background image

0

The pressure reducer of reflex ’fillcontrol’ is factory-set to 3.0 bar.

 

System-specific setting pressure between:

At least:  

 p

0

 + 0.5 bar

and
at most:  

 Final pressure of the system (Pick-up pressure of the safety valve – 0.5 bar)

The pressure reducer can be set as follows:

Remove insulation of reflex ’fillcontrol’.

-  

Ensure that the inlet pressure is at least 1.3 bar higher than the desired outlet pressure p

0

.

To change the pressure setting, pull the adjustment knob downwards and unlock it.

To increase the outlet pressure, turn the pressure adjustment knob clockwise and counterclockwi-
se to reduce it.

The selected pressure can be read on the manometer (→ p.3 No. 6).

After the desired pressure is set, push the pressure adjustment knob upwards to lock it into place 
again.

Disassemble the test manometer.

GB

Igångkörning av systemet/ 
Initial filling of the system

För att fylla systemet håll in      - ner knappen samtidigt som du trycker på       - upp knappen 3 gånger inom två   
sekunder. Lysdiod "III" lyser nu grönt och påfyllningen har startats. Det ska vara klart inom 2 timmar eller när 
"Mode" knappen har blivit tryckt på 2 gånger. (observera: Efter första trycket kommer E2 meddelandet upp)
Lysdiod "Auto" är grön, om fyllningstiden överstiger två timmar tror systemet att det finns ett läckage och ett
felmeddelande kommer fram i displayen

 (→ S.12).

Under systemets fyllningstid skall trycket kvarstå

 (→ S.8)

.

(Driftövervakningen/Larmet är avaktiverat under tiden). 

Viktigt! :  Uppfyllningen av systemet kan endast startas om det aktuella trycket är satt  
   lägre än p

0

! värdet.

For the initial filling of the system, press and hold the

key and press the

key three times within two 

seconds. The LED „III“ (filling time) lights up and the filling starts. It is completed either after 2 hours, or 
when the „Mode“ key is pressed for two times (Attention: After the first pressing the message E2 occurs). 
The LED „Auto“ is green. If the filling time exceeds 2 hours, the system considers that there is a leakage 

and an error message appears (→ p.12).

Throughout system filling time the set pressure is maintained (→ p.8).

(The operation time surveillance and the cyle monitoring are deactivated during this time). 

Important!: The filling of the system can only be started, if the actual pressure set is lower  

 

   

      than the p

0

 value!

S

GB

Rengörning av smutsfiltret/

 

Cleaning dirt trap

Smutsfiltret

 (→ S.3, Nr. 7) 

måste rengöras!

 (→ 

Underhålls instruktionen

). 

sätt tillbaka isoleringen

 

 

efter rengörningen.

The dirt trap (

S.3,  No. 7) has to be cleaned! (→ Maintenance instruction). Install insulation after clea

-

ning.

S

GB

reflex ’påfyllningsstation’ 
Inför igångkörning/
Initial start-up

Содержание fillcontrol

Страница 1: ...reflex fillcontrol reflex p fyllningsstation Water make up device Installation Drift och sk tselanvisningar Installation operation and maintenance instructions Stand Status 04 06...

Страница 2: ...lectrical connection 7 Terminal connection diagram 7 Initial start up Prerequisites for initial start up 8 Steps of initial start up 8 System dependent setting 8 9 Pressure reducer setting 9 10 Parame...

Страница 3: ...us Access menus Quit error messages Upp ner val knappar Up Down operation selection buttons 1 Avst ngning Shut off 2 Tryck givare Pressure sensor 3 Kontroll panel Control Control panel 4 Motor kulvent...

Страница 4: ...cal data are provided on the type plate or the markings on the valve Make sure to fully comply with the service parameters of tempera ture and pressure protection do not remain under these values and...

Страница 5: ...off system separator type BA acc to DIN EN 1717 tundish dirt trap mano meter connections motor operated ball valve control unit pressure sensor manometer and pressure reducer acc to DIN EN 1567 Adjus...

Страница 6: ...the connecting pipe of the reflex fillcontrol make sure that stagnation is excluded The down stream pipe has to be passed in a way length nominal width that the the loss of pressure in this pipe is 0...

Страница 7: ...power supply Kopplings schema Terminal connection diagram Givare Transducer Tryckgivare 3 pols anslutning PH Str mf rs rjd tryckgivare Jord tryckgivare Signal tryckgivare fr nh gertillv nster Pressure...

Страница 8: ...ometern har blivit installerad p reduceringsventilen fabriks monterad fr n approx 06 06 Installation reflex fillcontrol is completed The connection on the water side of the system and to the refill wa...

Страница 9: ...e knappen igen i 4 sekunder s kommer lysdiod I Tryck blinka var 0 5 sekund Det inst llda trycket visas nu i displayen f r att st lla in r tt v rde p0 s f r man justera det genom att trycka p ner eller...

Страница 10: ...fyllningstiden verstiger tv timmar tror systemet att det finns ett l ckage och ett felmeddelande kommer fram i displayen S 12 Under systemets fyllningstid skall trycket kvarst S 8 Drift vervakningen...

Страница 11: ...low the setting value if the second value is exeeded reflex fillcontrol is turned off p 8 During the LED Auto is green and at the same time the LED IV is red The operation time and the number of cycle...

Страница 12: ...ppen i 3 sek E3 Auto blinkar r tt Osannolikt tryck signal och eller motorn terg r inte till noll l ge och eller internt systemfel ROM och eller internt systemfel EE Flera Olika Informera Reflex servic...

Страница 13: ...nande vatten Kolla s att O ringen och t tningarna r intakta reng r eller byt ut om det r n dv ndigt Underh ll reduceringsventil Reduceringsventilen m ste testas med j mna mellanrum minst en g ng per r...

Страница 14: ...rating conditions but after one year at the latest The connections available for ball valves allow a functionality test of the device to be carried out with an adequate pressure gauge Dirt trap Isolat...

Страница 15: ...r Inspection report no ECL SAF TR 05 071 V01 00 Pr finstitut Labor Inspection body inspection institiute Herberg Service Plus GmbH N rnberg EMV Richtlinie EMV directive EN 55014 1 und 55014 2 Category...

Страница 16: ...ical modifications Reflex Winkelmann GmbH Co KG Gersteinstrasse 19 59227 Ahlen Germany Telefon 49 23 82 70 69 0 Telefax 49 23 82 70 69 588 www reflex de Somatherm AB Bang rdsgatan 1 Box 900 671 29 ARV...

Отзывы: