![Regin PDTX C Series Скачать руководство пользователя страница 1](http://html1.mh-extra.com/html/regin/pdtx-c-series/pdtx-c-series_instructions-manual_1434305001.webp)
EN
INSTRUCTION
PDTX…-C
REV. C, 2022-03-14
N
No
ottee!! More information about the product configuration can be found in
the variable list, which is available for download from www.regincontrols.
com
C
Caauuttiioonn!! Read and understand the instruction before using the product.
C
Caauuttiioonn!! Ensure that the installation complies with local safety
regulations.
C
Caauuttiioonn!! Before installation or maintenance, the power supply should first
be disconnected. Installation or maintenance of this unit should only be
carried out by qualified personnel. The manufacturer is not responsible
for any eventual damage or injury caused by inadequate skills during instal-
lation, or through removal of or deactivation of any security devices.
Function
Presigo PDTX…-C is a range of pressure transmitters equipped with one
or two pressure sensors, two universal inputs, two universal outputs and
an RS485 port for Modbus communication. It operates as a Modbus
slave.
This range of pressure transmitters is especially well suited as distributed
I/O modules for air handling unit controllers. They are designed for easy
installation together with Regin’s Corrigo or EXOcompact controllers.
Technical data
Supply voltage
24 V AC/DC (21…27 V AC/DC)
Protection class
IP54
Power consumption
< 4 VA
Ambient humidity
0…95 % RH (non-condensing)
Ambient temperature
-25…+50 °C
Working range, pressure
0…1250 / 0…2500 / 0…7500 Pa (factory setting)
0…12 / 0…25 / 0…75 mbar
0…127 / 0…254 / 0…764 mmH
2
O
0…5 / 0…10 / 0…30 inH
2
O
Working range, flow
0...65000 m
3
/h (factory setting)
0...31000 l/s
0...65000 Ft
3
/min
Cable glands
2 x M20 (cable diameter 5…12 mm)
1 x M16 (cable diameter 3.5…10 mm)
Max overvoltage
±18 V, on any terminal (not G and G0)
Electronic damping
0 s (0…120 s)
Accessories, included
Two pressure outlets (straight) and 2 m plastic tube.
Art. no.: ANS-20
Dimensions, external
(WxHxD)
167 x (~130) x 46 mm
Pressure data
Media
Air, non-combustible and non-aggressive gases
Annual deviation
±2 Pa (1250 Pa)
±4 Pa (2500 Pa)
±20 Pa (7500 Pa)
K-factor
5 (5…700)
Universal Input, UI1 and UI2
Universal inputs (UI)
2
Configuration
AI (AI / DI), see specifications below
Configured as AI:
Analogue inputs (AI)
0…10 V (0…10 V / PT1000 / Ni1000-01)
Accuracy
± 1 % (0…10 V)
± 0.5 K (PT1000/Ni1000-01)
Measuring range,
temperature
-40…+60 °C
Configured as DI:
Digital input (DI)
Potential-free contacts on / off (on = closed)
Output current
0.5 mA (max 2.5 V)
Universal Output, UO1 and UO2
Universal outputs (UO)
2
Configuration
AO (AO / DO), see specifications below
Configured as AO:
Analogue outputs (AO)
0…10 V
Load impedance, 0...10 V
Min. 10 kΩ
Accuracy
± 1 %
Configured as DO:
Configuration
Mosfet outputs, 24 V AC or DC, 2 A continuous
Power output
Max. 2A (total UO1 + UO2)
Communication port data
Communication ports
1
Port type
RS485
Supported protocols
Modbus
Port isolation
Non-isolated
Cable length
Max 100 m
Models
Article
Number of
sensors
Max overload
pressure (kPa)
Measuring range,
pressure (Pa)
PDTX12-C
1
25
0…1250
PDTX25-C
1
50
0…2500
PDTX75-C
1
120
0…7500
PDTX12-2-C
2
25 / 25
0…1250 (sensor 1) /
0…1250 (sensor 2)
PDTX25-2-C
2
50 / 50
0…2500 (sensor 1) /
0…2500 (sensor 2)
PDTX12S25-C
2
25 / 50
0…1250 (sensor 1) /
0…2500 (sensor 2)
PDTX12S75-C
2
25 / 120
0…1250 (sensor 1) /
0…7500 (sensor 2)
Presigo