SP 1-Ex
23
Controller setting procedure:
Set the actuator into a mid-position.
The initialisation routine starts at the switched-on controller, zero system deviation and short
pressing of the SW1 button for ca 2 sec (i.e. until the diode D3 got on). Loosing the button some of the
default menus starts (usually control signal) what is shown with 1 blink on the D3 diode as well as one
of the default parameters (usually control signal of 4-20mA) what is shown with 1 blink on the D4
diode. Then the required parameters of the controller can be changed according to Table 2:
•
press shortly the SW1 button to list the menu shown with the blinking number on the D4 diode.
•
press shortly the SW2 button to set parameters shown with the blinking number on the D4 diode.
After changing of the parameters according to user's wishes, put the controller to autocalibration
with pressing the SW1 button for ca 2 sec (i.e. until the diode D3 got on). During this process the
controller performs the feedback transmitter and turning sense checking, sets actuator to the positions
"open" and "closed", measures inertia mass in the directions "opening" and "closing", and loads the
adjusted parameters into the EEPROM memory. In case that during the initialisation process an error
occurs (e.g. in connection or adjustment) the initialisation process will be interrupted and the
controller with the D4 diode reports about the type of the error. Else after finishing the initialisation
process the controller is put into the regulation mode.
Error messages of the controller with D4 diode at initialisation:
4 blinks .......improper connection of the torque switches
5 blinks .......improper connection of the feedback transmitter
8 blinks .......bad sense of actuator's turning direction or adverse connection of the feedback
transmitter
4.7.2 Watching operation and error states
Watching operation and error states is possible with the EA open.
a.)
Operation status with the D3 LED diode indicating
:
•
it is continuously lighting - the controller regulates
•
it is continuously not lighting - system deviation in the insensitiveness range - the EA has stopped
b.)
Error state with the D4 and D3 LED diodes indicating - D4 continuously lighting,
D3 indicates error state with blinking
1 blink (repeated):
- indication of the "TEST" mode - the EA is put to the position
according to the signal in the "TEST" menu (at connecting the 66
and 86/87 terminals)
2 blinks (repeating after short pause): - missing of control signal - the EA is put to the position according to
the signal in the "TEST" menu
4 blinks (repeating after short pause): - thrust switches activity indication (the EA switched-off with the
thrust switches in a mid-position)
5 blinks (repeating after short pause): - failure of the feedback transmitter - the EA is put to the position
according to the signal in the "TEST" menu
7 blinks (repeating after short pause): - control signal (current at range 4-20mA less than 4mA (3.5mA)
Содержание SP 1-Ex
Страница 28: ...26 SP 1 Ex 7 Enclosures 7 1 Wiring diagrams Wiring diagrams EA SP 1 Ex...
Страница 29: ...SP 1 Ex 27 Wiring diagrams EA SP 1 Ex with controller ERROR MESSAGE ERROR MESSAGE...
Страница 30: ...28 SP 1 Ex...
Страница 33: ...SP 1 Ex 31 7 2 Dimensional drawings 7 2 1 Dimensional drawings flange connection Flange...
Страница 35: ...SP 1 Ex 33 Coupling shape Pull rod TV360...