Chapter 9
page 48
Menu structure
Technical dept. - All rights reserved - Reproduction prohibited
9.2.3.
Back light
This setting enables or disables the automatic switch-off of the backlit display.
9.2.4.
Tone (Panel display: ON-OFF)
This setting disables the sound when keys are pressed. It does not affect the alarm signals.
9.2.5.
°C/°F
This setting allows the user to select the temperature measurement unit (°C or °F).
9.2.6.
Recipe selection procedure
This function is designed to optimise the boiler filling according to the type of pellet being used. Indeed,
since many different types of pellet are available on the market, the boiler operation may be affected by the
filling variability due to the different physical characteristics of the fuel. If the pellet tends to clog up the
brazier due to a fuel filling excess or due to the poor quality of the fuel itself, or if the flame is too low even
at high power, the supply of pellets into the brazier can be decreased/increased:
1.
Press the top right key “
D
” in the display to enter the menu
2.
Using the two keys at the bottom “
F
” and “
C
”, scroll through the various menus until you reach the
SETTINGS
menu.
3.
Press key “
D
” corresponding to the word
SET
.
4.
Using the two keys at the bottom “
F
” and “
C
”, scroll through the various menus until you reach the
PELLET RECIPE
menu.
5.
Confirm by pressing key “
D
” corresponding to the word
SET
.
6.
Modify the value using the bottom keys “
F
” and “
C
” corresponding to the symbols
+
and
–
7.
Confirm by pressing key “
D
” corresponding to the
OK
key.
Each time the value is increased/decreased by a 5% filling at all flame levels
9.2.7.
Smoke Blower Offset
This function is designed to modify the speed of the blower in order to adapt the flow rate of air for
combustion depending on the different fuels and on the different characteristics of the smoke outlet ducts.
Each time the value is increased/decreased by a 5% filling at all flame levels
9.2.8.
Puffer / EC Pump
Enable this function to modify the logical management of the pump to adapt it if a puffer or high efficiency
pump is installed.