Installer level - #SECONDARY INSTAL.P menu
Parameter
Adjustment range
Description
Factory
setting
Customer
setting
NIGHT
(1)
DEC.
The lower temperature is maintained
(Night mode)
¼
DEC.
STOP
The boiler is stopped (Night mode)
¼
IN 0-10V
OFF
/
TEMPERATURE
/
POWER %
Activating the control at 0-10 V
¼
OFF
VMIN/OFF 0-10V
(1)(4)
0 to 10 V
Voltage corresponding to the instruction
set minimum
0.5 V
VMAX 0-10V
(1)(4)
0 to 10 V
Voltage corresponding to the instruction
set maximum
9.5 V
CONS.MIN 0-10V
(1)
(4)
10 to 70 °C
Instruction minimum set temperature
20 °C
CONS.MAX 0-10V
(1)
(4)
10 to 100 °C
Maximum set temperature
80 °C
BAND WIDTH
(1)
4 to 16 K
Control unit bandwidth for the 3-way
valves.
Option of increasing the bandwidth if the
valves are rapid or of reducing it if they are
slow.
12 K
BOIL/3WV SHIFT
(1)
0 to 16 K
Minimum temperature difference between
the boiler and the valves
4 K
H. PUMP DELAY
(1)
0 to 15 minutes
Timing of the shutdown of the heating
pumps.
The timing of heating pump shutdown
prevents the boiler overheating.
4 minutes
HW. PUMP DELAY
(1)
2 to 15 minutes
Timing of the shutdown of the domestic
hot water pump.
The timing of the domestic hot water load
pump shutdown prevents the boiler and
the heating circuits overheating (Only if a
load pump is used).
2 minutes
ADAPT
ON
Automatic adaptation of the heating
curves for each circuit with a room sensor
with an influence of >0.
ON
OFF
The heating curves can only be modified
manually.
PRIORITY DHW
(5)
TOTAL
Interruption of pool heating and reheating
during domestic hot water production.
TOTAL
SLIDING
Domestic hot water production and
heating on the valve circuits if the available
output is sufficient and the hydraulic
connection allows.
NO
Heating and domestic hot water
production in parallel if the hydraulic
connection allows.
a
Risk of overheating in the direct circuit.
(1) The parameter is only displayed if
INSTALLATION
parameter is set to
EXTENDED
(2) The parameter can be set to the heating curve by pressing key
f
(3) The parameter is only displayed if
SCREED DRYING
is other than
OFF
(4) The parameter is only displayed if
IN 0-10V
is set to
ON
.
(5) If a reversal valve is connected, DHW priority will always be total regardless of the setting.
iSense Pro DIN - AD280
5. Operating the appliance
12/04/2011 - 300025649-001-B
42