ULR 1PA-Ex, ULR 2PA-Ex
4.2
Procedure for setting individual parameters and the register of errors and
warnings
- is given in the separate attachment 74 1053 02 resp. 74 1076 02 of these operating instructions.
The factory default setting of individual programmes shown in Table 3 and Table 4, as long as otherwise
specified by the customer:
Table 3
Factory default settings of individual parameters in version without local control; possibility to set-up
by operating the control unite buttons.
For the individual parameters set-up see appendix
74 1053 02
MENU
NAME
FACTORY SETTING-UP
1
TORQUE
100% of value shown on nameplate for OPEN & CLOSE direction.
2
END LIMIT
- C = Po O = Position
- end position switching closed and
open from position
if valve type is not specified
- C = O = Position
- closed in end by thrust position
and end position switching open from position for single-seat
valves
- C = O = Torque
– switching in both end positions by
thrust for double-seat valves
3
TORQUE BLOCKING
- 2 sec. blocking time
- 5% blocking position for OPEN & CLOSE direction
4
RELAY READY
- errors (READY COM-NO relay contacts closed in error free
conditions)
5
RELAY 1...RE5
- position O for relay R1
- position C for relay R2
- from position 95% for relay RE3
- from position 5% for relay RE4
- disabled for RE5 relay
6
CPT (output signal)
4 to 20 mA
REGULATION – (according to
specification)
2P
3P
7
ANALOG INPUT
-
4 to 20 mA (2 to 10 V)
8
DEAD ZONE
-
3 %
9
FAILURE REACTION
STOP
Other parameters set-up is possible to change only by using the PC software
TITLE
FACTORY SETTING-UP
DIRECTION OF ROTATION
clockwise
THERMOSTAT TEMPERATURE
25 °(space heater OFF temperature)
INTERNAL DEAD ZONE
2 % (only for 3P)
Safe position
0 %
FUNCTION I1
ESD
ACTIVE I1
high level
FUNCTION I2
DISABLED
ACTIVE I2
high level
THERMAL FUSE FAILURE
functionless with this EA type
THERMAL FUSE RESET
functionless with this EA type
CYCLE MODE
DISABLED
CYCLE RUNNING TIME
10 s
CYCLE PAUSE
50 s
CYCLE POSITION O1
0 %
CYCLE POSITION O2
100 %
CYCLE POSITION C1
0 %
CYCLE POSITION C2
100 %
O AND C TOLERANCE
1 %
CREATE BACKUP
START
RESTORE FROM BACKUP
START
RESTORE FACTORY SETUP
START
ACTIVE ERRORS
CLEAR
Содержание REMATIC ULR 1PA-Ex
Страница 13: ...ULR 1PA Ex ULR 2PA Ex 11 Fig 1 2 1 7 6 5 4 8 3...
Страница 14: ...12 ULR 1PA Ex ULR 2PA Ex Fig 1A 8 2 4 6 5 5 3 7 1...
Страница 38: ...36 ULR 1PA Ex ULR 2PA Ex 7 Enclosures 7 1 Wiring diagrams ULR 1PA Ex and ULR 2PA Ex...
Страница 39: ...ULR 1PA Ex ULR 2PA Ex 37...
Страница 40: ...38 ULR 1PA Ex ULR 2PA Ex...
Страница 41: ...ULR 1PA Ex ULR 2PA Ex 39...
Страница 42: ...40 ULR 1PA Ex ULR 2PA Ex...
Страница 45: ...ULR 1PA Ex ULR 2PA Ex 43 7 2 Dimensional drawings Explosion proof electric linear actuator Rematic ULR 1PA Ex...
Страница 46: ...44 ULR 1PA Ex ULR 2PA Ex...
Страница 47: ...ULR 1PA Ex ULR 2PA Ex 45...
Страница 48: ...46 ULR 1PA Ex ULR 2PA Ex Explosion proof electric linear actuator Rematic ULR 2PA Ex...