7.14.3 REHAU Pressure Test Procedure

- Use an air test if conditions do not permit a water test (e.g., freezing 

conditions, insuf

fi

cient water supply/pressure).

- Air temperature will affect the gauge pressure. Perform all pressure 

tests at a constant temperature. Verify maximum pressure require-
ments for other systems prior to performing the test. 

- Conduct a visual inspection of the piping system, to ensure all 

connections have been properly made and all piping has been 
properly secured prior to pressurization.

- Perform a preliminary pressure test pressurizing the system to 1.5 

times the maximum operating pressure not to exceed the maximum 
pressures de

fi

ned above for 30 minutes.

- As the piping expands, restore pressure, 

fi

rst at 10 minutes into the 

test and again at 20 minutes.

- At the end of the 30-minute preliminary test, pressure must not fall 

by more than 5 psi from the maximum, and there shall be no 
leakage.

- After performing the preliminary test, perform the main pressure test 

immediately. The main pressure test shall last at least 2 hours. The 
test pressure should be restored and must not fall more than 3 psi 
after 2 hours. No leakage should be detected.

- It is recommended to maintain pressure on the system during further 

construction, where practical, to immediately identify any damage. If 
a water (hydrostatic) test is used, protect the water from freezing or 
drain water from pipes.

- If any repairs or corrections are necessary, depressurize the system 

before proceeding. 

NOTICE

 

-

When other thermoplastic piping materials (e.g., CPVC, PP-R) are 
present in the piping system, these sections of piping must be 
isolated from the REHAU PEXa piping system during the pressure 
test. The installer must consult the other component manufacturer’s 
installation instructions for pressure testing those sections of the 
system.

 

-

Always refer to the local codes for pressure testing requirements and 
use air testing only if approved by the local Authority Having 
Jurisdiction (AHJ).

 

-

REHAU only provides the general guidelines for performing a 
pressure test, which by no means supersede or are intended to 
contradict safety requirements. It is the responsibility of the installing 
contractor to ensure a proper and safe pressure test is performed on 
site.

 

-

All other trades must be noti

fi

ed that the pressure test will be 

conducted on the piping system.

7.15 Testing System Flow

The local Authority Having Jurisdiction (AHJ) may require a 

fl

ow 

veri

fi

cation test of the two most hydraulically remote sprinklers. This 

fl

ow veri

fi

cation test is a valuable procedure to ensure the installed 

fi

re sprinkler system is operating as designed. The local inspector 

must be noti

fi

ed prior to performing the 

fl

ow test to ensure the 

inspector is present during the test.

The 

fl

ow test must be performed after all piping, 

fi

ttings, sprinklers 

and plumbing connections have been completed and successful 
pressure testing of the system has been done. The 

fl

ow test must 

occur prior to closing in the system.

The 

fl

ow veri

fi

cation test consists of the following steps:

1.  Remove the sprinklers. 

Make sure the piping system is not under pressure and water 
has been drained from the portion of piping serving the 
sprinklers. Using the manufacturers' sprinkler wrench, carefully 
remove the sprinklers intended for testing and secure in a safe 
place in order to avoid any damage.

2.   Install the appropriate test 

fi

ttings.

Obtain proper test 

fi

ttings that consist of a 1/2 in. MPT adapter 

that will connect to the FIREPEX sprinkler 

fi

tting, a 

fl

ow control 

valve, a pressure gauge, a sprinkler test ori

fi

ce and a 30-gallon 

bucket. Thread male adapter into the sprinkler 

fi

ttings. Use pipe 

thread seal tape to make the threaded connections watertight.

3.   Open the main shut-off valve.

Ensure all connections are made and all plumbing connections 
are sealed. Open main shut-off valve to supply water to the 
system.

4.   Open the ball valve on the test 

fi

ttings.

Open the valves and bleed all air from the system using the 
containment buckets. Once all air is purged from the system, 
close the valves. The system should be pressurized to its working 
pressure.

5.   Record the static pressure readings.

Note the static pressure at the manifold pressure gauge and at 
the pressure gauge on the test apparatus.

6.   Perform the 

fl

ow veri

fi

cation test.

Simultaneously open the ball valves on the test apparatuses. 
Ensure the buckets are properly placed under the apparatuses to 
capture all water. The ball valves are to be open for exactly 60 
seconds. During this time, record the residual pressure readings. 
After 60 seconds, shut the ball valves immediately.

32

Содержание Firepex

Страница 1: ...FIREPEX RESIDENTIAL FIRE SPRINKLER SYSTEM Design and Installation Guide...

Страница 2: ...eeve Fittings 11 5 1 Fitting Scope 11 5 2 Fitting Assembly 14 5 3 Installation Considerations 14 5 4 EVERLOC Compression sleeve Tools 17 5 3 Fire Sprinklers 19 6 System Planning 21 6 1 Determine Local...

Страница 3: ...delines are defined in the REHAU PEXa Limited Warranty as The most current and applicable versions of all the technical literature available on the REHAU North America website at www na rehau com reso...

Страница 4: ...nkler Systems The NFPA 13D standard categorizes all fire sprinkler systems within two general types wet pipe systems and dry pipe systems Wet pipe systems are filled with water and installed in areas...

Страница 5: ...l information is not intended to be used as final drawings or specifications and is provided only as an aid in designers develop ment of the final specification and is not intended as a substitute for...

Страница 6: ...n connections and routing of the service line into the residence Determine the specifications for the sprinklers including water flow and operating pressure requirements and coverage area specificatio...

Страница 7: ...are not certified for fire sprinkler systems The FIREPEX system is third party certified by NSF International www nsf org to the following standards UL 1821 Standard for Thermoplastic Sprinkler Pipe a...

Страница 8: ...70 C per DIN 16892 Modulus of Elasticity 87 000 130 500 psi 68 F 43 500 58 000 psi 176 F 600 900 N mm2 20 C 300 400 N mm2 80 C Minimum 20 C per DIN 16892 Specification English SI Standard Tensile Stre...

Страница 9: ...d pressure T P relief valves are safety mechanisms in case the system overheats mandatory in hot water distribution systems These valves act quickly to relieve excess temperature or pressure if either...

Страница 10: ...1 1 2 in 13 0 330 2 in 17 0 432 4 10 Chemical Compatibility While RAUPEX pipes are resistant to many chemicals that are used in typical residential fire sprinkler applications there are some chemical...

Страница 11: ...3 4 to 2 in manufactured in accordance with ASTM F876 For a detailed description of the REHAU system components refer to the REHAU Building Solutions Product Catalog 855 312 5 1 1 Fitting Features EVE...

Страница 12: ...designed specifically for use with EVERLOC fittings and RAUPEX pipe EVERLOC compression sleeves have the following features Co extruded platinum colored PE coating Squarely cut ends that can be slid o...

Страница 13: ...3 1 1 2 x 1 1 2 in C Male EVERLOC LF Brass Adapter 5 4 2 x 2 in C Female EVERLOC LF Brass Adapter 7 0 2 x 2 in C Male EVERLOC LF Brass Adapter 6 9 Adapters PEX to MPT FPT Fitting Description Equivale...

Страница 14: ...y Expand the RAUPEX pipe twice ensuring the expander head is rotated 1 2 of one expander head segment between expansions using the EVERLOC compression sleeve tools Insert the EVERLOC compression sleev...

Страница 15: ...nspection per prevailing local codes The requirement to wrap an EVERLOC joint can depend on many factors including location and the presence of other materials that contact or can come in contact with...

Страница 16: ...owed to expand e g it is encased in concrete it may burst NOTICE Designers and installers must take precautions as per the guidelines defined in NFPA 13D to ensure that pipes do not freeze Frozen pipe...

Страница 17: ...and the following safety symbols which are found on the EVERLOC compression sleeve tools Safety Alert Symbol To reduce the risk of injury follow the specified safety instructions Read and follow all s...

Страница 18: ...tter Lubricant Cleaning brush Tool case black latches Product Instruction Manual Fig 5 19 EVERLOC XL power tool standard kit 5 4 3 EVERLOC XL Expander Tool 1 1 4 to 2 in In addition to the EVERLOC XL...

Страница 19: ...empera ture around the sprinkler approaches its operating temperature the cover plate detaches and falls away Continued heating of the now exposed sprinkler causes the sprinkler s heat responsive elem...

Страница 20: ...nklers are visible in the wall and do not have a cover plate During fire conditions continued heating of the exposed sprinkler causes the heat responsive element to disengage This allows water to flow...

Страница 21: ...on standards and plumbing codes followed by the authority having jurisdiction In addition the local licensing requirements for the qualified sprinkler system installer must also be determined Fire spr...

Страница 22: ...entering the residence is above 80 psi 6 bar a pressure reducing valve PRV is required to limit the pressure to a maximum of 80 psi 6 bar When using a PRV the designer must take into consideration th...

Страница 23: ...d for the most hydraulically demanding point in the system for both one head activation and two head activation The most hydraulically demanding point in the system is usually the sprinkler most dista...

Страница 24: ...rature does not exceed 120 F 49 C If the ambient temperature is expected to exceed this limitation the system must be properly protected Piping must be installed at least 24 in 61 cm from air return g...

Страница 25: ...is the distance between the bottom of the joist and the bottom of the FIREPEX sprinkler fitting bracket S is the distance from the top of the threads of the fire sprinkler to the face of the drywall p...

Страница 26: ...of the FIREPEX sprinkler fitting bracket S is the distance from the top of the threads of the fire sprinkler to the face of the deflector provided by the sprinkler manufacturer DW is the thickness of...

Страница 27: ...7 Recessed pendent sprinkler mounting example 7 2 1 4 Horizontal Sidewall Sprinkler Mounting Positioning the FIREPEX sprinkler fitting for a horizontal sidewall sprinkler can be done using equation 2...

Страница 28: ...in tool boxes Contact with oil or oily products such as gasoline paint thinner glues or solvents Exposure of polymer fittings and PEXa sleeves to soldering or any open flame Excessive or permanent ex...

Страница 29: ...ists and other structural members care must be taken not to damage the pipe Protection is not required for installation in wood studs walls floor plates or joists if the following provisions are met T...

Страница 30: ...Pipe support bend Fig 7 20 Talon drive hooks Fig 7 21 Locking clip 7 10 Supporting EVERLOC Fittings Supports and clamps shall not be placed directly on the EVERLOC fitting multi port tee or compressio...

Страница 31: ...jury always wear close fitting protective eye wear with side protection Eye wear must be impact rated and marked as complying with ANSI Z87 1 Never use a torch open flame or heat gun on a pressurized...

Страница 32: ...er and safe pressure test is performed on site All other trades must be notified that the pressure test will be conducted on the piping system 7 15 Testing System Flow The local Authority Having Juris...

Страница 33: ...er wrench thread the sprinklers into the fitting New thread seal tape shall be applied to the sprinklers prior to installation 7 16 Maintaining the System The installer needs to communicate that the o...

Страница 34: ...tions guarantees or warranties of any kind are made as to its accuracy suitability for particular applications or the results to be obtained therefrom Before using the user will determine suitability...

Отзывы: