Blocking code
Description
Flow temperature sensor above normal range (high-limit thermostat):
Bad connection: check the wiring and connectors.
Incorrectly fitted sensor: check that the sensor has been correctly fitted
Faulty sensor: replace the sensor
No flow or insufficient flow:
Check the circulation (direction, pump, valves)
Check the water pressure
Check the cleanliness of the heat exchanger
Maximum flue gas temperature exceeded:
Wait until the flue gas temperature has decreased
Configuration procedure active:
No action
Configuration error or unknown configuration number:
Reset
and
Configuration error:
Reset
and
Water pressure too low:
Not enough water in the system: check the water pressure
Wiring fault: check the wiring
Blocking input active or frost protection active:
External cause: remove external cause
Wrong parameter set: check the parameters
Bad connection: check the connection
Blocking input is active:
External cause: remove external cause
Wrong parameter set: check the parameters
Bad connection: check the connection
Waiting time release signal has elapsed:
External cause: remove external cause
Wrong parameter set: check the parameters
Bad connection: check the connection
Communication error with the SCB PCB:
Bad connection with BUS: check the wiring
No PCB in boiler: reconnect PCB or retrieve from memory with Auto-detect.
No flame during operation:
No ionisation current:
Vent the gas supply to remove air
Check that the gas valve is fully opened
Check the gas supply pressure
Check the operation and setting of the gas valve unit
Check that the air supply inlet and flue gas outlet are not blocked
Check that there is no recirculation of flue gases
(1) These blockings are not stored in the error memory.
8.2 Lock out
If the blocking conditions still exist after various start attempts, the boiler
goes into lockout (also called error). The boiler will also lock out if an error
is signalled anywhere in the boiler. An error code will appear on the dis
play. The error code is displayed as follows:
In a red flashing display:
the symbol
the symbol
the error code, for example,
The meaning of the error codes can be found in the error table. Note the
error code.
8 Troubleshooting
7616014 - v.03 - 15022016
27