8 Electrical connections
64 of 80
FlexiMova
®
mm - Design and Installation
8.6.2
Connection of the braking resistor
If the application requires the use of the braking resistor (requiring
dynamics or rapid decelerations) the product must be connected as
illustrated in
Figure 34
, and comply with the resistance values specified
for each size. The braking resistor must be connected between the “+”
terminal and the “BR” terminal.
Cabling of this component is the responsibility of the installer who
must use suitable cables and comply with the specified resistance
values.
Figure 34
: Connection of the braking resistor
Braking resistor with protection
and overuse signal device
Protection signal to safely shut
down the converter
No.
Denomination
No.
Denomination
1
Mains connection
4
Brake and DC link
2
Motor connection
5
Motor PTC: only PTC with double insulation
3
PTC connection
6
Jumper for IT network
Be careful with the braking resistor connections.
Hot surfaces: residual risk
No. 6
exists
(see par. 5.12)
.
WARNING