background image

            

 

 

 

Rev. 3F Aug 2020 

 

 

 

P/N 77740213 

Page  

6

 

 

Supply And Return Tubing Installation 

The installed 1/4” supply tubing and 3/8” vent and drain tubing should be sufficiently long so that there are no kinks or twists.  
These obstructions can restrict flow to the bearing or hamper drainage from the bearing housing.  Additionally sags and traps are 
to be avoided by making the lengths too long.  Sags or traps will collect oil and affect the flow of oil mist to the bearing or the mist 
return to the LubriMate

®

.  Tubing should bend smoothly as changes in direction are made.  The maximum length of supply tubing 

to an application point should be less than three (3) meters.  A similar length restriction applies to drain tubing. 

 
 

Ambient Operating Temperature 

The LubriMate

®

 uses the power of compressed air to generate the oil mist for bearing lubrication. The ability to create the oil mist 

is directly influenced by the viscosity of the lubricant.  As ambient temperatures fall and oil viscosity increases, oil mist generation 
decreases.  Below certain temperatures, the LubriMate

®

 will not produce oil mist. 

 
Where the LubriMate without the optional oil heater it is recommended that the LubriMate

®

  be operated at ambient conditions 

above 50 degrees F. The LubriMate

®

 Lubrication System is shipped with a supply of ISO 68 grade, diester type lubricant. Use the 

following chart as a guide for selection and use of other viscosity grades.  For units equipped with an oil heater, the it is 
recommended that the oil temperature be set at 110 F. This helps to maintain a consistent  

 

Viscosity Grade 

Minimum Operating Temperature 

ISO 32 

32 F  (    0 C) 

ISO 46 

40 F  ( 4.4 C) 

ISO 68 

          50 F  ( 9.9 C) 

ISO 100 

60 F  (15.6 C) 

ISO 150 

70 F  (21.0 C) 

    >ISO 150 

Not Recommended 

 
 
 

Maintaining Minimum Air Flow to the LubriMate

®

 

To insure proper generation of oil mist a minimum airflow must be provided to the internal mist head in the LubriMate

®

.  

If the 

application requires only one lubrication point or a combination of mist reclassifiers that have a combined flow of less 
than 0.40 SCFM, additional airflow is needed for proper operation.

 The LubriMate

®

 is equipped with an internal mist flow 

bypass valve, which can be used to increase or decrease the mist output volume. The mist bypass valve is located on the right 
side of the mist generator head. Opening the mist flow bypass valve directs mist flow directly into the mist recovery system, thus 
increasing output mist flow volume.   

 

 

LubriMate

®

 Lubrication System oil mist generators are shipped with the mist flow bypass valve in the OPEN position. If your total 

mist out put is 

 0.40 SCFM, close the mist flow by pass to the full closed position. The valve is in the full closed position when 

the adjust valve is fully turned in and seated. It is in the full open position when the face of the valve is flush with the edge of the 
mist generator head. See the section of this manual titled 

Selection of Application Fittings (Mist Reclassifiers)

  to determine the 

mist output of your system. 

IMPORTANT 
1.  Do not use oil that 

contains paraffin or 
viscosity modifiers. 

2.  Do not use motor oil in 

the LubriMate

®

.

 

Mist Flow Bypass Valve 
  Adjust CW to the full 
CLOSED position if the total oil 
mist output is 

 0.40 SCFM  

  Adjust CCW to full OPEN 
position if the total oil mist 
output is < 0.40 SCFM (factory 
setting) 

Содержание LUBRIMATE

Страница 1: ...NO SERIAL NO LubriMist MIST PRESSURE SWITCH RATING OIL HEATER VOLTS WATTS P O BOX 19294 HOUSTON TEXAS 77224 9294 713 464 6266 FAX 713 464 9871 1 800 800 LUBE www lsc com THE RIGHT CHOICE Lubrication...

Страница 2: ...gn with coalescing filter eliminates stray mist from venting at the unit thus test stands remain clean and free of oil mist This publication provides instruction and information on the set up and oper...

Страница 3: ...into the bearing housing A drain tube connects the bearing housing drain to any of five return ports located on the LubriMate The air stripper separates the remaining oil from the returned oil mist T...

Страница 4: ...to the inlet air pressure regulator filter 1 8 NPT located at the left side of the unit The inlet air supply should be capable of delivering 4 SCFM at 55 PSIG This is the minimum required air pressure...

Страница 5: ...ation For gear boxes and sleeve bearings with oil level the purge oil mist method is to be used With purge mist the air space above the oil level is filled with oil mist The resulting purge keeps outs...

Страница 6: ...ents is maintained by the splash or recirculation of the oil from the oil reservoir The purge mist itself does not provide the lubrication rather it fills and flows through the volume space above the...

Страница 7: ...istent Viscosity Grade Minimum Operating Temperature ISO 32 32 F 0 C ISO 46 40 F 4 4 C ISO 68 50 F 9 9 C ISO 100 60 F 15 6 C ISO 150 70 F 21 0 C ISO 150 Not Recommended Maintaining Minimum Air Flow to...

Страница 8: ...over time the stripping filter element becomes saturated with oil This is normal and expected However the resulting increased pressure drop across the filter may cause a portion of the returning mist...

Страница 9: ...a leak or loose connection in the supply tubing a missing application fitting or a broken line 5 2 High mist pressure may indicate plugged application fitting or a restricted bearing housing vent or d...

Страница 10: ...CH RATING OIL HEATER VOLTS WATTS P O BOX 19294 HOUSTON TEXAS 77224 9294 713 464 6266 FAX 713 464 9871 1 800 800 LUBE www lsc com THE RIGHT CHOICE Lubrication Systems Company FULL ADD OIL LEVEL 131 2 1...

Страница 11: ...ches of H2O 2 77 700 744 Return Pressure Gauge 3 77 700 743 Air Stripping Coalescing Filter Element 4 77 700 742 Bulls Eye Sight Glass 5 LS 02 05 120 Oil Suction Screen 6 77 600 807 Air Filter Pressur...

Страница 12: ...ESURE SWITCH Oil HEATER 120 VAC 250 Watt ALUMINUM PORT TEFLON COATED POLYIMIDE DIAPHRAGM ADJ RANGE 7 H20 DECR TO 100 H20 INCR SPST CONTACT RATING 11 AMP 1 2 HP AT 125 OR 250 VAC 5 AMP RESISTIVE 3 AMP...

Страница 13: ...Rev 3F Aug 2020 P N 77740213 Page 12 Notes and Records...

Отзывы: