12
SP 1-Ex
•
..failure of feedback position transmitter
Statistic data:
(using RS 232 and personal computer)
•
..number of controller operation hours
•
..frequency of relay switching in direction "opening"
•
..frequency of relay switching in direction "closing"
Supply voltage:
.............. terminal 61 (L1) -1(N) ............... 230, 24 V AC, ±10%
Frequency:
..................... 50/60 Hz ±2%
Input control signals - analogue:
.................................................................................... 0 - 20 mA
..................................................................................................................................... 4 - 20 mA
........................................................................................................................................ 0 - 10 V
Input resistance for signal 0/4 - 20 mA ...................................................................................... 250
Ω
Input resistance for signal 0/2 - 10 V ......................................................................................... 50k
Ω
(Actuator opens at rising of control signal.)
Controller linearity:
............................... 0.5 %
Controller insensitiveness:
.................. 1 - 10% (adjustable)
Feedback (position transmitter):
......... resistive 100 up to 10,000
Ω
current 4 up to 20 mA
Power outputs:
......... 2x relay 5A/250 V AC
Digital outputs:
........4x LED (supply, error, adjustment, "opening", "closing" - with two-colour LED)
Error status:
.............................control switch 24 V, 2W - POR
Reaction at error situation:
.....transmitter error - error message LED
Control signal missing:
...........error message LED
SYS mode:
................................error message LED
Adjusters:
.................................communication connector
2x calibrating and adjusting button
Manual control:
with hand wheel; rotating clockwisely (counterclockwisely) EA output part is
moving in direction "Z" - closed ("O" - open)
Mechanical connection:
Basic and connecting dimensions are given in dimensional drawings.
Electric connection
with terminal board
(
X
)
:
- max. 12 terminals – connecting cable size
0,5 - 2,5
mm
2
- 2 cable bushings – cable diameter from 9 to 13 mm
with protection terminal:
- external and internal, mutually connected and marked with protection
earthling mark.
Electric connection - according to
wiring diagrams.
Содержание SP 1-Ex
Страница 28: ...26 SP 1 Ex 7 Enclosures 7 1 Wiring diagrams Wiring diagrams EA SP 1 Ex...
Страница 29: ...SP 1 Ex 27 Wiring diagrams EA SP 1 Ex with controller ERROR MESSAGE ERROR MESSAGE...
Страница 30: ...28 SP 1 Ex...
Страница 33: ...SP 1 Ex 31 7 2 Dimensional drawings 7 2 1 Dimensional drawings flange connection Flange...
Страница 35: ...SP 1 Ex 33 Coupling shape Pull rod TV360...