Commissioning 

 

 

 

Vacuum spray degassing 

 18.12.2019 

 Rev. A 

 

English  

 13 

 

3. 

Fill the vacuum spray pipe with water. 

 

Air escapes via the degassing valve (2) and the water pressure can be 

read at the vacuum gauge (1). 

 

 

 

Vent the pump: 
4. 

Turn the venting screw (1) until air or a water/air mixture escapes. 

5. 

If required, use a screwdriver to rotate the pump at the fan wheel of the 

pump motor.  

 CAUTION 

 Risk of injury due to pump start-up! Hand injury due to a 

pump start-up. Switch the pump to a zero-volts state before turning the 

pump motor at the fan wheel with a screwdriver.  

 

CAUTION 

 Device damage. Pump damage due to a pump start-up. Switch 

the pump to a zero-volts state before turning the pump motor at the fan 

wheel with a screwdriver. 

 

Water/air mixtures are removed from the pump. 

6. 

Re-tighten the venting screw when only water escapes. 

7. 

Close the feed and drain cock. 

 

Filling and venting is concluded. 

 



Note! 
The "PU" pump must not be switched on when the Servitec is filled with 

water. 

 



Note! 
Do not fully unscrew the venting screw. Wait until air-free water 

appears. Repeat the venting process until the "PU" pump is fully vented. 

 

7.6

 

Vacuum test 

Perform the vacuum test to ensure the proper functioning of the Servitec. 

 

 

 

Close the ball valve (1) with the dirt trap of the "DC" feed line to the spray 

pipe. The second ball valve (2) in the feed line from the "DC" pump to the 

system remains open. 

Generate a vacuum with the manual mode of the controller. 

 

Press "Manual" on the controller's operator panel. 

 

Use the "Back" toggle button to select "SE" system degassing at the 

operator panel. 

 

The pump will start after a time delay of 50 seconds. 

Use the "Back" toggle button to switch off "SE" system degassing after the 

pump runs for 10 seconds. 

 

Note the vacuum indicated on the vacuum gauge. 

 

 

 

Observe the "PI" vacuum gauge (1) for approximately 10 minutes. The 

pressure must not change. If the pressure has increased, check the Servitec 

for leaks. 

 

Check all screw fittings at the "VT" vacuum spray tube for leaks. 

 

Check the vent screw at the "PU" pump for leaks. 

 

Check the "DV" degassing valve at the "VT" vacuum spray tube for 

leaks. 

 



Note! 
Repeat steps 2 to 4 until no further pressure rise is observed. 

 

After a successful vacuum test, open the ball valve with dirt trap. 

If the controller displays the "Insufficient water" error message, confirm 

with "Quit". 

  The vacuum test is completed. 

 



Note! 
The obtainable vacuum corresponds to the saturation pressure at the 

existing water temperature. 

 

At 10 °C, a vacuum of approximately -1 bar can be obtained. 

 

7.7

 

Use the device to fill the facility system with water 

In systems with a water volume less than 3000 litres and a pressure maintenance 

with diaphragm-type expansion vessels, the Servitec may be used for filling 

using degassed water. Thus, the oxygen content and the content of free gases is 
reduced for commissioning. 
Set the controller to the following operating modes: 

 

"Magcontrol" automatic make-up, see chapter 8.2.1 "Customer menu" on 

page 16 

 

Manual operation, see chapter 8.1.2 "Manual mode" on page 16 . 

   "NE" make-up degassing mode. 

The controller calculates the required filling pressure. As soon as this value has 
been attained, the controller automatically stops the filling process. If the 

maximum filling time (10 hours by default) is exceeded, the system aborts the 

make-up process with an error message. After the cause has been found, 

acknowledge the error message by pressing "Quit" at the controller's operating 

panel and continue with the filling process, see chapter 8.2.4 "Messages" on 
page 17 . After filling is completed, you must vent the system to ensure proper 

circulation through the entire system. 

 



Note! 
Monitor the system for the entire automatic filling process. 

 



Note! 
Filling the system with water is not part of the deliverables of the Reflex 

Customer Service. 

 

7.8

 

P arametrising the controller in the Customer menu 

System-specific values can be corrected via the customer menu. In the course of 
initial commissioning, the factory settings must be adjusted for the system-

specific conditions. 

 



Note! 
For a description of the operation, see chapter 7.2 "Setting the minimum 

operating pressure for Magcontrol" on page 11 . 

 

All grey marked menu items must be reviewed during commissioning. 
 
Press "Manual" to switch to manual operation. 
Press "Menu" to display the first main menu option "Customer menu". 

 

Switch to the next main menu option. 

Customer menu 

 

 

Standard software in various languages. 

Language 

 

 

Adjust the "Hour", "Minute", and "Second" display 
when each begins to flash. 
This time is used for entries in the fault memory. 

Time: 

 

 

 

 

Содержание Servitec 35

Страница 1: ...Vacuum spray degassing 18 12 2019 Rev A Servitec 35 95 Control Basic controller GB Operating manual Original operating manual...

Страница 2: ...d commissioning certificate 11 7 Commissioning 11 7 1 Checking the requirements for commissioning 11 7 2 Setting the minimum operating pressure for Magcontrol 11 7 3 Controller 11 7 3 1 Operator panel...

Страница 3: ...perating manual DANGER Danger of death and or serious damage to health The sign in combination with the signal word Danger indicates imminent danger failure to observe the safety information will resu...

Страница 4: ...gassing and make up station Its main areas of application are heating and cooling circuits and systems in which malfunctions due to dissolved or free gases are to be prevented The Servitec provides th...

Страница 5: ...The pumpreturns degassed water from the vacuum spraytube to the system whereit again begins to dissolve gases There it is able to dissolvegases again Discharge The PU pumpshuts off The system continue...

Страница 6: ...softening systems The operational reliability of the device is assured and prevents automatic make up during major water loss or small leaks Fillset Compact for make up Fillset Compact with integrated...

Страница 7: ...t 6 2 Preparatory work Condition of the delivered device Check all screw fittings and electrical connections of the Servitec for proper seating Tighten the screws and fittings as necessary Preparing t...

Страница 8: ...ystem near the diaphragm type MAG expansion vessel This ensures that the pressure in the diaphragm type expansion vessel is monitored In this case select the Magcontrol operating mode in the controlle...

Страница 9: ...ed for facilities with pressurisation stations and enables flexible operation at constant pressure Demand matched water make up takesplace depending on the measured water level in the expansion vessel...

Страница 10: ...e device 20 Level signal 21 Level 18V 22 PE shield Pressure analogue input Pre wired 23 Pressure signal 24 Pressure 18 V 25 0 10 V correcting variable Ball control valve Pre wired 26 0 10 V feedback 2...

Страница 11: ...leaned of welding residue and dirt before commissioning The entire facility system is filled with water and all gases have been vented in order to ensure a circulation through the entire system The el...

Страница 12: ...trol make up variant 5 Enter the actuating pressure of the heat generator safety valve Safety valvepressure Indicated when selecting the Magcontrol make up variant 6 Enter the minimum operating pressu...

Страница 13: ...r a successful vacuum test open the ball valve with dirt trap 6 If the controller displays the Insufficient water error message confirm with Quit The vacuum test is completed Note The obtainable vacuu...

Страница 14: ...installed standard Only displayed if YES has been set in the With water meter menu option Make up quantity OK Delete meter yes Set the displayed make up quantity to 0 no The displayed water quantity i...

Страница 15: ...omatic make up The Servitec controller monitors the functions Faults are displayed and evaluated For automatic mode you can set three different degassing programmesin the Customer menu see chapter 8 2...

Страница 16: ...ting CAUTION Risk of injury dueto pumpstart up Hand injuries may occur when the pumpstarts up if you turn the pumpmotor at the impeller using a screwdriver Switch the pumpto a zero volts state before...

Страница 17: ...enu on page 16 ER Code Alarm Floating contact Cause Remedy Alarm reset 01 Minimum pressure Yes For Magcontrol setting only Set value not reached Water loss in the system Pumpfault Expansion vessel def...

Страница 18: ...ot achieved Check power supply 33 Adjustment parameter EPROM parameter memory defective Inform ReflexCustomer Service Quit 34 Main board communication faulty Connecting cable defective Main board defe...

Страница 19: ...the housing of the ST 1 dirt trap 6 Open the ball valve upstream of the ST 1 dirt trap 7 Press Auto on the controller s operator panel The Servitec is switched on and the PU pumpis in operation Note...

Страница 20: ...cooled down or wear protective safety gloves The operating authority is required to place appropriate warning signs in the vicinity of the device CAUTION Risk of injury dueto pressurised liquid If ins...

Страница 21: ......

Страница 22: ...SI2003enA 9127373 01 20 ReflexWinkelmann GmbH Gersteinstra e 19 59227 Ahlen Germany 49 0 2382 7069 0 49 0 2382 7069 9546 www reflex de...

Отзывы: