Make the connection as follows:
1. Open the unit's cover.
2. Insert the cables into the unit.
3. Connect the unit with
a controller and the power
supply.
See electrical drawings.
4. Install all removed parts.
Check all plug and terminal
connections to verify that
they are tight and make a
permanent contact. Tighten as
required.
CAUTION
Connection terminals
Electrical wiring
Leak testing
The leak test is carried out after
the connection has been made.
1. Flush the system twice with tap
water.
2. Clean the sieve insert on the
dirt trap.
3. Fill the system with water again
and vent the unit at the manual
bleed valves.
4. Adjust the test pressure to at
least 200 kPa (2.0 bar).
5. Check the connections for
leaking water after a period of
at least 24 hours . If leaks are
visible, the connection has not
been properly made. Tighten
the threaded connection or
make a new connection.
6. After a successful leak test,
remove the excess pressure
from the medium piping if a
water-glycol mixture is used
or adjust the non-circulating
pressure to the required system
pressure.
Electrical drawings
Legend
Wt
= white
Gn
= green
Ye
= yellow
Pk
= pink
Gn/Ye = green/yellow
Bl
= blue
Bn
= brown
Bk
= black
Gr
= grey
Vi
= violet
Or
= orange
Rd
= red
KWK 100-4R to 400-4R
Neutral conductor
Phase conductor
Earth conductor
Power supply
230V, 1~, 50Hz
Level 2
Level 1
Level 3
Condensate pump
■
If the condensate which forms is
to be removed by a condensate
pump, this can be placed in the
unit.
Follow the separate Installation
Instructions.
KWK 100-4R
KWK 150-4R
KWK 250-4R
KWK 400-4R
Conden-
1.0 µF
2.0 µF
1.5 µF
2.5 µF
sor
Air flow
Sound pr
essur
e
Sound power
level
Power
consumption
Transformer
terminal
Conductor
colour
Connection
Air flow
Sound pr
essur
e
Sound power
level
Power
consumption
Transformer
terminal
Conductor
colour
Connection
Air flow
Sound pr
essur
e
Sound power
level
Power
consumption
Transformer
terminal
Conductor
colour
Connection
Air flow
Sound pr
essur
e
Sound power
level
Power
consumption
Transformer
terminal
Conductor
colour
Connection
m³/h dB(A) dB(A)
W
m³/h dB(A) dB(A)
W
m³/h dB(A) dB(A)
W
m³/h dB(A) dB(A)
W
min max
Item 1 333 40.5 49
63
1
338 43.5 52
44
1
584 47.5 56
85
1
716 47.5 56
90
1
Item 2 296 39.5 48
56
2
348 41.5 50
38
2
505 44.5 53
75
2
570 42.5 51
69
2
Item 3 252 38.5 47
49
3
304 38.5 47
32
3
430 41.5 50
65
3
490 37.5 46
58
3
Item 4 200 34.5 43
40
4
bk
1
254 36.5 45
29
4
bk
1
353 36.5 45
54
4
bk
1
432 34.5 43
47
4
bk
1
Item 5 147 28.5 37
29
5
bl
2
194 32.5 41
21
5
bl
2
254 27.5 36
40
5
bl
2
300 26.5 35
35
5
bl
2
Item 6 128 25.5 34
27
6
rd
3
184 25.5 34
17
6
rd
3
232 26.5 35
36
6
rd
3
283 25.5 34
30
6
rd
3
15
Содержание KWK 100-4R
Страница 2: ......