °C, 0% glycol concentration
5) Crank case heating compressor (standard equipment)
6) Only with winter pressure regulation accessory, set
7) Contains greenhouse gas according to Kyoto protocol
Содержание KWL 130