Regency
®
P121-10/P131-10 Zero Clearance Direct Vent Gas Fireplace
|
23
23
|
installation
Vertical Venting with Two (2) 90
o
Elbows
Option
V
+
V1
H
A)
1' (305mm) Minimum
4' (1.22m) Maximum
B)
2' (610mm) Minimum
6' (1.86m) Maximum
C) 3' (914mm) Minimum
9' (2.7m) Maximum
D) 4' (1.22m) Minimum
12' (3.6m) Maximum
E)
5' (1.5m) Minimum
15' (4.5m) Maximum
F)
6' (1.86m) Minimum
17' (5.1m) Maximum
Vertical Venting with Two (2) 90
o
Elbows
Vertical Venting with Three (3) 90
o
Elbows
Diagram 9
Diagram 10
Diagram 11
Option
V
H + H1
A)
1' (305mm) Minimum
2' (610mm) Maximum
B)
2' (610mm) Minimum
4' (1.22m) Maximum
C) 3' (914mm) Minimum
6' (1.86m) Maximum
D) 4' (1.22m) Minimum
8' (2.4m) Maximum
With the above options, maximum total pipe length if 37 feet
with minimum of 6 feet total vertical and maximum 17 feet total
horizontal.
Please note minimum 1 foot between 90
o
elbows is required.
With the above options, maximum total pipe length if 37 feet
with minimum of 4 feet total vertical and maximum 8 feet total
horizontal.
Please note minimum 1 foot between 90
o
elbows is required.
Option V + V1 H
H + H1
A)
2' (610mm) Min. 1' (305mm) Max. 2' (610mm) Max.
B)
3' (914mm) Min. 4' (1.22m) Max. 5' (1.5m) Max.
C)
4' (1.22mm) Min. 6' (1.86m) Max. 8' (2.4m) Max.
D)
5' (1.5m) Min.
8' (2.4m) Max.
12' (3.6m) Max.
With the above options, maximum total pipe length if 37 feet with minimum
of 5 feet total vertical and maximum 12 feet total horizontal.
Please note minimum 1 foot between 90
o
elbows is required.