Exiting Fault “BYPASS” Mode
The Fault “BYPASS” mode can be exited at any time by again pressing the Fault “BYPASS”
Switch.
The recommended "FAULT Bypass time" setting is 4 hours.
NOTE:
When in this mode the display will alternate betw een the “Fault Bypassed” display
and the current operating mode. The purge may also alternate between other
displays, which will be self explanatory.
NOTE:
Pumpout time that occurs while in the Fault “Bypass” mode is not added to 30 -Day
averages, but is added only to cumulative pumpout time.
The last 24 hour pumpout
time and display will reset to zero and will remain at zero during the bypass
period
.
WARNING:
Since the purge unit has NO “Purge Fault” protection when in the
“Bypass” TIME PERIOD, the Fault “Bypass” mode should be used sparingly, and only
if purge system is in proper working order.
“
DIAG
.” Keypad
Switch
The “DIAG” mode can only be accessed by pressing the “DIAG” keypad switch, then
immediately entering access code number
“47”
.
NOTE
: All purge unit activity ceases when in the Diagnostic mode. This allows the purge
operator to perform various “isolated” diagnostic tests. The “SENSORS” keypad
switch may also be used while in the diagnostic mode.
The “DIAG” keypad switch is used to test the Compressor, Pump, Drain, and Remote Alarm
circuits and may be used in conjunction with the SENSORS display keypad switch for purge
analysis. Any one output or combination of outputs may be selected simultaneously.
Displayed:
Diagnostics Mode
OUTPUTS =
One or more of the following:
C
for Compressor
P
for Pump
D
for Drain
A
for Alarm
B
for Auxiliary Relay (R-113 purge unit only)