Reflex Servimat L Скачать руководство пользователя страница 22

Controller 

22 

  English  

Servimat M/L — 28.01.2021

ER Code 

Alarm 

Floating 

contact 

Causes 

Remedy 

Alarm reset 

08 

Pressure measurement 

YES 

 

Controller receives incorrect 
signal. 

 

Connect the plug.

 

Check functioning of the pressure
sensor. 

 

Check the cable for damage.

 

Check the pressure sensor.

"Quit" 

09 

Level sensor 

YES 

 

Controller receives incorrect 
signal. 

 

Check functioning of the load cell.

 

Check the cable for damage.

 

Connect the plug.

"Quit" 

10 

Maximum pressure 

 

Set value exceeded.

 

Pressure relief pipe not 
functioning. 

 

Dirt trap clogged.

 

Check set value in the Customer or 
Service menu. 

 

Check functioning of the pressure relief
pipe. 

 

Clean the dirt trap.

"Quit" 

11 

Make-up quantity 

"With water meter" must be activated 

in the Customer menu. 

 

Set value exceeded.

 

Severe water loss in the system.

 

Check set value in the Customer or 
Service menu. 

 

Check water loss in the system and
repair, if necessary. 

"Quit" 

14 

Discharge period 

 

Set value exceeded.

 

Degassing pipe closed.

 

Dirt trap clogged.

 

Check degassing line.

 

Check dirt trap.

15 

Make-up valve 

 

Contact water meter measures 
without make-up requirement.

 

Check the make-up valve for leaks.

"Quit" 

16 

Power failure 

 

No power.

 

Connect to power supply.

18 

Parameter 

 

Parameter settings incorrect.

 

Check settings, if necessary make basic 
settings in the service menu. 

19 

Stop 

˃

 4 hours 

 

Device is in Stop mode for more 
than 4 hours. 

 

Set the controller to Automatic mode.

20 

Max. Make-up volume 

 

Set value exceeded.

 

Reset the "Make-up quantity" meter in
the Customer menu. 

"Quit" 

21 

Maintenance recommended 

 

Set value exceeded.

 

Perform maintenance and reset the 
maintenance counter upon completion.

"Quit" 

24 

Replace cartridge 

 

Set value for soft water capacity
exceeded. 

 

Replace cartridges.

 

Set soft water capacity.

"Quit" 

25 

Datalogger 

 

No SD card inserted.

 

SD card write protected.

 

SD card not recognised.

 

Insert FAT16 or FAT32 formatted SD
card. 

 

Disable write-protection.

 

Check SD card.

30 

I/O module fault 

 

I/O module defective.

 

Connection between option card 
and controller faulty. 

 

Option card defective.

 

Inform Reflex Customer Service.

31 

EEPROM defective 

YES 

 

EEPROM defective.

 

Internal calculation error.

 

Inform Reflex Customer Service.

"Quit" 

32 

Undervoltage 

YES 

 

Supply voltage too low.

 

Check power supply.

33 

Adjustment parameter 
faulty 

YES 

 

EPROM parameter memory 
defective.

 

Inform Reflex Customer Service.

34 

Communication 
Main board faulty 

 

Connecting cable defective.

 

Main board defective.

 

Inform Reflex Customer Service.

35 

Digital input voltage faulty 

 

Short-circuit of input voltage.

 

Check the wiring at the digital inputs 
(water meter, for example). 

36 

Analogue input voltage faulty 

 

Short-circuit of input voltage.

 

Check the wiring at the analogue inputs 
(pressure/level). 

37 

No MKH 1 input voltage 

 

Short-circuit of input voltage.

 

Check wiring of the ball valve.

38 

No MKH 2 input voltage 

 

Short-circuit of input voltage.

 

Check wiring of the ball valve.

39 

Pressure jumper 

 

Jumper J1 on the main board set 
incorrectly. 

 

Change the jumper setting accordingly.

40 

Level jumper 

 

Jumper J1 on the main board set 
incorrectly. 

 

Change the jumper setting accordingly.

41 

Replace battery 

 

Buffer battery discharged.

 

Replace the battery in the operating 
unit (CPU). 

42 

Bus module 

 

Bus module activated but not 
present. 

 

Connecting cable defective.

 

Bus module defective.

 

Connect bus module.

 

Check connection cable.

 

Replace bus module.

Содержание Servimat L

Страница 1: ...Servimat M L 09 04 2019 Pressure maintenance with degassing GB Operating manual Original operating manual...

Страница 2: ...nstallation and commissioning certificate 13 7 Commissioning 13 7 1 Checking the requirements for commissioning 13 7 2 Determining the P0 minimum operating pressure for the controller 13 7 3 Filling t...

Страница 3: ...ice on page 25 3 Safety 3 1 Explanation of symbols The following symbols and signal words are used in this operating manual DANGER Danger of death and or serious damage to health The sign in combinati...

Страница 4: ...afety clothing gloves and goggles for example 4 Description of the device 4 1 Description The Servimat is a pump controlled pressure maintaining make up and degassing station for heating and cooling w...

Страница 5: ...water from the primary tank back into the system The pressure in the facility system rises The controller ensures that the pressure is maintained further supported by the stabilisation provided by th...

Страница 6: ...ontent is shown on the packing Immediately after receipt of the goods please check the shipment for completeness and damage Please notify us immediately of any transport damage Basic pressure maintena...

Страница 7: ...54 G1 1360 146 6 bar 400 740 65 G1 1345 133 Type D mm Weight kg Connection inches H mm h mm 6 bar 500 740 78 G1 1560 133 6 bar 600 740 94 G1 1810 133 6 bar 800 740 149 G1 2275 133 6 bar 1000 740 740...

Страница 8: ...ATTENTION Damage due to improper installation Additional device stresses may arise due to the connection of pipes or system equipment Ensure that pipes are connected from the device to the system wit...

Страница 9: ...tank Ensure that you connect the connection set for the overflow collector to the connection 2 below the label 1 Interchanging the connections may cause the pump to run dry For tanks up to 740 mm Con...

Страница 10: ...mal insulation when condensate forms 6 3 6 Fitting the level sensor ATTENTION Damage to the pressure load cell due to unprofessional installation Incorrect installation may result in damage to the LIS...

Страница 11: ...ain circuit board is voltage free 3 Insert a suitable screwed cable gland for the cable bushings at the rear of the connection component M16 or M20 for example 4 Thread all cables to be connected thro...

Страница 12: ...44 E1 E1 Contact water meter Factory provided 45 E2 Insufficient water switch E2 LSL 51 GND 52 24 V supply 53 0 10 V correcting variable 54 0 10 V feedback 55 GND Pressure relief valve control ball va...

Страница 13: ...on in the Maintenance certificate see chapter 10 5 Maintenance certificate on page 24 For the installation Place date Company Signature For the commissioning Place date Company Signature 7 Commissioni...

Страница 14: ...height 18 m run on temperature 70 C 158 F safety temperature 100 C 212 F Example calculation for suction pressure maintenance P0 pst pD 0 2 bar pst hst 10 pst 18 m 10 pst 1 8 bar pD 0 0 bar at a safet...

Страница 15: ...the VT vacuum spray pipe The venting screw at the PU pump 8 After successful conclusion of the vacuum test open the ball valve 2 9 If the controller displays the Insufficient water error message ackno...

Страница 16: ...ure relief valve WV1 Safe Control make up valve MKH3 Opening closing of tank spray pipe to the system The change in the filling level and the tank pressure are indicated on the display Note Manual ope...

Страница 17: ...ully calibrated 9 3 Modifying the controller s start routine Note For handling the operator panel see chapter 9 1 Operator panel on page 17 The start routine is used to set the required parameters for...

Страница 18: ...ccessfully completed you cannot commission the device In this case please contact Customer Service see chapter 12 1 Reflex Customer Service on page 25 9 Once null balancing has concluded successfully...

Страница 19: ...ress X to cancel your input without saving the new settings The controller automatically opens again the list 9 3 2 Service menu This menu is protected with a password It can be accessed only by the R...

Страница 20: ...24 hours The times for interval degassing are stored in the Service menu Daily start of interval degassing is at 8 00 a m Note Manual activation of the degassing program takes place in the customer me...

Страница 21: ...valve does not open Check set value in the Customer or Service menu Clean the dirt trap Check functioning of the PV1 solenoid valve If necessary manually add water 03 High water YES Set value exceeded...

Страница 22: ...and reset the maintenance counter upon completion Quit 24 Replace cartridge Set value for soft water capacity exceeded Replace cartridges Set soft water capacity Quit 25 Datalogger No SD card inserte...

Страница 23: ...ng the dirt trap on page 23 Annually Clean the dirt trap see chapter 9 3 1 Customer menu on page 18 Depending on the operating conditions Check the controller settings see chapter 9 3 3 Default settin...

Страница 24: ...13 Level sensor at the primary tank Preparation 1 Switch to Automatic mode 2 Close the cap valves upstream of the tanks and the EC expansion lines 3 Record the displayed filling level value in 4 Drain...

Страница 25: ...hot medium can cause burns Maintain a sufficient distance from the escaping medium Wear suitable personal protective equipment safety gloves and goggles CAUTION Risk of burns on hot surfaces Hot surf...

Страница 26: ...SI1870enC 9127065 01 21 Reflex Winkelmann GmbH Gersteinstra e 19 59227 Ahlen Germany 49 0 2382 7069 0 49 0 2382 7069 9546 www reflex winkelmann com...

Отзывы: