When floor drying is active on a circuit, all other circuits (e.g. DHW)
are shut down. The use of this function is only possible on circuits B
and C.
A
STOP DRYING TEMP
Z
START DRYING TEMP
E
Today
R
NB DAYS DRYING
T
Normal regulation (End of drying)
Y
Heating temperature setting (°C)
For example
A
STOP DRYING TEMP
:
47 °C
Z
START DRYING TEMP
:
20 °C
R
NB DAYS DRYING
T
Normal regulation (End of drying)
Y
Heating temperature setting (°C)
Every day at midnight (00:00): the set point (
START
DRYING TEMP
) is recalculated and the remaining number
of days (
NB DAYS DRYING
) is decremented.
n
ROOM S.INFL
Used to adjust the influence of the room sensor on the water
temperature for the circuit concerned.
0
No influence (remote control fitted in a location with no influence)
1
Slight influence
3
Average influence (recommended)
10
Room thermostat type operation
n
NIGHT
This parameter is displayed if at least one circuit does not
include a room sensor.
For circuits without a room sensor:
4
NIGHT :DEC.
(Reduced): The reduced temperature is maintained
during reduced periods. The circuit pump operates constantly.
4
NIGHT :STOP
(Stop): Heating is shut down during reduced
periods. When installation antifreeze is active, the reduced
temperature is maintained during reduced periods.
2
3
4
1
6
5
C002768-A
00:00
00:00
00:00
2
10
9
8
7
6
5
4
3
2
1
23
20
26
29
32
35
38
41
44
47
4
4
5
1
6
C002769-A
00:00
00:00
00:00
iSense Pro DIN - AD280
5. Operating the appliance
12/04/2011 - 300025649-001-B
44