background image

Commissioning 

 

 

 

12 

  English  

Vacuum spray degassing 

 18.12.2019 

 Rev. A 

 

 

Error LED 

 

The Error LED illuminates in the event of a fault 

Display 

Auto LED 

 

The Auto LED illuminates green in Automatic mode 

 

The Auto LED flashes green in Manual mode  

 

The Auto LED is not illuminated when the system is stopped 

OK 

 

Confirm actions 

Stop 

 

For commissioning and entry of new values in the controller 

"Back" to the previous menu 

Manual 

 

For tests and maintenance tasks 

Auto 

 

For continuous operation 

"Forward" to the next menu 

10 

Menu 

 

Call up the Customer menu 

11 

Quit 

 

Acknowledge messages 

 
S electing and changing parameters 
1. 

Use "OK" (5) to select the parameter. 

2. 

Use the "

" (7) or "

" (9) arrow keys to change the parameter. 

3. 

Use "OK" (5) to confirm the parameter. 

4. 

Use the "

" (7) or "

" (9) arrow keys to switch to a different menu 

option. 

5. 

Use "Quit" (11) to switch to a different menu level. 

 

7.4

 

Mo difying the controller's start routine 

The start routine is used to set the required parameters for the Servitec 

commissioning. It commences with the first switching on of the controller and 

can only be set once. The following parameter changes or checks are carried out 

from the customer menu, see chapter 8.2.1 "Customer menu" on page 16 . 

 



Note! 

Plug in the contact plug to provide power (230 V) to the controller. 

 

You are in Stop mode. The "Auto" LED on the operator panel has extinguished. 

 

1. 

Software language selection. 

Language 

 

 

2. 

Prior to commissioning, read the 
operating manual in full and check for 

proper assembly. 

Read the operating 
manual! 

 

 

 

3. 

Enter the variant of your Servitec. 

Select the system. 

 

 

 

4. 

Select the desired make-up variant: 

M a gcontrol:  
Pressure-dependant make-up in a system with 

an expansion vessel. 
L evelcontrol:  
Level-dependent make-up in a system with a 

pressure maintenance station. 

Servitec 
Magcontrol 

 

 

 

 

Indicated when selecting the "Magcontrol" 
make-up variant: 
5. 

Enter the actuating pressure of the heat 
generator safety valve. 

Safety valve pressure 

 

 

 

 

Indicated when selecting the "Magcontrol" 
make-up variant: 
6. 

Enter the minimum operating pressure.  

For calculating the minimum operating 

pressure P0, see chapter 7.2 "Setting the 
minimum operating pressure for 

Magcontrol" on page 11 

Min. op. pressure 

 

 

 

 

7. 

Change the flashing display items for 
"Hour", "Minute", and "Seconds" to the 

current time. 

The time of an alarm will be stored in the fault 

memory. 

Time: 

 

 

 

 

8. 

Change the flashing display items for 
"Day", "Month", and "Year" to the current 

date. 

The date of an alarm will be stored in the fault 
memory. 

Date: 

 

 

 

 

9. 

Select in the message line and confirm 
with "OK": 

Terminate start routine?   

yes:  

The start routine is terminated. Servitec 

automatically switches to stop mode. 

 

 

no: 

The start routine restarts. 

 

 

 

The pressure is displayed only in "Magcontrol" 
mode. 

2.0 bar   

STOP 

 

 



Note! 
You are in Stop mode. Please do not switch from the start routine to 

Automatic mode after entering the parameters. 

 

7.5

 

Fi lling the device with water and venting 

 CAUTION 

 

Risk of injury due to pump start-up 

Hand injuries may occur when the pump starts up if you turn the pump motor at 
the impeller using a screwdriver. 

 

Switch the pump to a zero-volts state before turning the pump at the fan 

wheel with a screwdriver. 

 

ATTENTION 

 

Device damage due to pump start-up 
Pump damage may occur when the pump starts up if you turn the pump motor 

at the impeller using a screwdriver. 

 

Switch the pump to a zero-volts state before turning the pump at the fan 

wheel with a screwdriver. 

 

 

 

Vacuum gauge "PI" 

 

Pump "PU" 

Degassing valve "DV" 

 

WC 

Make-up pipe 

Feed and drain cock "FD" 

 

DC 

Degassing lines 

"AV" venting screw 

 

 

 

 

1. 

Use the facility system to fill the Servitec. 

 

After you have opened the "DC" ball valves, the vacuum spray tube 
will autonomously fill if the facility system provides sufficient water. 

2. 

Optional 

 

Use the feed and drain cock (3) to fill water into the Servitec.  

 

Connect a hose at the feed and drain cock (3) of the "VT" vacuum 

spray pipe. 

Содержание Servitec 35

Страница 1: ...Vacuum spray degassing 18 12 2019 Rev A Servitec 35 95 Control Basic controller GB Operating manual Original operating manual...

Страница 2: ...d commissioning certificate 11 7 Commissioning 11 7 1 Checking the requirements for commissioning 11 7 2 Setting the minimum operating pressure for Magcontrol 11 7 3 Controller 11 7 3 1 Operator panel...

Страница 3: ...perating manual DANGER Danger of death and or serious damage to health The sign in combination with the signal word Danger indicates imminent danger failure to observe the safety information will resu...

Страница 4: ...gassing and make up station Its main areas of application are heating and cooling circuits and systems in which malfunctions due to dissolved or free gases are to be prevented The Servitec provides th...

Страница 5: ...The pumpreturns degassed water from the vacuum spraytube to the system whereit again begins to dissolve gases There it is able to dissolvegases again Discharge The PU pumpshuts off The system continue...

Страница 6: ...softening systems The operational reliability of the device is assured and prevents automatic make up during major water loss or small leaks Fillset Compact for make up Fillset Compact with integrated...

Страница 7: ...t 6 2 Preparatory work Condition of the delivered device Check all screw fittings and electrical connections of the Servitec for proper seating Tighten the screws and fittings as necessary Preparing t...

Страница 8: ...ystem near the diaphragm type MAG expansion vessel This ensures that the pressure in the diaphragm type expansion vessel is monitored In this case select the Magcontrol operating mode in the controlle...

Страница 9: ...ed for facilities with pressurisation stations and enables flexible operation at constant pressure Demand matched water make up takesplace depending on the measured water level in the expansion vessel...

Страница 10: ...e device 20 Level signal 21 Level 18V 22 PE shield Pressure analogue input Pre wired 23 Pressure signal 24 Pressure 18 V 25 0 10 V correcting variable Ball control valve Pre wired 26 0 10 V feedback 2...

Страница 11: ...leaned of welding residue and dirt before commissioning The entire facility system is filled with water and all gases have been vented in order to ensure a circulation through the entire system The el...

Страница 12: ...trol make up variant 5 Enter the actuating pressure of the heat generator safety valve Safety valvepressure Indicated when selecting the Magcontrol make up variant 6 Enter the minimum operating pressu...

Страница 13: ...r a successful vacuum test open the ball valve with dirt trap 6 If the controller displays the Insufficient water error message confirm with Quit The vacuum test is completed Note The obtainable vacuu...

Страница 14: ...installed standard Only displayed if YES has been set in the With water meter menu option Make up quantity OK Delete meter yes Set the displayed make up quantity to 0 no The displayed water quantity i...

Страница 15: ...omatic make up The Servitec controller monitors the functions Faults are displayed and evaluated For automatic mode you can set three different degassing programmesin the Customer menu see chapter 8 2...

Страница 16: ...ting CAUTION Risk of injury dueto pumpstart up Hand injuries may occur when the pumpstarts up if you turn the pumpmotor at the impeller using a screwdriver Switch the pumpto a zero volts state before...

Страница 17: ...enu on page 16 ER Code Alarm Floating contact Cause Remedy Alarm reset 01 Minimum pressure Yes For Magcontrol setting only Set value not reached Water loss in the system Pumpfault Expansion vessel def...

Страница 18: ...ot achieved Check power supply 33 Adjustment parameter EPROM parameter memory defective Inform ReflexCustomer Service Quit 34 Main board communication faulty Connecting cable defective Main board defe...

Страница 19: ...the housing of the ST 1 dirt trap 6 Open the ball valve upstream of the ST 1 dirt trap 7 Press Auto on the controller s operator panel The Servitec is switched on and the PU pumpis in operation Note...

Страница 20: ...cooled down or wear protective safety gloves The operating authority is required to place appropriate warning signs in the vicinity of the device CAUTION Risk of injury dueto pressurised liquid If ins...

Страница 21: ......

Страница 22: ...SI2003enA 9127373 01 20 ReflexWinkelmann GmbH Gersteinstra e 19 59227 Ahlen Germany 49 0 2382 7069 0 49 0 2382 7069 9546 www reflex de...

Отзывы: