u
Outside sensor
Settings to be made for this type of installation: Master boiler
Parameters
Access
Settings to be made See chapter
INSTALLATION
Installer level
#SYSTEM
menu
EXTENDED
¼
"Displaying the parameters in extended
CASCADE:
(1)
Installer level
#NETWORK
menu
ON
¼
"Configuring the network", page 45
MASTER CONTROLLER
(1)
Installer level
#SYSTEM
menu
ON
SYSTEM NETWORK
(1)
Installer level
#SYSTEM
menu
ADD GENE MANU
(1) The parameter is only displayed if
INSTALLATION
parameter is set to
EXTENDED
Settings to be made for this type of installation: Follower boilers
Parameters
Access
Settings to be made See chapter
INSTALLATION
Installer level
#SYSTEM
menu
EXTENDED
¼
"Displaying the parameters in extended
CASCADE:
(1)
Installer level
#NETWORK
menu
ON
¼
"Configuring the network", page 45
MASTER CONTROLLER
(1)
Installer level
#SYSTEM
menu
OFF
SLAVE NUMBER
(1)
Installer level
#SYSTEM
menu
2, 3, ...
(1) The parameter is only displayed if
INSTALLATION
parameter is set to
EXTENDED
4. Installation
iSense Pro DIN - AD280
29
12/04/2011 - 300025649-001-B