Installer level - Menu #NETWORK
(1)
Parameter
Adjustment range Description
Factory setting Customer setting
CASCADE:
ON
/
NO
ON
: System in cascade
NO
MASTER CONTROLLER
(2)
ON
/
NO
Configure this control system as
master on the bus
ON
SYSTEM NETWORK
(3)
Specific menu: Enlist generators or
VMs in cascade mode (See following
chapter: "Connecting appliances in
cascade")
FUNCT
(3)
CLASSIC
Operation in cascade: Successive
triggering of the various boilers in the
cascade according to requirements
CLASSIC
PARALLEL
Functioning in parallel cascade: If the
outside temperature is lower than the
value
PARALLEL CASC.
, all of the
boilers are started up at the same time
PARALLEL CASC.
(4)
-10 to 20 °C
Outside temperature triggering all
stages in parallel mode
10 °C
TIMER GENE P. CASC
(2)
0 to 30 min
Minimum duration of post-operation of
the generator pump
0 mn
INTER STAGE TIMER
(2)
1 to 30 min
Time delay for starting up or shutting
down generators.
4 mn
SLAVE NUMBER
(5)
2 to 10
Set the network address of the
secondary generator
2
3WW PLC
Specific menu (Not used)
InOne SCENARIO
Specific menu: Configure the InOne
scenarios to be managed by the SCU
PCB (See following chapter:
"Configuring the scenarios")
REMOVE DEVICE
Specific menu: see below
(1) The menu is displayed only if the
INSTALLATION
parameter is set to
EXTENDED
(2) The parameter is only displayed if
CASCADE:
is set to
ON
(3) The parameter is only displayed if
MASTER CONTROLLER
is set to
ON
(4) The parameter is only displayed if
FUNCT
is set to
PARALLEL
(5) The parameter is only displayed if
MASTER CONTROLLER
is set to
OFF
n
Connecting appliances in cascade
It is possible, in a cascade configuration, to enlist generators and/or
VMs as slaves. Proceed as follows:
1. Set
CASCADE:
to
ON
by pressing the rotary button and then
turning and pressing it again to confirm.
2. Select
SYSTEM NETWORK
and press the rotary button to go to
the specific menu.
1
1
2
2
r
c
STD
(
'
t
v
0
2
4
6
8
10
12
14
16
18
22
24
20
p
b
AUTO
x c
r
j
L
g
m
CASCADE
MASTER CONTROLER
SYSTEM NETWORK
FUNCT
INTER STAGE TIMER
ON
ON
TRADITIONAL
4'
a
C002409-C-04
iSense Pro DIN - AD280
5. Operating the appliance
12/04/2011 - 300025649-001-B
46