KWK 100
660
415
88
158
70
205
70
KWK 150
810
565
88
158
70
205
70
KWK 250
960
715
88
158
70
205
70
KWK 400
1110
865
88
158
70
205
70
Unit suspension
B
C
D
E
F
G
A
All information in mm.
View from the front
Unit installation
Wall installation
The unit is attached by means of
mounting holes in the case while
also taking account of the air outlet
side located in the upper part of
the unit.
■
Mark the mounting points
according to the bracket's
dimensions on structurally
acceptable building
components and secure the
unit.
■
Check again that the unit is
level.
■
Connect the medium pipes,
electrical cables and condensate
drainage line to the unit as
described below.
Ceiling installation
The unit is attached by means of
mounting holes in the case while
also taking account of the air outlet
side directed towards the centre of
the room.
■
Mark the mounting points
according to the bracket's
dimensions on structurally
acceptable building
components and secure the
unit.
■
Check again that the unit is
level.
■
Connect the medium pipes,
electrical cables and condensate
drainage line to the unit as
described below.
Installation
NOTE
Installation should only be
performed by authorised
specialists.
Selecting the hydraulic
connection
2-conductor cooling system
■
Wall installation without valve
assembly:
When the fan is switched off
the flow of air from the air
inlet can be ignored without
sacrificing comfort. In this
application case, use of a valve
assembly is not absolutely
essential.
■
Ceiling installation without
valve assembly:
A valve assembly must be
used in this application case
to prevent the flow of cold air
from the air outlet when the
fan is switched off.
■
Wall installation with valve
assembly:
In order to prevent any flow of
cold air and severe condensate
formation, for
reasons of
comfort
a valve assembly can
be used in this application case.
■
Ceiling installation with valve
assembly:
In order to prevent any flow
of cold air and permanent
flow-generated noise, for
reasons of comfort a valve
assembly is recommended in
this application case.
2-conductor system for
cooling and heating
■
As the 2-conductor system
must cool and heat equally,
for reasons of convection
during winter operation a
valve assembly is specified for
all installation methods for
this system operation to avoid
undesirable heat emission.
REMKO KWK -4R
12