35
Examples:
“Pump” keypad switch
(press to activate, press again to deactivat e)
Used to activate pumpout circuit which includes:
pumpout compressor C2
pumpout solenoid valves L1 and L2
Pumpout Relay RY2, with its associated LED indicator
Displayed:
Diagnostics Mode
OUTPUTS = P
“Drain” keypad switch
(press to activate, press again to deactivate)
Used to activate drain circuit which includes:
drain solenoid valve L3
Drain Relay RY3, with its associated LED
Displayed:
Diagnostics Mode
OUTPUTS = D
“Compressor” keypad switch
(press to activate, press again to deactivate)
Used to activate compressor circuit which includes:
compressor C1
Compressor RY1, with its associated LED indicator
Displayed:
Diagnostics Mode
OUTPUTS = C
“Alarm” keypad switch
(press to activate, press again to deactivate)
Used to activate the remote alarm relay RY7:
relay RY7 is activated
Displayed:
Diagnostics Mode
OUTPUTS = A
“AUX VALVE” keypad switch (Used only with R-113 purge units)
(press to activate, press
again to deactivate)
Used to activate the pump bypass relay RY4:
relay RY4 is activated