SP 1-Ex 

1.11  Packing, transport, storing and unpacking 

 

Surfaces  without  surface  treatment  are  treated  by  conservation   preparation  MOGUL  LV  2-3 

before packaging . 
Conservation is not necessary if the following storage conditions are complied with: 
• Storage temperature: -10 to +50 °C 
• Relative air humidity max.80 % 
•  Electric  actuators  and  their  accessories  must  be  stored  in  dry,  well  ventilated  covered  spaces, 
protected against impurities, dust, soil humidity (by placement to racks, or on palettes), chemicals and 
foreign interventions 
• There shall be no corrosive gases present in the storage areas. 

 

The of EA are delivered in solid packages guaranteeing resistance in accordance with 

EN/IEC 60  654. 
Package is a box. Products in boxes is possible to load on the pallets (pallet is returnable). On the 
outer side of the package is stated: 

  manufacturer label, 

  name and type of product, 

  number of pieces, 

  other data – notices and stickers. 

 

The  forwarder  is  obliged  to  secure  packed  products,  loaded  on  transportation  means,  against 

self-motion;  if  open  transportation  means  are  used,  to  secure  their  protection  against  atmospheric 
precipitations  and  splashing  water.  Displacement  and  securing  of  products  in  transportation  means 
must provide their stable position, exclude the possibility of  their inter-collision and their collision with 
the vehicle walls. 
Transportation can be executed by heatless and  non hermetic spaces of transportation vehicles with 
influences within the range:  
 

   

- temperature: -25

°

C up to +70

°

C (a strange version –50 ° C up to +45 ° C) 

                 

- humidity: 5 up to 100 %, with max. water content 0.029 kg/kg of dry air 

                

- barometric pressure 86 up to 108 kPa 

 

After  receiving  EA  check  whether  during  transport  or  storage  the  actuator  was  not 

damaged.  Compare  also  whether  the  parameters  on  their  nameplates  are  in  accordance  with 
accompanying  documentation  or  the  Contract.  If  any  discrepancy  or  fault  occur  inform 
immediately your supplier. 

 

If  the  actuators  and  accessories  are  not  immediately  installed,  they  have  to  be  stored  in  dry, 

well-ventilated sheltered rooms, protected against dirt, dust, soil humidity (with placing onto shelves or 
onto pallets), chemical impacts and encroachment, at ambient temperature from -10°C up to +50 °C 
and relative humidity max. 80 %, in special version at temperature –50°C do +40°C. 
 

  It is forbidden to store EA outside or in areas not prevented against direct impact of climate. 

  Strains  of  the  surface  finishing  should  be  promptly  removed  if  any  –  it  can  prevent  the  product 

against corrosion damages. 

  While  storing  more  than  one  year  it  is  necessary  to  check  lubrication filling  before  the  actuator  is 

put into operation. 

  The EA installed but not operated are to be protected the same way as when storing (e.g. with a 

wrapping). 

  After it is mounted onto a valve in free and wet areas or in areas where temperature is changing it 

is necessary to connect the space heater – to prevent the actuator against corrosion resulted from 
water condensed in the control part. 

  Remove odd conservation grease as late as before putting into operation.  

 

1.12  Assessment of the product and packaging and removal of contamination 

 

The  product  and  its  package  are  made  of  recycling materials.  Do  not throw  the  single  parts  of 

the package and of the product after their life but sort them according to instructions in corresponding 
executives or regulations of environment protection, and allow their recycling.  
 

The product and its packing are not a source of any environment pollution or contamination and 

do not contain any dangerous waste. 

Содержание SP 1-Ex

Страница 1: ...74 0720 02 74 0720 02 INSTALLATION SERVICE AND MAINTENANCE INSTRUCTIONS Explosion proof electric part turn actuators SP 1 Ex 1026...

Страница 2: ...73 X Design and type tests are in accordance with the following standards EN 60 079 0 Electrical apparatus for explosive gas atmospheres Part 0 General requirement EN 60 079 1 Electrical apparatus for...

Страница 3: ...it 16 4 2 Adjustment of position indicating unit Fig 3 16 4 3 Adjustment of resistant transmitter Fig 4 17 4 4 Adjustment of the Electronic Position Transmitter EPV the Resistive Transmitter Potentiom...

Страница 4: ...overvoltage category In order to demonstrate the compliance with the requirements of the European Council directive on machinery 2006 42 EC European Parliament and Council Directive 2014 34 E on equip...

Страница 5: ...IEC 60 079 7 tb identification of dust ignition protection by enclosure t according to EN IEC 60 079 31 II or III identification of the class of non explosive electric device according to the standar...

Страница 6: ...fety e type of protection applied to electrical apparatus in which additional measures are applied so as to give increased security against the possibility of excessive temperatures and of the occurre...

Страница 7: ...ature transmitting through junction component 5 Cable glands blinds are assigned only for transport and storage period i e for period till the actuator is builded into operation with danger of explosi...

Страница 8: ...on protected from direct climatic effects such as direct sunlight Installation and operation of EA is possible in any position Vertical position of output part axis and with the control part above the...

Страница 9: ...ration amplitude 19 6 m s 2 for f fp transition frequency fp is from 57 up to 62 Hz AH 2 medium impacts shocks and vibrations AG 2 with serious danger of plants and mould growing AK 2 with serious dan...

Страница 10: ...hether during transport or storage the actuator was not damaged Compare also whether the parameters on their nameplates are in accordance with accompanying documentation or the Contract If any discrep...

Страница 11: ...and max load torque Nm closing time s 90 operation stroke and electric motor parameters are given in Table 1 Table 1 Basic specifications Electric motor 3 Type number Operating speed 10 1 Operating st...

Страница 12: ...C 4K Position transmitters Resistive position transmitter Resistance single B1 100 2 000 Operating life of transmitter 1 106 cycles Load capacity 0 5 W do 40 C 0 W 25 C Maximum current load 100 mA Max...

Страница 13: ...Z 0 mA or 4 mA clamps 81 82 Values tolerance of output signal of EPV and capacitive transmitter Z 0 2 mA O 0 1 mA EPV and capacitive transmitter linearity error 1 5 1 EPV and capacitive transmitter h...

Страница 14: ...relay 5A 250 V AC Digital outputs 4x LED supply error adjustment opening closing with two colour LED Error status control switch 24 V 2W POR Reaction at error situation transmitter error error message...

Страница 15: ...lange clings to the valve gearing Fix the flange with four screws with mechanical ruggedness min 8G tightened to allow moving of EA Then the fixing screws tighten uniformly crosswisely 3 1 2 Mechanica...

Страница 16: ...d N connect to the corresponding terminals In case of the three phase version connect the phase cables L1 L2 and L3 to U V W terminals 2 3 4 the protection cables to the marked places of internal and...

Страница 17: ...transmitter and the sense of turning puts the EA to the positions open and closed measures inertia mass in the directions opening and closing and loads the adjusted parameters into the EEPROM memory...

Страница 18: ...re in the production plant adjusted to a fixed angle according to the specification given on the nameplate While setting adjusting and resetting follow these steps Fig 3 In the version with a transmit...

Страница 19: ...smitters is according to the customer s specification To adjust the transmitter follow these steps Loosen the fixing screws 9 of the transmitter holder and push the transmitter out of mesh Connect a m...

Страница 20: ...h limit positions and repeat the procedure if needed Note The output signal of 4 20mA can be adjusted at the range from 75 up to 100 of the rated stroke stated on the actuator s nameplate At values le...

Страница 21: ...tric actuators SP 1 Ex with controllers Note In case that reversed output signals are needed in the position OPEN minimum output signal contact personnel of service centres The capacitive transmitter...

Страница 22: ...er of precision class 0 5 and loading resistance lower than 500 on the terminals 81 82 Follow the procedure described in the previous chapter A C Adjustment of the Capacitive Transmitter Served as a F...

Страница 23: ...s they function as limit switches in case of position unit switching off failure or as protection against overload The procedure is as follows Loosen the counter nut of the stop end screw Z Rotate the...

Страница 24: ...blink control signal 3 blinks 0 10V DC 1 blink EA opens receiving signal SYS 2 blinks EA closes receiving signal SYS 2 blinks response for signal SYS TEST 3 blinks EA stops receiving signal SYS 1 bli...

Страница 25: ...ontroller with the D4 diode reports about the type of the error Else after finishing the initialisation process the controller is put into the regulation mode Error messages of the controller with D4...

Страница 26: ...Changing or filling grease up during first years operation is not required To refill or to replenish the grease is needed during revisions Intervals between two prevention inspections are four years G...

Страница 27: ...ion shaft 5 Fig 10 5 4 Troubleshooting At failure of power supply the EA stops in the position where it was before the failure If needed the EA can be set only with the manual control the hand wheel A...

Страница 28: ...26 SP 1 Ex 7 Enclosures 7 1 Wiring diagrams Wiring diagrams EA SP 1 Ex...

Страница 29: ...SP 1 Ex 27 Wiring diagrams EA SP 1 Ex with controller ERROR MESSAGE ERROR MESSAGE...

Страница 30: ...28 SP 1 Ex...

Страница 31: ...m of switches S1 S4 B1 single resistant transmitter B2 double resistant transmitter B3 capacitive transmitter or EPV E1 space heater F1 electric motor thermal protection F2 space heater thermal switch...

Страница 32: ...Z398 must be specified in the order by words If it is not stated wiring diagram will be realized according to the scheme Z395 8 Terminal 20 22 24 and 26 are not moved in the scheme Z519d Z249a and Z5...

Страница 33: ...SP 1 Ex 31 7 2 Dimensional drawings 7 2 1 Dimensional drawings flange connection Flange...

Страница 34: ...Shape L xx Shape H xx Shape V xx Flange dimension D xx U L xx U H xx U V V xx W Z X D 14 14 L 14 14 H 14 14 22 V 20 20 0 22 5 6 0 D 17 17 L 17 17 H 11 11 16 V 17 17 0 19 5 6 0 D 16 16 L 16 16 H 8 8 1...

Страница 35: ...SP 1 Ex 33 Coupling shape Pull rod TV360...

Страница 36: ...r o Strojn cka 7 080 01 Pre ov Tel 421 0 51 7480 460 Fax 421 0 51 7732 096 E mail regada regada sk Czech Republic Exclusive representation Regada s r o Ltd for sale of electric actuators Regada esk s...

Отзывы: