background image

7.12 Kink Repair

RAUPEX pipe is 

fl

exible and resists kinking even at temperatures well 

below freezing. If the pipe does become kinked, 

fl

ow may be 

obstructed or reduced. Kinked pipe must be repaired.

Straighten the pipe by heating the area with a heat gun, rotating the 
heat gun around the pipe to evenly heat the surface. Always use 
caution when operating a heat gun and never use a torch or open 

fl

ame to heat the pipe.

When fully heated, the pipe will become transparent. When the kink is 
gone, turn off the heat gun and let the area cool. (It is normal for 
small bubbles or wrinkles to appear.) This type of heating will anneal 
or stiffen the pipe, making it stronger but also less 

fl

exible in the 

heated area. Therefore, do not try to bend the pipe in the same spot. 
This may require a slight adjustment of fasteners.

 WARNING

 

-

Never use a torch, open 

fl

ame or heat gun on a pressurized system. 

Exceeding the temperature pressure ratings will result in dangerous 
separation of materials leading to serious injury or death.

7.13 Installing Sprinklers

The sprinklers must be installed in accordance with their listing and 
limitations. Follow all sprinkler manufacturers' guidelines for threading 
sprinkler into FIREPEX 

fi

re sprinkler 

fi

ttings. 

Sprinkler wrenches are installation tools speci

fi

cally designed for use 

with residential sprinklers. The appropriate wrench must be used with 
the individual sprinkler to provide the proper leverage when tightening 
and to minimize slippage during installation. 

 CAUTION

Using wrenches other than those designated by the 

fi

re sprinkler 

manufacturer may damage the 

fi

re sprinkler.

7.14 Pressure Testing

REHAU has a detailed pressure test procedure for testing a REHAU 
PEXa piping system as set forth below.

 WARNING

 

 

-

Failure to follow proper safety precautions for an air pressure test 
could result in dangerous separation of the material, leading to 
serious injury or death.

 

-

Use personal protective equipment. To reduce the risk of eye injury, 
always wear close-

fi

tting protective eye wear with side protection. 

Eye wear must be impact-rated and marked as complying with ANSI 
Z87.1.

 

-

Never use a torch, open 

fl

ame or heat gun on a pressurized system. 

Exceeding the temperature pressure ratings will result in dangerous 
separation of materials leading to serious injury or death.

 

-

Never rework a connection that is under pressure. Depressurize the 
system, cut out connection and replace.

 

-

To reduce the risk of personal injury, only quali

fi

ed persons 

conducting and/or inspecting the pressure test should be present. 

The following recommended pressure test procedure applies to both 
compressed air and hydrostatic (water) testing:

7.14.1 General Recommendations

 

-

A pressure test must always be performed prior to closing in the 
system (e.g., behind drywall).

 

-

Perform test using water or air at ambient temperature. Do not 
exceed 150 psi (1030 kPa) for the piping system. Verify maximum 
pressure limits are not exceeded for all system components prior to 
performing the pressure test.  

 

-

When air pressure testing with polymer 

fi

ttings do not 

exceed 120 psi (825 kPa). 

 

-

For RFH and SIM systems, a pressure test must always be per-
formed on the system prior to and during the installation of the 
thermal mass to ensure that RAUPEX pipe and connections are leak 
free. For dry systems (e.g., joist space), a pressure test must be 
performed after installation and up to the time that the system is put 
in operation.

 

-

Tests shall comply with local codes where applicable and, where 
required, shall be witnessed by the building of

fi

cial.

7.14.2 Pressure Testing with Air

Air can store a high amount of energy as compared to water during a 
pressure test. Due to this higher energy, different failure modes of 
system materials must be understood by persons conducting the 
pressure test.

 

-

If a thermoset polymer (e.g., PEXa pipe) is over-pressurized and fails 
(bursts), it does so in a ductile mode, meaning that the pipe will 
swell and then split with no separation of fragments. 

 

-

If a rigid thermoplastic polymer material (e.g., PPSU) is over-pres-
surized and fails (bursts), it does so in a brittle mode and can result 
in separation of the material.

31

Содержание Firepex

Страница 1: ...FIREPEX RESIDENTIAL FIRE SPRINKLER SYSTEM Design and Installation Guide...

Страница 2: ...eeve Fittings 11 5 1 Fitting Scope 11 5 2 Fitting Assembly 14 5 3 Installation Considerations 14 5 4 EVERLOC Compression sleeve Tools 17 5 3 Fire Sprinklers 19 6 System Planning 21 6 1 Determine Local...

Страница 3: ...delines are defined in the REHAU PEXa Limited Warranty as The most current and applicable versions of all the technical literature available on the REHAU North America website at www na rehau com reso...

Страница 4: ...nkler Systems The NFPA 13D standard categorizes all fire sprinkler systems within two general types wet pipe systems and dry pipe systems Wet pipe systems are filled with water and installed in areas...

Страница 5: ...l information is not intended to be used as final drawings or specifications and is provided only as an aid in designers develop ment of the final specification and is not intended as a substitute for...

Страница 6: ...n connections and routing of the service line into the residence Determine the specifications for the sprinklers including water flow and operating pressure requirements and coverage area specificatio...

Страница 7: ...are not certified for fire sprinkler systems The FIREPEX system is third party certified by NSF International www nsf org to the following standards UL 1821 Standard for Thermoplastic Sprinkler Pipe a...

Страница 8: ...70 C per DIN 16892 Modulus of Elasticity 87 000 130 500 psi 68 F 43 500 58 000 psi 176 F 600 900 N mm2 20 C 300 400 N mm2 80 C Minimum 20 C per DIN 16892 Specification English SI Standard Tensile Stre...

Страница 9: ...d pressure T P relief valves are safety mechanisms in case the system overheats mandatory in hot water distribution systems These valves act quickly to relieve excess temperature or pressure if either...

Страница 10: ...1 1 2 in 13 0 330 2 in 17 0 432 4 10 Chemical Compatibility While RAUPEX pipes are resistant to many chemicals that are used in typical residential fire sprinkler applications there are some chemical...

Страница 11: ...3 4 to 2 in manufactured in accordance with ASTM F876 For a detailed description of the REHAU system components refer to the REHAU Building Solutions Product Catalog 855 312 5 1 1 Fitting Features EVE...

Страница 12: ...designed specifically for use with EVERLOC fittings and RAUPEX pipe EVERLOC compression sleeves have the following features Co extruded platinum colored PE coating Squarely cut ends that can be slid o...

Страница 13: ...3 1 1 2 x 1 1 2 in C Male EVERLOC LF Brass Adapter 5 4 2 x 2 in C Female EVERLOC LF Brass Adapter 7 0 2 x 2 in C Male EVERLOC LF Brass Adapter 6 9 Adapters PEX to MPT FPT Fitting Description Equivale...

Страница 14: ...y Expand the RAUPEX pipe twice ensuring the expander head is rotated 1 2 of one expander head segment between expansions using the EVERLOC compression sleeve tools Insert the EVERLOC compression sleev...

Страница 15: ...nspection per prevailing local codes The requirement to wrap an EVERLOC joint can depend on many factors including location and the presence of other materials that contact or can come in contact with...

Страница 16: ...owed to expand e g it is encased in concrete it may burst NOTICE Designers and installers must take precautions as per the guidelines defined in NFPA 13D to ensure that pipes do not freeze Frozen pipe...

Страница 17: ...and the following safety symbols which are found on the EVERLOC compression sleeve tools Safety Alert Symbol To reduce the risk of injury follow the specified safety instructions Read and follow all s...

Страница 18: ...tter Lubricant Cleaning brush Tool case black latches Product Instruction Manual Fig 5 19 EVERLOC XL power tool standard kit 5 4 3 EVERLOC XL Expander Tool 1 1 4 to 2 in In addition to the EVERLOC XL...

Страница 19: ...empera ture around the sprinkler approaches its operating temperature the cover plate detaches and falls away Continued heating of the now exposed sprinkler causes the sprinkler s heat responsive elem...

Страница 20: ...nklers are visible in the wall and do not have a cover plate During fire conditions continued heating of the exposed sprinkler causes the heat responsive element to disengage This allows water to flow...

Страница 21: ...on standards and plumbing codes followed by the authority having jurisdiction In addition the local licensing requirements for the qualified sprinkler system installer must also be determined Fire spr...

Страница 22: ...entering the residence is above 80 psi 6 bar a pressure reducing valve PRV is required to limit the pressure to a maximum of 80 psi 6 bar When using a PRV the designer must take into consideration th...

Страница 23: ...d for the most hydraulically demanding point in the system for both one head activation and two head activation The most hydraulically demanding point in the system is usually the sprinkler most dista...

Страница 24: ...rature does not exceed 120 F 49 C If the ambient temperature is expected to exceed this limitation the system must be properly protected Piping must be installed at least 24 in 61 cm from air return g...

Страница 25: ...is the distance between the bottom of the joist and the bottom of the FIREPEX sprinkler fitting bracket S is the distance from the top of the threads of the fire sprinkler to the face of the drywall p...

Страница 26: ...of the FIREPEX sprinkler fitting bracket S is the distance from the top of the threads of the fire sprinkler to the face of the deflector provided by the sprinkler manufacturer DW is the thickness of...

Страница 27: ...7 Recessed pendent sprinkler mounting example 7 2 1 4 Horizontal Sidewall Sprinkler Mounting Positioning the FIREPEX sprinkler fitting for a horizontal sidewall sprinkler can be done using equation 2...

Страница 28: ...in tool boxes Contact with oil or oily products such as gasoline paint thinner glues or solvents Exposure of polymer fittings and PEXa sleeves to soldering or any open flame Excessive or permanent ex...

Страница 29: ...ists and other structural members care must be taken not to damage the pipe Protection is not required for installation in wood studs walls floor plates or joists if the following provisions are met T...

Страница 30: ...Pipe support bend Fig 7 20 Talon drive hooks Fig 7 21 Locking clip 7 10 Supporting EVERLOC Fittings Supports and clamps shall not be placed directly on the EVERLOC fitting multi port tee or compressio...

Страница 31: ...jury always wear close fitting protective eye wear with side protection Eye wear must be impact rated and marked as complying with ANSI Z87 1 Never use a torch open flame or heat gun on a pressurized...

Страница 32: ...er and safe pressure test is performed on site All other trades must be notified that the pressure test will be conducted on the piping system 7 15 Testing System Flow The local Authority Having Juris...

Страница 33: ...er wrench thread the sprinklers into the fitting New thread seal tape shall be applied to the sprinklers prior to installation 7 16 Maintaining the System The installer needs to communicate that the o...

Страница 34: ...tions guarantees or warranties of any kind are made as to its accuracy suitability for particular applications or the results to be obtained therefrom Before using the user will determine suitability...

Отзывы: