7 Settings
7.1 Parameter descriptions
Tab.3
Factory settings for user level parameters
Parameter
Description
Adjustment range
Quinta Ace160
Activate manual mode
0 = Off
1 = On (with flow temperature set point in manual
mode)
2 = Weather-compensated (flow temperature in ac
cordance with heating curve)
0
Activate CH
0 = Off
1 = On
1
Activate DHW
0 = Off
1 = On
1
Flow temperature in manual mode
7 to 90ºC
40
Reserve parameter
This parameter is part of the timer program; change
only if necessary
16
Reserve parameter
This parameter is part of the timer program; change
only if necessary
20
Reserve parameter
This parameter is part of the timer program; change
only if necessary
6
Reserve parameter
This parameter is part of the timer program; change
only if necessary
21
Reserve parameter
This parameter is part of the timer program; change
only if necessary
22
Reserve parameter
This parameter is part of the timer program; change
only if necessary
20
Room set point
5 to 30ºC
20
CH group control
0 = internal timer program
1 = manual control
2 = according to frost protection
3 = temporary
1
Selected time program for CH opera
tion
Do not change
0
Setting LANGUAGE
EN, FR, DE, NL, IT, ES, PL, PT
0
Setting CONTRAST
0 to 3
3
Setting UNIT
0 = bar/ºC
1 = psi/ºF
0
Setting SUM/WIN
0 = manual switching summer/winter time
1 = automatic switching summer/winter time
1
Setting LIGHTING
0 = the background illumination for the display
switches off after three minutes of inactivity
1 = the background illumination for the display re
mains on
0
(1) If parameter AP103 is set to a language, the display shows written text. If parameter AP103 is set to 0, the display shows the parameter
code
Tab.4
Factory settings for installer level parameters
Parameter
Description
Adjustment range
Quinta Ace160
Blocking input function
0 = Not in use
1 = Shutdown without frost protection
2 = Shutdown with frost protection
3 = Lockout with frost protection (pump only)
1
7 Settings
12
7616014 - v.03 - 15022016