RCF-230TD
3
Nº
Description
FS
10
Not used for this model
11
Switch off timer for Comfort mode
0 min
12
Switch on delay for Comfort mode
0 min
13
Sensor connected to AI1:
0=Internal sensor, 1=External room sensor,
11=Supply air limitation sensor
0
14
Sensor connected to UI1:
0=None, 1=Change-over digital, 2=Change-over
analogue, 3=Off mode (open window)
0
15
Type of digital actuator:
0=Thermal, 1=3-point
0
16-
17
Not used for this model
18
Period time for heating actuator with
thermal actuator
60 s
19
Period time for cooling actuator with
thermal actuator
60 s
20
Runtime for heating actuator with increase/de-
crease actuator
120 s
21
Runtime for cooling actuator with increase/de-
crease actuator
120 s
22
Time in hours between exercise of heating actua-
tor
23
23
Time in hours between exercise of cooling actua-
tor
23
24
Setpoint or actual value shown in the display:
0=Actual, setpoint when changing the setpoint,
1=Actual value, setpoint adjustment when setpoint
adjustment is altered, 2=Setpoint, 3=Only the
setpoint adjustment
2
25
Configuration of fan control:
0=No control, 1=The fan is controlled by heating
requirement, 2=The fan is controlled by cooling
requirement, 3=The fan is controlled by heating
and cooling requirement
When using an electric heater, this parameter
should only be set to 1 or 3, or the heater may be
overheated.
3
26
Start signal in % of the controller output, heating
or cooling, for fan speed 1
20 (5
when
using an
electric
heater)
Nº
Description
FS
27
Start signal in % of the controller output, heating
or cooling, for fan speed 2
60
28
Start signal in % of the controller output, heating
or cooling, for fan speed 3
100
29
Hysteresis for start/stop of fans in % of the control-
ler output
5
30
Number of fan speeds
3
31
Fan speed in the Auto mode:
0=The fan speed follows the cooling/heating
output, 1=The fan speed is minimum limited to
the lowest speed
1
32
Temperature compensation on AI1
0 K
33
Temperature compensation for the internal room
sensor.
0 K
34
Highest permitted setpoint offset upwards. Set
-
table value=0...13 K. Starting point=22°C.
13 K
35
Highest permitted setpoint offset downwards. Set
-
table value=0...17 K. Starting point=22°C.
17 K
36
NO/NC digital input 1:
0=NO, 1=NC
0
37
NO/NC universal input 1:
0=NO, 1=NC
0
38
NO/NC digital output 4:
0=NO, 1=NC
1
39
NO/NC digital output 5:
0=NO, 1=NC
1
40
Manual/Auto heating output signal:
0=Off, 1=Manual, 2=Auto
2
41
Manual/Auto cooling output signal:
0=Off, 1=Manual, 2=Auto
2
42
Heating output signal in manual mode.
0
43
Cooling output signal in manual mode.
0
44
Model
-
45
Version Major
-
46
Version Minor
-
47
Released or beta version
-
48
Revision
-
49
Display backlight low
10
50
Display backlight high
30
Nº
Description
FS
51-
63
Not used for this model
64
Basic setpoint. Settable value=5...50°C.
22°C
65
Settings, active buttons:
0 = No active buttons
1 = Only On/Off button active
2 = Only Up/Down buttons active
3 = On/Off and Up/Down buttons active
4 = Only fan button active
5 = On/Off and fan button active
6 = Up/Down and fan buttons active
7 = All buttons active
7
66
Function to prevent user from setting manual fan
speed if fan should not run due to cooling/heating
output according to parameter 25.
0 = Not active
1 = Active
0
67
Not used for this model
-
68
Not used for this model
-
69
Fan kickstart. The fan will then run at 100
% for a set time when starting up (0...10
seconds).
0 s
70
Supply air temperature max limitation for
cascade control and heating control
35°C
71
Supply air temperature min limitation for
cascade control and heating control
24°C
72
Supply air temperature max limitation for
cascade control and cooling control
24°C
73
Supply air temperature min limitation for
cascade control and cooling control
12°C
74
Cascade factor between room controller and
supply air controller
3°C
75
Frost protection temperature for supply air
when supply air temperature limitation is
active
8°C
76
Activate supply air temperature limitation for:
0 = Heating control, 1 = Cooling control, 2 =
Both heating and cooling control
1