City Series CB72EPV
installation
Framing Dimensions Corner Kit - Corner Install (Left Corner)
NOTE:
Framing may be constructed of combustible material (ie. 2 x 4)and does not require steel studs.
Note: A combined minimum of
120 square inches of open area
is required for the convection air
outlet to cool the enclosure. En-
sure clearances for Convection Air
Outlets are met.
See clearances CB72EPV in this
manual as there are different meth-
ods as to how this can be achieved.
NOTE: Unit cannot be load-bearing. All finishing materials must be supported by the framing.
Note: This appliance must be in-
stalled on a level and solid surface
such as a plywood floor which must
be the full width and depth of the
appliance.
Maximum material di-
mensions 2" x 4" for
header studs (installed
on edge and flat)
Framing
Dimensions
Description
Corner Kit
A
Framing Height
51” (1295mm)
B
Framing Width
84" (2134mm)
C
Framing Depth
20-5/8" (524mm)
D
Unit Base to Top Enclosure (Min.)
87"(2210mm)
G
Vent Centerline Height
55-1/4" (1403mm)