Relcross 9130 Скачать руководство пользователя страница 12

 

 
Page 12 of 24  

February 2006 

 

 

 

Ver 0    

8 OPERATOR 

ADJUSTMENT 

See table below and diagrams on page 16 for operator feature adjustment. After 
adjustment, cycle the door several times and check for proper operation, then continue 
with step 6.11 on page 10. 

NOTE 

Adjust operator for the slowest operation practical in accordance with the latest BS 7036 
standards for power assisted low energy power operated doors. 

Opening speed 5 sec’s or more                                              Closing speed 3 sec’s or more 

OTE 

Features Control 

Description 

Anti-
Clockwise 

Clockwise 

Opening 
Speed 

P1 

Controls opening speed of door 

Slower 

Faster 
 

Back Check 
Speed 

P2 

Controls speed of door near full 
open position prevent door 
slamming 

Slower Faster 

Hold Open 
Time Delay 

P3 

Controls length of time door 
remains in the full open 
position 1 to 30Sec 

Less time 
1 Sec 
 

`More Time 
30 Sec’s 
 

Auto 
Reverse 
setting 

P4 

Sets pressure required on door 
opening before door stops 

Less Pressure 
required 

More 
Pressure 
Required 

Latch 
Position 
 

P5 

Determines distance at which 
the door begins to decelerate to 
full closed position to prevent 
door slamming 

Less Latch 

More Latch 
 

Closing 
Speed 

P6 

Controls closing speed of door 

Slower 

Faster 
 

Safety 
Opening 
Angle 

P7 

Controls the angle during the 
open cycle that safety operates  

Closer to 
closed 
position 

Further from 
closed 
position 

Safety 
Closing 
Angle 

P8 

Controls the angle during the 
close cycle that safety operates 

Closer to open 
position 

Further from 
open 
position 

Delayed 
Activation 

SW1 
 

 

 

 

Push And 
Go 
 

SW2 

When switched on pushing the 
door open by 5 degrees causes 
the operator to open for the 
remainder of the open cycle 

 

 

Power 
boost On or 
OFF 
 
 

SW3 

Enables or disables Power Boost 
which gives a force in the closed 
direction when the door is 
closed. Used for high wind 
situations 

 

 

Power 
boost 
continuous 
or 5 Sec’s 

SW4 

Enables power boost to operate 
continuously or for 5 Sec’s only 
after door closes. 
 

 

 

 
 
 

Содержание 9130

Страница 1: ...Page 1 of 24 February 2006 Ver 0 9100 Series Relcross 9100 Series Installation Instructions www relcross co uk ...

Страница 2: ...to the full open position creating the potential energy in the spring When closing the electrical power is reduced and the door closes by controlling the potential energy release in the spring force The activating circuit opens the door from any position on the closing swing During power failure the 9100 acts as a manual door closer size 3 Door opening and closing cycles including opening speed ba...

Страница 3: ...Page 3 of 24 February 2006 Ver 0 REPLACEMENT PARTS AND SYSTEM COMPONENTS Cont Swing Door Operator Swing door operator Pull arm and track assembly Push arm assembly 9130 9140 ...

Страница 4: ...nd frame dimensions and required clearances Clearances for pull system Clearances for push system 3 5 Ensure door weights is less than 90Kgs for heavier doors consult supplier 3 6 Check that a 240 Volt single phase 60 Hz fused supply 5 amp fuse maximum is available at the side of the jamb within approximately 1 Meter of the header Approved type conduit is recommended for 240V systems 3 7 The suppl...

Страница 5: ...m See Page 5 Push system See Page 6 NOTE NOTE For push units with a reveal greater than 150 mm refer to installation sheet included in the extended arm Packaging 4 3 Install operator mounting bracket on the header frame 4 4 Install motor gearbox on operator mounting bracket then install control box on bracket Go to wiring page 7 Pull System Framed Header and Door Preparation ...

Страница 6: ...ebruary 2006 Ver 0 OPERATOR INSTALLATION Cont Push System Framed Header and Door Preparation REVEAL Butt Hung Offset Pivot DIM A Centre Pivot DIM A 25 559 686 51 533 660 76 508 635 102 483 610 127 457 584 152 457 584 ...

Страница 7: ...lied for custom applications And connect the following cables Ground cable Ground the operator properly with the earth from main supply Hall effect Cable do not wrap the hall effect cable around the motor cable Motor power cable do not wrap the motor cable around the hall effect cable Control box power cable 5 2 Connect Activate Safety Key switch and lock accessories as needed Refer to the accesso...

Страница 8: ...rned OFF 6 2 Install a jumper across the control box MAIN ACT T28 and COMMON T27 6 3 Turn the operator power switch on The operator motor will activate and drive to the full open position 6 4 Attach the arm to the operator spindle loosely with the 8 mm socket head screw for push systems ensure adjusting boss is inserted correctly 6 5 Attach the arm to the door 6 5 1 For push systems attach the pus...

Страница 9: ... door in the full open position and adjust the arm length as necessary to align the door at 90 degrees from closed When the arm is adjusted to the correct length tighten up the8 mm socket head screw that secures the arm to the operator spindle and ensure this is secure then tighten the arm locking screw 6 7 Turn off the power operator switch The door closes 6 8 Remove the jumper from the control b...

Страница 10: ...ND COVER INSTALLATION Cont 6 11 Snap optional end cap insert from screw bag into the end cap opposite the on off switch 6 12 Install the cover assembly on the operator 6 13 Release the operator for service see Release for Service on page 14 ...

Страница 11: ...inds Increase the back check speed slightly and check door operation continue increasing back check speed until door opens fully 7 5 If the door slams open decrease the back check speed slightly and check door operation Continue decreasing back check speed until the door opens without slamming 7 6 After the sizing cycle is complete and the doors are closed apply a maintained activation signal and ...

Страница 12: ...setting P4 Sets pressure required on door opening before door stops Less Pressure required More Pressure Required Latch Position P5 Determines distance at which the door begins to decelerate to full closed position to prevent door slamming Less Latch More Latch Closing Speed P6 Controls closing speed of door Slower Faster Safety Opening Angle P7 Controls the angle during the open cycle that safety...

Страница 13: ...Page 13 of 24 February 2006 Ver 0 OPERATOR ADJUSTMENT Cont ...

Страница 14: ...Y ON OFF F 0 ON OFF SPEED Less BACKCHECK ANGLE SAFETY SAF LATCH POSITION Slow More AUTO Short C B D FUNCTION SELECTOR Close Only Thru Arc OPEN Thru Arc Slow Open Only Fast SPEED SAFETY ACT ANGLE CLOSE SPEED 9 8 7 A E F 1 0 6 4 5 2 3 P B PNG ON OFF CONT P B 5 SECS N A Long Less Fast More ...

Страница 15: ...dent that might occur This must be done 9 3 Verbally instruct the owner or person in charge of the proper operation of the door 9 4 Instruct the owner or person in charge to routinely inspect the door for the following Occasional damage Developing problems Minor preventative maintenance 9 5 Instruct the owner or people in charge who and where to call for service and maintenance when required IMPOR...

Страница 16: ...Auto Reverse on open 17 10 1 3 Standard operation 18 10 2 FUNCTION SELECTION 18 10 2 1 Standard 0 18 10 2 2 Lock in OFF Only 1 18 10 2 3 Lock in 1 Way Only 2 18 10 2 4 PNG in OFF 3 18 10 2 5 Door closes and Unlocks in Fire Alarm 4 18 10 3 FUNCTION CHART 18 10 4 CONTROL BOX SETUP 18 10 5 9100 Series WIRING 18 ...

Страница 17: ...r to full open The door closes at close speed then latch up to closed position where the system sets the counter for closed position From these two parameters opened and closed position the system calculates all the other parameters it requires for normal operation i e latch position back check position etc Notes If the encoder is connected for opposite direction or faulty or disconnected the door...

Страница 18: ... hold open speed and holds the door open until activation and or timer is cleared The door will then close at close speed Potentiometer setting up to latch position Potentiometer setting Where the speed is decreased by driving the motor in the open direction fixed setting the power is set such that the spring will overcome this power and continue to allow the door to close up to the closed positio...

Страница 19: ...lock operation is set from the function selector the time delay is fixed Key switch Position 1 Way the activation from internal Activate T27 T28 safety operates Electric lock operates when door closed dependant upon function selection Key switch Position 2 way the activation from internal Activate T27 T28 and external Activation T22 T23 safety operates Electric lock does not operate when door clos...

Страница 20: ... as a standard door with electric lock operating in OFF only This selection will give a fast activation in Auto or 1 Way from closed as there is no delay for lock operation 10 2 3 Lock in 1 Way Only 2 Operates as a standard door with electric lock operating in 1 Way only 10 2 4 PNG in OFF 3 Operates as a standard with Push Go operating in key switch OFF 10 2 5 Door closes and Unlocks in Fire Alarm...

Страница 21: ...pen T14 Key switch off T12 2 Way T22 T23 T8 Not Used Locking in OFF only 1 As Std Door locks in OFF Only Locking Auto only 2 As Std Door Locks in AUTO Only Standard PNG in OFF 3 As Std PNG operates in key switch OFF Fire Alarm to close door Normally closed Breakout 4 As Std F A T9 T10 Normally closed Door closes and remains unlocked 5 6 7 8 9 A B C D E F ...

Страница 22: ...E TIME DELAY ON OFF F 0 ON OFF SPEED Less BACKCHECK ANGLE SAFETY SAF LATCH POSITION Slow More AUTO Short C B D FUNCTION SELECTOR Close Only Thru Arc OPEN Thru Arc Slow Open Only Fast SPEED SAFETY ACT ANGLE CLOSE SPEED 9 8 7 A E F 1 0 6 4 5 2 3 P B PNG ON OFF CONT P B 5 SECS N A Long Less Fast More ...

Страница 23: ...Page 23 of 24 February 2006 Ver 0 10 5 9100 Series WIRING ...

Страница 24: ...Page 24 of 24 February 2006 Ver 0 10 6 9100 Series Terminal Block ...

Отзывы: