17 - SAFETY DEVICES AND ALARMS
Technical Dept. - All rights reserved - Reproduction prohibited
ALARM SIGNALLING
When a condition occurs other than the one expected for regular operation of the boiler, an alarm is triggered.
The reason for the alarm is given on the control panel. The sound signal is not enabled for alarms A01-A02 in order not to disturb the user
when there is an absence of pellets in the night tank.
Panel signalling
type of problem
Solution
A01
The fire does not ignite.
Check the level of pellets in the hopper.
Check that the brazier is correctly positioned in its
seat and has no build-up or unburned material.
Make sure the spark plug warms up.
Thoroughly empty and clean the brazier before
restarting.
A02
The fire goes out abnormally.
Check the level of pellets in the tank.
A03
Thermostats alarm
The temperature of the pellet tank or the water
temperature exceed the envisaged safety
threshold.
Wait until the end of the cooling phase, stop the
alarm and re-ignite the boiler setting the supply of
fuel to minimum (SETTINGS menu - pellet recipe). If
the alarm persists, contact the service centre.
Check whether the room fan is working correctly (if
there is one).
A04
Smoke overtemperature.
The set smoke threshold has been exceeded. Reduce
the load of pellets (SETTINGS menu - Pellet recipe).
A05
Pressure switch alarm
Fumes pressure switch intervention or water
pressure insufficient.
Check for chimney obstructions / door open or the
pressure of the hydraulic system.
A08
Anomalous operation of smoke fan.
If the alarm persists, contact the service centre.
A09
Fault with the smoke sensor.
If the alarm persists, contact the service centre.
A19
Fault with water sensor.
Water sensor detached / interrupted / defective / not
recognised.
A20
Puffer probe alarm.
Puffer probe detached / interrupted / defective / not
recognised.
Service
Routine maintenance warning (does not seize) When this blinking message appears upon start-up, it
means it is time to carry out scheduled maintenance.
Call the assistance centre.
ALARM RESET
NEVER open the stove door whilst it is either in the initial start-up or on its shut down cycle, pellets will still be
smoldering or therefore volatiles may be present.
ATTENTION!
If during operation or initial ignition you encounter combustion smoke spillage in to the room from the appliance
or the flue then please switch off the appliance, ventilate the room and contact the installation / service technician
immediately.