Regin PDTX C Series Скачать руководство пользователя страница 4

LEDs

Description

Yellow

RS485 data transmission indication

Red

Global device status. Is activated when an error is
present (see the variable list for more details).

Green

1 Hz flash rate: Normal operation
5 Hz flash rate: Zero-set calibration is preformed
25 Hz flash rate: Factory reset is performed

Push-button

Action

Description

Quick press

Zero-set pressure calibration
The green LED will be flashing when the zero-set
operation has been made.

Long press (> 10 s)

Reset to factory default settings
The green LEDs will be flashing during the opera-
tion. The unit will then reset and restart.

Zero-set pressure calibration

A short press on the push-button will zero-set calibrate the available
pressure sensors.

N

No

ottee!! Be sure to disconnect the pressure tubes before doing this. Let the

unit warm up for 10 minutes before attempting zero-set.

Factory reset

A long press on the push-button, more than 10 seconds, will perform a
factory restore of user defined settings.

Table 4

displays some of the

settings that will be restored.

Table 4 Factory settings

Description

Factory setting

Working range, pressure

0…1250 / 0…2500 / 0…7500 Pa

Working range, flow

0...65000 m

3

/h

UI

0…10 V

UO

0…10 V

Modbus address

1

Modbus setting

8 bytes, 1 stop bit, no parity

Modbus baud rate

9600 bps

K-factor

5

N

No

ottee!! All changes made with Modbus will be reset when a factory reset

is made.

This product carries the CE-mark. More information is available at
www.regincontrols.com.

Documentation

All documentation can be downloaded from www.regincontrols.com

Contact

AB Regin, Box 116, 428 22 Kållered, Sweden
Tel: +46 31 720 02 00, Fax: +46 31 720 02 50
www.regincontrols.com, [email protected]

SE

INSTRUKTION

PDTX…-C

N

Nootteerraa!! Mer information om hur produkten konfigureras finns i variabe-

llistan, som är tillgänglig för nedladdning från www.regincontrols.com

O

Obbsseerrvveerraa!! Läs och förstå instruktionen innan du använder produkten.

O

Obbsseerrvveerraa!! Se till att installationen uppfyller lokala

säkerhetsbestämmelser.

O

Obbsseerrvveerraa!! Innan installation eller underhåll måste matningsspänningen

först kopplas från. Installation eller underhåll av denna enhet ska endast ut-
föras av kvalificerad personal. Tillverkaren är inte ansvarig för eventuella
skador som orsakas av felaktig installation och/eller inaktivering eller bort-
tagning av säkerhetsanordningar.

Funktion

Presigo PDTX…-C är en serie trycktransmittrar med en eller två
tryckgivare, två universella ingångar, två universella utgångar och en
RS485-port för Modbus-kommunikation. Den fungerar som en Modbus-
slav.

Denna serie trycktransmittrar passar mycket väl som distribuerade I/O-
moduler för luftbehandlingsenheter. De är utformade för enkel
installation med Regins regulatorer Corrigo eller EXOcompact.

Tekniska data

Matningsspänning

24 V AC/DC (21…27 V AC/DC)

Skyddsklass

IP54

Strömförbrukning

< 4 VA

Omgivande luftfuktighet

0…95 % RH (icke-kondenserande)

Omgivningstemperatur

-25…+50 °C

Arbetsområde, tryck

0…1250 / 0…2500 / 0…7500 Pa (fabriksinställning)
0…12 / 0…25 / 0…75 mbar
0…127 / 0…254 / 0…764 mmH

2

O

0…5 / 0…10 / 0…30 inH

2

O

Arbetsområde, flöde

0...65000 m

3

/h (fabriksinställning)

0...31000 l/s
0...65000 Ft

3

/min

Kabelgenomföringar

2 x M20 (kabeldiameter 5…12 mm)
1 x M16 (kabeldiameter 3,5…10 mm)

Max spänning

±18 V, oberoende av plint (ej G och G0)

Elektronisk dämpning

0 s (0…120 s)

Tillbehör, inkluderade

Två tryckuttag (raka) och 2 m plastslang. Art. no.:
ANS-20

Dimensioner, yttre
(BxHxD)

167 x (~130) x 46 mm

Tryckdata

Media

Luft, icke-brännbara och icke-aggressiva gaser

Årlig avvikelse

±2 Pa (1250 Pa)
±4 Pa (2500 Pa)
±20 Pa (7500 Pa)

K-faktor

5 (5…700)

Universella ingångar, UI1 och UI2

Universella ingångar (UI)

2

Konfigurering

AI (AI / DI), se specifikationer nedan

Konfigurerad som AI:

Analoga ingångar (AI)

0…10 V (0…10 V / PT1000 / Ni1000-01)

Noggrannhet

± 1 % (0…10 V)
± 0,5 K (PT1000/Ni1000-01)

Mätområde, temperatur

-40…+60 °C

Konfigurerad som DI:

Presigo

4 (18)

Содержание PDTX C Series

Страница 1: ...inH2O Working range flow 0 65000 m3 h factory setting 0 31000 l s 0 65000 Ft3 min Cable glands 2 x M20 cable diameter 5 12 mm 1 x M16 cable diameter 3 5 10 mm Max overvoltage 18 V on any terminal not...

Страница 2: ...st pressure and the inlet marked with to the one with the lowest pressure N No ot te e A straight cut off nipple must be used for mounting in the ventila tion duct For optimal measuring results measur...

Страница 3: ...2 UI2 u UI Value in 0 10 V mode u 1 UI1 u 2 UI2 t UI Value in temperature mode C t 1 UI1 t 2 UI2 L UO Value in digital mode L 1 UO1 L 2 UO2 U UO Value in 0 10 V mode U 1 UO1 U 2 UO2 Two digits can be...

Страница 4: ...ntrols com O Ob bs se er rv ve er ra a L s och f rst instruktionen innan du anv nder produkten O Ob bs se er rv ve er ra a Se till att installationen uppfyller lokala s kerhetsbest mmelser O Ob bs se...

Страница 5: ...till plint 3 A och 4 B Anv nd v nster kabelgenomf ring f r matningssp nning och kommunikation 3 Sp nningss tt enheten G r de kommunikationsinst llningar som nskas i menyn se Inst llningar Notera att t...

Страница 6: ...joysticken till v nster f r att avf rda ndringarna 7 F r joysticken till v nster f r att terg till f reg ende meny N No ot te er ra a Den senast gjorda inst llningen i transmittern g ller alltid oavse...

Страница 7: ...n ut f rs L t enheten v rma upp i 10 minuter innan ett f rs k till nollpunktska librering g rs Fabriks terst llning Ett l ngt tryck p tryckknappen mer n 10 sekunder utf r en fabriks terst llning av an...

Страница 8: ...e 24 V AC oder DC 2 A kontinuierlich Ausgang Spannungsversorgung Max 2 A gesamt UO1 UO2 Kommunikation ber Datenschnittstelle Kommunikationsschnitt stellen 1 Schnittstellentyp RS485 Unterst tzte Protok...

Страница 9: ...rbunden mit Klemme 1 7 GND Intern verbunden mit Klemme 2 8 UO2 Universalausgang 2 Klemme Name Beschreibung 9 UI1 Universaleingang 1 10 GND Intern verbunden mit Klemme 2 11 UI2 Universaleingang 2 Verwe...

Страница 10: ...den mehrere aufeinanderfolgende Anzeigen verwendet um einen l ngeren Wert darzustellen Beispiel Ein Druckwert von 2350 Pa am F hler 1 wird mit drei Anzeigen dargestellt d h 1 P 1 2 23 3 50 Die Ma einh...

Страница 11: ...tallation est conforme aux normes de s curit locales A At tt te en nt tiio on n Avant de proc der l installation ou la maintenance de l ap pareil il convient de couper l alimentation lectrique Les op...

Страница 12: ...et 4 B Utiliser l entr e la plus gauche pour l alimentation et la communication 3 Mettre le r gulateur sous tension R gler les param tres de communication partir du menu voir R glages Note Adresse Mod...

Страница 13: ...par un mouvement vers la gauche 7 Manette vers la gauche pour un retour l cran pr c dent N NB B La derni re configuration entr e dans le transmetteur est toujours valide ind pendamment de la configura...

Страница 14: ...ression R initialisation Un appui long sur le bouton poussoir plus de 10 secondes lance la r initialisation aux param tres usine Tableau 4 indique les param tres restaur s Tableau 4 R glages usine Des...

Страница 15: ...Lunghezza del cavo Max 100 m Modelli Articolo Numero di sensori Max pressione di sovraccarico kPa Campo di misura pressione Pa PDTX12 C 1 25 0 1250 PDTX25 C 1 50 0 2500 PDTX75 C 1 120 0 7500 PDTX12 2...

Страница 16: ...ualizzate e modificate tramite il sistema di menu o tramite Modbus Tutte le altre impostazioni sono accessibili e modificabili tramite Modbus Il joystick viene utilizzato per spostarsi all interno del...

Страница 17: ...bps Tabella 3 Impostazioni nel sottomenu C Impostazioni Modbus Descrizione n1 8 byte 1 bit di stop nessuna parit impo stazione di fabbrica n2 8 byte 2 bit di stop nessuna parit E1 8 byte 1 bit di sto...

Страница 18: ...u www industrietechnik it Documentazione La documentazione pu essere scaricata da www industrietechnik it Contatti AB Industrietechnik SRL Via Julius Durst Str 50 I 39042 Bressanone BZ Tel 39047283062...

Отзывы: