Outdoor unit error display (control board
flashing code of the outdoor module)
In the event that the red control lamp lights up on
the indoor module, then the fault is on the outdoor
module. Two LEDs are visible after removing the
enclosure panel which light up in green and red
during normal operation (see adjacent figure). If
the LEDs flash, then there is a fault. Causes and
measures for their remedy can be taken from the
following table. (
Z
= flashing)
1
Fig. 64: 1: Green and red LEDs
Green
LED
Red LED
Meaning
Remedial measures
Z
Z
Phase error: The supply cable to the
outdoor module or the connection
between the indoor and outdoor mod-
ules is not correct.
Check the electrical connection
(swapped phases), check connection
cable
ZZ
One of the connectors has been
removed from the PCB or has intermit-
tent contact
Check all connectors on the PCB,
check high and low pressure sensors
ZZZ
Fault on PCB
Exchange PCB
ZZ
Z
Wiring error between indoor and out-
door modules
Check connection cable for correct
polarity and proper contact
ZZ
Data transfer error between indoor and
outdoor modules
Check if the connection cable has
been improperly extended or incor-
rectly connected
ZZZ
Z
Hot gas temperature in refrigerant cir-
cuit too high or hot gas heating too low
Check refrigerant; check hot gas tem-
perature sensor; check expansion
valve
ZZ
High pressure valve has tripped
Open any closed ball valves, check for
excess refrigerant
Low pressure cut-off switch has tripped Open any closed ball valves, check for
excess refrigerant
No voltage on condenser
Check power supply to the condenser
ZZZ
Overheating protection tripped, exces-
sive liquid temperature in refrigerant cir-
cuit
Clean dirty heat exchanger on outdoor
module, rectify possible pneumatic
short circuit on the outdoor device
ZZZZ
Circuit breaker on condenser (overload)
has tripped, or no operating voltage at
the condenser
Open any closed spherical valves,
check supply voltage, exchange faulty
control panel
ZZZZZ
Fault in hot gas temperature sensor or
fin temperature sensor (cable breakage
or short circuit)
Check PCB connector for firm connec-
tion, check functionality of the sensor
ZZZZZZ
Temperature fault on inverter cooling
block
Rectify obstruction to flow in outdoor
module
ZZZZZZZ
Fault in power supply
Check and repair power supply
ZZZZ
Z
Fault on liquid line sensor (cable
breakage or short circuit)
Check PCB connector for firm connec-
tion, check functionality of the sensor
ZZZZ
Temperature of liquid line too high / too
low
Check refrigerant line. Lack of refrig-
erant
REMKO CMF/CMT
72