Reflex Servimat L Скачать руководство пользователя страница 12

Installation 

12 

  English  

Servimat M/L — 28.01.2021

 

Terminal 
number 

Signal 

Function 

Wiring 

10 

Y3 

3-way motorized ball valve

Factory-
provided 

11 

N  

12 

PE  

13 

Dry-run protection message 
(floating) 

User supplied 

14 
15 

M1 

PU 1 pump 

Factory-
provided 

16 

N  

17 

PE  

18 

M2 

--- 

--- 

19 

N  

20 

PE  

21 

FB1 

Pump 1 voltage monitoring 

Factory-
provided 

22a 

FB2a  

Pump 2 voltage monitoring 

Factory-
provided 

22b 

FB2b  

External make-up request 
together with 22a 

Factory-
provided 

23 

NC  

Group message (floating) 

User supplied 

24 

COM  

25 

NO 

27 

M1 

Flat plug for supply, pump 1 

Factory-
provided 

31 

M2 

Flat plug for supply, pump 2 

Factory-
provided 

35 

+18 V (blue) 

Analogue input, LIS level 
measuring 
at the primary tank 

User supplied 

36 

GND 

37 

AE (brown)  

38 

PE (shield) 

39 

+18 V (blue) 

Analogue input, "PIS" pressure 
measuring  
at the primary tank 

User, optional 

40 

GND 

41 

AE (brown)  

42 

PE (shield) 

43 

+24 V

Digital inputs 

User, optional 

44 

E1 

E1: Contact water meter 

Factory-
provided 

45 

E2 

Insufficient water switch E2 
(LSL) 

--- 

51 

GND 

--- 

--- 

52 

+24 V (supply)

53 

 10 V 

(correcting 
variable) 

54 

 10 V 

(feedback)  

55 

GND 

Pressure relief valve (control 
ball valve RKH1) 

Factory-
provided 

56 

+24 V (supply)

57 

 10 V 

(correcting 
variable) 

58 

 10 V 

(feedback) 

6.4.2

Terminal plan, operating unit 

RS-485 interfaces 

I/O interface 

I/O interface (reserve) 

Micro SD card 

10 V supply 

Analogue outputs for Pressure and Level 

Battery compartment 

Bus module supply voltage 

RS

485 connection 

10 

RS

485 connection 

Terminal number 

Signal 

Function 

Wiring 

RS-485 interface 
S1 networking 

User 
supplied 

GND S1 

RS-485 interface 
S2 modules: Expansion or 
communication module 

User 
supplied 

6  

GND S2 

+5 V

I/O interface: Interface to the 

main board 

Factory 

R × D  

T × D  

10 

GND IO1 

11 

+5 V 

I/O interface: Interface to the 
main board 
(reserve) 

--- 

12 

R × D  

13 

T × D 

14 

GND IO2 

15 

10 V~  

10 V supply 

Factory 

16 
17 

FE 

18 

Y2PE 
(shielding) 

Analogue outputs: Pressure 

and Level 

Standard 4 

 20 mA 

User 
supplied 

19 

Pressure  

20 

GNDA  

21 

Level  

22 

GNDA 

Содержание Servimat L

Страница 1: ...Servimat M L 09 04 2019 Pressure maintenance with degassing GB Operating manual Original operating manual...

Страница 2: ...nstallation and commissioning certificate 13 7 Commissioning 13 7 1 Checking the requirements for commissioning 13 7 2 Determining the P0 minimum operating pressure for the controller 13 7 3 Filling t...

Страница 3: ...ice on page 25 3 Safety 3 1 Explanation of symbols The following symbols and signal words are used in this operating manual DANGER Danger of death and or serious damage to health The sign in combinati...

Страница 4: ...afety clothing gloves and goggles for example 4 Description of the device 4 1 Description The Servimat is a pump controlled pressure maintaining make up and degassing station for heating and cooling w...

Страница 5: ...water from the primary tank back into the system The pressure in the facility system rises The controller ensures that the pressure is maintained further supported by the stabilisation provided by th...

Страница 6: ...ontent is shown on the packing Immediately after receipt of the goods please check the shipment for completeness and damage Please notify us immediately of any transport damage Basic pressure maintena...

Страница 7: ...54 G1 1360 146 6 bar 400 740 65 G1 1345 133 Type D mm Weight kg Connection inches H mm h mm 6 bar 500 740 78 G1 1560 133 6 bar 600 740 94 G1 1810 133 6 bar 800 740 149 G1 2275 133 6 bar 1000 740 740...

Страница 8: ...ATTENTION Damage due to improper installation Additional device stresses may arise due to the connection of pipes or system equipment Ensure that pipes are connected from the device to the system wit...

Страница 9: ...tank Ensure that you connect the connection set for the overflow collector to the connection 2 below the label 1 Interchanging the connections may cause the pump to run dry For tanks up to 740 mm Con...

Страница 10: ...mal insulation when condensate forms 6 3 6 Fitting the level sensor ATTENTION Damage to the pressure load cell due to unprofessional installation Incorrect installation may result in damage to the LIS...

Страница 11: ...ain circuit board is voltage free 3 Insert a suitable screwed cable gland for the cable bushings at the rear of the connection component M16 or M20 for example 4 Thread all cables to be connected thro...

Страница 12: ...44 E1 E1 Contact water meter Factory provided 45 E2 Insufficient water switch E2 LSL 51 GND 52 24 V supply 53 0 10 V correcting variable 54 0 10 V feedback 55 GND Pressure relief valve control ball va...

Страница 13: ...on in the Maintenance certificate see chapter 10 5 Maintenance certificate on page 24 For the installation Place date Company Signature For the commissioning Place date Company Signature 7 Commissioni...

Страница 14: ...height 18 m run on temperature 70 C 158 F safety temperature 100 C 212 F Example calculation for suction pressure maintenance P0 pst pD 0 2 bar pst hst 10 pst 18 m 10 pst 1 8 bar pD 0 0 bar at a safet...

Страница 15: ...the VT vacuum spray pipe The venting screw at the PU pump 8 After successful conclusion of the vacuum test open the ball valve 2 9 If the controller displays the Insufficient water error message ackno...

Страница 16: ...ure relief valve WV1 Safe Control make up valve MKH3 Opening closing of tank spray pipe to the system The change in the filling level and the tank pressure are indicated on the display Note Manual ope...

Страница 17: ...ully calibrated 9 3 Modifying the controller s start routine Note For handling the operator panel see chapter 9 1 Operator panel on page 17 The start routine is used to set the required parameters for...

Страница 18: ...ccessfully completed you cannot commission the device In this case please contact Customer Service see chapter 12 1 Reflex Customer Service on page 25 9 Once null balancing has concluded successfully...

Страница 19: ...ress X to cancel your input without saving the new settings The controller automatically opens again the list 9 3 2 Service menu This menu is protected with a password It can be accessed only by the R...

Страница 20: ...24 hours The times for interval degassing are stored in the Service menu Daily start of interval degassing is at 8 00 a m Note Manual activation of the degassing program takes place in the customer me...

Страница 21: ...valve does not open Check set value in the Customer or Service menu Clean the dirt trap Check functioning of the PV1 solenoid valve If necessary manually add water 03 High water YES Set value exceeded...

Страница 22: ...and reset the maintenance counter upon completion Quit 24 Replace cartridge Set value for soft water capacity exceeded Replace cartridges Set soft water capacity Quit 25 Datalogger No SD card inserte...

Страница 23: ...ng the dirt trap on page 23 Annually Clean the dirt trap see chapter 9 3 1 Customer menu on page 18 Depending on the operating conditions Check the controller settings see chapter 9 3 3 Default settin...

Страница 24: ...13 Level sensor at the primary tank Preparation 1 Switch to Automatic mode 2 Close the cap valves upstream of the tanks and the EC expansion lines 3 Record the displayed filling level value in 4 Drain...

Страница 25: ...hot medium can cause burns Maintain a sufficient distance from the escaping medium Wear suitable personal protective equipment safety gloves and goggles CAUTION Risk of burns on hot surfaces Hot surf...

Страница 26: ...SI1870enC 9127065 01 21 Reflex Winkelmann GmbH Gersteinstra e 19 59227 Ahlen Germany 49 0 2382 7069 0 49 0 2382 7069 9546 www reflex winkelmann com...

Отзывы: