Regency HZ33CE-10 Gas Fireplace
|
10
installation
Caution Requirements
The top, back and sides of the fireplace are defined by
standoffs. The metal ends of the standoff may
NOT
be recessed into combustible construction.
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials are not
adhered to. It is of greatest importance that this fireplace and vent
system be installed only in accordance with these instructions.
CLEARANCES
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest
importance that this fireplace and vent system be installed only in accordance with these instructions.
C
F
G
Clearance:
Dimension
Measured From:
A: *Front Floor Clearance (min.)
0"
Underside of Unit
B: *Sidewall (on one side)
9" (229mm)
Side Opening of Unit
C: *Ceiling
(room and/or alcove)
30" (762mm)
Top Opening of Unit
D: Alcove Width
84" (1219mm)
Sidewall to Sidewall (Minimum)
E: Alcove Depth
36" (914mm)
Front to Back Wall (Maximum)
F: Mantel
12" (305mm)
G: Mantel Clearances
15-3/4" (400mm)
From Top Opening of Unit
C
Close to Ceiling
Flue Clearances
Horizontal - Top
2-1/2"
Horiztonal - Side
1-1/2"
Horiztonal - Bottom
1-1/2"
Vertical (Flex Vent)
1-1/2"
Vertical (Rigid)
1-1/4"