ULR 1PA-Ex, ULR 2PA-Ex
25
3P CONTROL (REGULATING)
Setting-up: 3P c other functions, in addition to STOP on I1 and other ones in addition to 2P on I2 input.
The EA moves either to the OPEN or CLOSE direction with
0/4/12 to 20 mA, 4 to 12 mA (0/2 to 10 V)
input control signal
supplied on terminals
+IN, -IN.
The EA stops once the required position is reached
(corresponding with the input control signal supplied) or the set end position is reached.
Note: The ES fails to stop in case that the STOP function is selected on I1 input with 3P control mode and
24V DC voltage supplied on I1 terminal.
3P/2P switched over to I2
Setting-up:
3P/2P
control switched over to
I2
(
2P
function is automatically selected for
I2
input function in
selecting this control option) + other functions in addition to STOP on I1:
The EA moves either to the OPEN or CLOSE direction with signal
0/4/12 to 20 mA, 4 to 12 mA
(0/2 to
10 V)
input control signal
supplied on terminals
+IN, -IN.
The EA stops once the required position is
reached (corresponding with the input control signal supplied) or the set end position is reached.
The EA stops to respond to signal
0/4/12 to 20 mA, 4 to 12 mA
(0/2 to 10 V
) input control signal and rests
in case of
I2 active input
(with 24V DC constantly ON or OFF – as per I2 function set-up to ACTIVE – or
supplied on I2 connector). The EA is allowed to move either to the
OPEN
or
CLOSE
direction with
24V DC
voltage
supplied to terminals
OPEN
or
CLOSE.
The EA stops if power supply is cut-off or the end position
is reached.
The EA stops to respond to the input control signal and fixes its position once the supply
voltage on I2 is OFF.
3P/2P switched over to I2 (PULSE 2P)
Setting-up:
3P/2P control switched over to I2
(
2P
function is automatically selected for
I2
input function in
selecting this control option) + other functions in addition to
STOP
on
I1
:
The EA moves either to the OPEN or CLOSE direction with
input control signal
0/4/12 to 20 mA,
4 to 12 mA (0/2 to 10 V)
supplied on connectors
+IN, -IN.
The EA stops once the required position is
reached (corresponding with the input control signal supplied) or the set end position is reached.
The EA stops to respond to
0/4/12 to 20 mA, 4 to 12 mA (0/2 to 10 V)
input control signal and rests in
case of
I2 active input
(with 24V DC constantly ON or OFF – as per I2 function set-up to ACTIVE – or
supplied on I2 terminal). The EA is allowed to move either to the OPEN or CLOSE direction with
24 V DC
voltage pulse supplied connectors
OPEN
or
CLOSE
. The EA stops once the 24V DC voltage is supplied on
I1 terminal (STOP) or the set end position is reached.
The EA stops to respond to the input control signal and fixes its position once the supply voltage on I2 is
OFF.
Содержание REMATIC ULR 1PA-Ex
Страница 13: ...ULR 1PA Ex ULR 2PA Ex 11 Fig 1 2 1 7 6 5 4 8 3...
Страница 14: ...12 ULR 1PA Ex ULR 2PA Ex Fig 1A 8 2 4 6 5 5 3 7 1...
Страница 38: ...36 ULR 1PA Ex ULR 2PA Ex 7 Enclosures 7 1 Wiring diagrams ULR 1PA Ex and ULR 2PA Ex...
Страница 39: ...ULR 1PA Ex ULR 2PA Ex 37...
Страница 40: ...38 ULR 1PA Ex ULR 2PA Ex...
Страница 41: ...ULR 1PA Ex ULR 2PA Ex 39...
Страница 42: ...40 ULR 1PA Ex ULR 2PA Ex...
Страница 45: ...ULR 1PA Ex ULR 2PA Ex 43 7 2 Dimensional drawings Explosion proof electric linear actuator Rematic ULR 1PA Ex...
Страница 46: ...44 ULR 1PA Ex ULR 2PA Ex...
Страница 47: ...ULR 1PA Ex ULR 2PA Ex 45...
Страница 48: ...46 ULR 1PA Ex ULR 2PA Ex Explosion proof electric linear actuator Rematic ULR 2PA Ex...