42
ULR 1PA-Ex, ULR 2PA-Ex
UN....................voltage for EPV
READY.............READY relay (free-programmable)
R1 to RE5 ........additional relays
TORQUE..........thrust scanning
DMS3 ...............electronic module
X.......................voltage supply source terminal board with screw terminals
X1.....................terminal board with screw terminals on the control unit
X2.....................screw terminal box on the additional relays board
X3.....................screw terminal of supply 3-phase motor
Terminals:
PE, N, L - terminals (0,05-1,5 mm
2
) of supply (24 V AC resp. 110/120 V AC, resp. 220/230 V AC, 50/60 Hz
(according to the specification – voltage and frequency are stated on nameplate of EA)
2, 3, 4 – terminals (0,08-2,5 mm
2
) of supply 3-phase motor 3x400 resp. 3x380 V AC
5,6 - terminals (0,08-2,5 mm2 ) wired 3-phase motor/s thermal protection
OP, CL - terminals (0,08 - 2,5 mm
2
) of the outputs of the direction rotations of the EA (220/230 V AC)
0 V, +24 V – terminals (max. 1,5 mm
2
) of output voltage 24 V DC (40 mA)
COM, CLOSE OPEN, I1, I2 – terminals (0,05 - 1 mm2) of control inputs 24 V /DC
+IN, -IN, SH – terminals (0,05 - 1 mm2) of analogue input signal /4/12 up to 20 mA, resp.4 up to 12 mA
+L, -L, SH – terminals (0,05 - 1 mm
2
) of output current signal (passive) 4-20 mA
COM, NO, NC – terminals (0,05 – 1,5 mm
2
) relay READY resp. relay RE5
COM, NO – terminals (0,05 – 1,5 mm
2
) relay R1, R2
COM 1, RE3, RE4 - terminals (0,05 – 1,5 mm
2
) of relay RE3, RE4
COM5, NO5, NC5 – terminals (0,05 – 1,5 mm
2
) relay RE5 (on the module of the additional relays)
Note 1: On terminal N, L terminal power supply (X) feed supply voltage 230 V AC, or 24 V AC by you - specified
type of construction EA. For supply voltage 24 V AC no need connect ground wire PE. For a version of EA with
the supply voltage 3x400 or 3x380V, terminals N, L on terminal board of power supply (X) are fed by power
supply 220 respectively 230 V AC.
Note 2: Three-phase electric motor in the electric actuators ULR 1PA-Ex do not have thermal protection of the
electromotor F1 wired to terminals 5 and 6 (thermal protection of the electric motor is inbuilt).
Thermal protection wired to the terminals 5 and 6 is offered only for 3-phase electric motor of the electric
actuators ULR 2PA-Ex.
Note 3: Program possibilities for
R1, R2, RE3, RE4, RE5
relays: DISABLED, open position, close position,
torque-open, torque – close, torque open or torque close, torque open or position open, torque close or position
close, open, close, movement, movement flasher, to position, from position, warning, remote control, local
control, control shut off.
Program possibilities for
READY
relay: errors, errors or warnings, errors or no remote, errors or warnings or no
remote.
Program possibilities for output signal (from
EPV
passive): 4 to 20 mA, 20 to 4 mA.
Control programme options (regulating): 2P, 3P, 3P/2P switched over to I2
Program possibilities
for input control signal (N)
: 4 to 20 mA (2 to 10 V), 20 to 4 mA (10 to 2 V), 0 to 20 mA (0
to 10 V), 20 to 0 mA (10 to 0 V).
Program possibilities for
inputs I1
: DISABLED, ESD, DBL (local releasing, remote releasing - not valid for EA
without local control), STOP.
Program possibilities for
inputs I2
: DISABLED, ESD, DBL (local releasing, remote releasing), STOP
2P (when controller is switch on)(for control programme option 3P/2P I2)) allows control using the binary 24V DC
inputs with I2 input activated.
Program possibilities of
FAILURE REACTION
: OPEN, CLOSE, STOP, SAFE POSITION.
The identical functions cannot be set on I1 &I2 inputs in addition to the disabled state (e.g., if the ESD function is
set on I1 input, it is not possible to select the (ESD) function on I2 input at the same time.
Содержание REMATIC ULR 1PA-Ex
Страница 13: ...ULR 1PA Ex ULR 2PA Ex 11 Fig 1 2 1 7 6 5 4 8 3...
Страница 14: ...12 ULR 1PA Ex ULR 2PA Ex Fig 1A 8 2 4 6 5 5 3 7 1...
Страница 38: ...36 ULR 1PA Ex ULR 2PA Ex 7 Enclosures 7 1 Wiring diagrams ULR 1PA Ex and ULR 2PA Ex...
Страница 39: ...ULR 1PA Ex ULR 2PA Ex 37...
Страница 40: ...38 ULR 1PA Ex ULR 2PA Ex...
Страница 41: ...ULR 1PA Ex ULR 2PA Ex 39...
Страница 42: ...40 ULR 1PA Ex ULR 2PA Ex...
Страница 45: ...ULR 1PA Ex ULR 2PA Ex 43 7 2 Dimensional drawings Explosion proof electric linear actuator Rematic ULR 1PA Ex...
Страница 46: ...44 ULR 1PA Ex ULR 2PA Ex...
Страница 47: ...ULR 1PA Ex ULR 2PA Ex 45...
Страница 48: ...46 ULR 1PA Ex ULR 2PA Ex Explosion proof electric linear actuator Rematic ULR 2PA Ex...