background image

RCF-230TD

3

Description

FS

10

Not used for this model

11

Switch off timer for Comfort mode

0 min

12

Switch on delay for Comfort mode

0 min

13

Sensor connected to AI1:
0=Internal sensor, 1=External room sensor, 
11=Supply air limitation sensor

0

14

Sensor connected to UI1:
0=None, 1=Change-over digital, 2=Change-over 

analogue, 3=Off mode (open window)

0

15

Type of digital actuator:
0=Thermal, 1=3-point

0

16-
17

Not used for this model

18

Period time for heating actuator with  
thermal actuator

60 s

19

Period time for cooling actuator with  
thermal actuator

60 s

20

Runtime for heating actuator with increase/de-
crease actuator

120 s

21

Runtime for cooling actuator with increase/de-
crease actuator

120 s

22

Time in hours between exercise of heating actua-
tor

23

23

Time in hours between exercise of cooling actua-
tor

23

24

Setpoint or actual value shown in the display: 
0=Actual, setpoint when changing the setpoint, 
1=Actual value, setpoint adjustment when setpoint 
adjustment is altered, 2=Setpoint, 3=Only the 
setpoint adjustment

2

25

Configuration of fan control:

0=No control, 1=The fan is controlled by heating 
requirement, 2=The fan is controlled by cooling 
requirement, 3=The fan is controlled by heating 
and cooling requirement
When using an electric heater, this parameter 
should only be set to 1 or 3, or the heater may be 
overheated.

3

26

Start signal in % of the controller output, heating 
or cooling, for fan speed 1

20 (5 
when 
using an 
electric 
heater)

Description

FS

27

Start signal in % of the controller output, heating 
or cooling, for fan speed 2

60

28

Start signal in % of the controller output, heating 
or cooling, for fan speed 3

100

29

Hysteresis for start/stop of fans in % of the control-
ler output

5

30

Number of fan speeds

3

31

Fan speed in the Auto mode: 
0=The fan speed follows the cooling/heating 
output, 1=The fan speed is minimum limited to 
the lowest speed

1

32

Temperature compensation on AI1

0 K

33

Temperature compensation for the internal room 
sensor.

0 K

34

Highest permitted setpoint offset upwards. Set

-

table value=0...13 K. Starting point=22°C.

13 K

35

Highest permitted setpoint offset downwards. Set

-

table value=0...17 K. Starting point=22°C.

17 K

36

NO/NC digital input 1:
0=NO, 1=NC

0

37

NO/NC universal input 1:
0=NO, 1=NC

0

38

NO/NC digital output 4:
0=NO, 1=NC

1

39

NO/NC digital output 5:
0=NO, 1=NC

1

40

Manual/Auto heating output signal: 

0=Off, 1=Manual, 2=Auto

2

41

Manual/Auto cooling output signal: 

0=Off, 1=Manual, 2=Auto

2

42

Heating output signal in manual mode.

0

43

Cooling output signal in manual mode.

0

44

Model

-

45

Version Major

-

46

Version Minor

-

47

Released or beta version

-

48

Revision

-

49

Display backlight low

10

50

Display backlight high

30

Description

FS

51-
63

Not used for this model

64

Basic setpoint. Settable value=5...50°C.

22°C

65

Settings, active buttons:

0 = No active buttons

1 = Only On/Off button active

2 = Only Up/Down buttons active

3 = On/Off and Up/Down buttons active

4 = Only fan button active

5 = On/Off and fan button active

6 = Up/Down and fan buttons active
7 = All buttons active

7

66

Function to prevent user from setting manual fan 
speed if fan should not run due to cooling/heating 
output according to parameter 25.
0 = Not active
1 = Active

0

67

Not used for this model

-

68

Not used for this model

-

69

Fan kickstart. The fan will then run at 100 
% for a set time when starting up (0...10 
seconds).

0 s

70

Supply air temperature max limitation for 
cascade control and heating control

35°C

71

Supply air temperature min limitation for 
cascade control and heating control

24°C

72

Supply air temperature max limitation for 
cascade control and cooling control

24°C

73

Supply air temperature min limitation for 
cascade control and cooling control

12°C

74

Cascade factor between room controller and 
supply air controller

3°C

75

Frost protection temperature for supply air 
when supply air temperature limitation is 
active

8°C

76

Activate supply air temperature limitation for: 
0 = Heating control, 1 = Cooling control, 2 = 
Both heating and cooling control

1

Содержание RCF-230TD

Страница 1: ...e all connections must be made externally An over heating protection or similar can be used to disconnect the supply voltage Disconnection RCF 230TD should be connected to a switch or circuit breaker...

Страница 2: ...open window symbol is shown if this function has been configured and a window is open OFF The controller does not heat or cool On Off button By pressing the On Off button RCF 230TD will switch between...

Страница 3: ...re compensation on AI1 0 K 33 Temperature compensation for the internal room sensor 0 K 34 Highest permitted setpoint offset upwards Set table value 0 13 K Starting point 22 C 13 K 35 Highest permitte...

Страница 4: ...5 for cooling actuators If the installation is a 2 pipe installation and the change over function is used the actuator should be connected to DO4 When connecting 3 point actuators DO4 is used for incr...

Страница 5: ...F lj alltid de anvisade s kerhetsf reskrifterna i dokumentationen f r att f rebygga risken f r brand elst t och personskador INSTRUKTION RCF 230TD SV Rumsregulator f r styrning av fan coil enheter RCF...

Страница 6: ...F nster visas i displayen regulatorn r i fr nslaget l ge och fl kten stannar f rutom om m gelskydd har valts eller nedkylning av elv rmaren r aktiv d forts tter fl kten att g F nsterkontakten ansluts...

Страница 7: ...min 12 Tillslagsf rdr jning f r Komfortl ge 0 min 13 Givare ansluten till AI1 0 Intern givare 1 Extern rumsgivare 11 Begr n sningsgivare f r tilluft 0 14 Givare ansluten till UI1 0 Ingen 1 Change over...

Страница 8: ...under inst lld tid 0 10 sekunder 0 s 70 Maxbegr nsning f r tilluftstemperatur vid kaskadreglering och v rmereglering 35 C 71 Minbegr nsning f r tilluftstemperatur vid kaskadreglering och v rmereglerin...

Страница 9: ...31 DO4 Digital utg ng 4 f r v rme kyl signal eller ppna med 3 punktsst ll don Digital utg ng 230 V AC max 300 mA Max 2 A under 20 ms 32 CDO45 Gemensam DO4 5 Gemensam anslutning f r digital utg ng 4 oc...

Страница 10: ...rbeiten an Fan Coil und Stellantrieben ist der Regler grund s tzlich mit Hilfe des Schutzschalters von der Versorgungsspannung zu trennen Einstellungen Regelmodi RCF 230TD verf gt ber die Regelmodi He...

Страница 11: ...instellungen von unbefugten Personen ge ndert werden Dabei ist es m glich entweder nur bestimmte Tasten oder ggf auch alle Tasten zu blockieren Die entsprechende Aktivierung erfolgt ber Parameter 65 D...

Страница 12: ...NO 1 NG 1 39 NO NG Digitalausgang 5 0 NO 1 NG 1 40 Hand Automatik Stellsignal Heizen 0 Aus 1 Hand 2 Auto 2 41 Hand Automatik Stellsignal K hlen 0 Aus 1 Hand 2 Auto 2 42 Stellsignal Heizen in Handbetri...

Страница 13: ...der Verwendung thermischer Stellantriebe wird DO4 f r Heizstel lantriebe und DO5 f r K hlstellantrieb eingesetzt Bei einer 2 Rohr System Installation und der Verwendung der Change Over Funktion muss...

Страница 14: ...ls de INSTRUCTION i Instruction pour les produits ayant la version 1 4 ou plus Veuillez lire cette instruction avant de proc der l installation et au raccordement du produit RCF 230TD FR Afin d viter...

Страница 15: ...ue le mode refroidissement est configur la s quence de fonction nement repr sentera une s quence normale de chauffage refroidisse ment au cours de laquelle DO4 et DO5 s ouvrent en fonction des besoins...

Страница 16: ...r les boutons AUGMENTER ET DIMINUER jusqu ce que l indication SER VICE apparaisse l cran environs 5 s puis appuyer deux fois sur la touche AUGMENTER Le param tre 1 s affiche en premier Le param tre 1...

Страница 17: ...auto 0 arr t 1 Manuel 2 Auto 2 41 Signal de sortie refroidissement manuel auto 0 arr t 1 Manuel 2 Auto 2 42 Commande manuelle du signal de sortie chauf fage 0 43 Commande manuelle du signal de sortie...

Страница 18: ...Raccordement de diff rents actionneurs Avec des actionneurs thermiques utiliser DO4 pour commander l actionneur du chauffage et DO5 pour commander l actionneur de refroidissement Lorsque la fonction c...

Страница 19: ...tact libre de potentiel pour un contact de fen tre ou un d tecteur de pr sence Configurable sur NO NF 41 Agnd Commun analo gique 42 AI Entr e analogique Sonde d ambiance PT1000 externe la place de la...

Отзывы: