City Series CB72EPV
|
53
installation
Chase Venting
CHASE VENTING
A minimum 288in
2
opening in the enclosure is required to maintain safe operating temperatures.
This can be achieved in a number of ways including the examples shown below.
Warning: DO NOT cover or place objects in front of the air outlet(s).
Regency Chase Vent
Dimensions: 4”x72” (288in
2
)
Custom chase vent
Example dimensions: 2.5”x116” (290in
2
)
Reveal at the chase top
Example dimensions: 2”x160” (320in
2
)
Venting into an adjacent room
Minimum 288in
2
Note: An adjacent room cannot be a garage/closed in carport.
Note: The enclosure opening cannot be any lower than 0-2" from the top of the enclosure for all installations.
Minimum height of enclosure from base of appliance is 87".